Sunteți pe pagina 1din 10

Loop Installation

and
Operating Instructions

P.O. Box 403, One Cedar Parkway, Jackson, WI 53037


Phone: 800-628-1909 Fax: 262-677-2058

Revision: December 9, 2002


Contents

Introduction 3

How to use manual 4

Loop Layout 4

Loop Installation 6
Installation Considerations 6
Test Loop 6

Detector Set Up 8
Sensitivity Adjustment 8
Presence Mode 9
Frequency 9
LED Display 9
Connections/Outputs 9

Loop Troubleshooting 10

2
Introduction
DO NOT INSTALL, OPERATE, OR
A loop is a metal detector that is PERFORM MAINTENANCE ON
used as an activator to open doors. It THIS LOOP UNTIL YOU READ AND
consists of a number of turns of wire UNDERSTAND THE
connected to a loop detector. A field INSTRUCTIONS IN THIS MANUAL.
is created around the wire. A vehicle
passing near the wire will change the If you have any questions, contact
field. The loop detector senses the your Rytec representative or call the
change and sends a signal to the Rytec Customer Support Department
door controller to open the door. at 800-628-1909. Always refer to the
serial number of the door that your
A loop is made up of a saw cut in the floor loop is connected to when
floor near the door. A length of wire calling the representative or
is installed in the saw cut and sealed Customer Support. Refer to the
in place. The size and location of the installation manual or the owner’s
loop, the number of turns of wire manual provided with your door for
used and some of the detector the location of the serial number
settings will vary from one plate.
application to the next.
The wiring connections and
This instruction book will explain schematics in this manual are for
installation, operation and general information purposes only. A
troubleshooting of loops. wiring schematic is provided with
each individual door specifically
NOTE: This manual is intended for the Loop covering the control panel and
Detector only. Installation and operation electrical components of that door.
information specific to your door is detailed
in the Installation, Owner’s and System 3
That schematic was shipped inside
Drive and Control manuals that were the control panel.
shipped with the door.
All electrical and mechanical work
The installation and operation of the must be performed in accordance
loop is not difficult providing you with local and state building codes by
follow the procedures outlined in this qualified installers and electricians.
manual. Any unauthorized changes
to these procedures, or failure to This product is covered by the Rytec
follow the steps as outlined, will door warranty. The warranty is in the
automatically void our warranty. Any door owner’s manual.
changes to the working parts,
assemblies, or specifications as
written, not authorized by Rytec
Corporation, will also cancel our How to use manual
warranty. The responsibility for the
successful operation and Throughout this manual, the
performance of this loop lies with the following key words are used to alert
owner of the door. the reader of potentially hazardous

3
situations, or situations where
additional information to successfully
Floor Loop Wall
perform the procedure is presented:

WARNING is used to indicate the


potential for personal injury, if the Door Wall
procedure is not performed as described.

Figure 1

Figure 2 shows a double loop layout.


CAUTION is used to indicate the
It is used on doors where metal is a
potential for damage to the product or part of the door panel, for example
property damage, if the procedure is not roll doors with metal bottom bars. It
followed as described. is also used in applications where
there is an expansion joint in the
IMPORTANT: IMPORTANT is used to floor in the door area and you don’t
relay information CRITICAL to the want to cut through the expansion
successful completion of the procedure.
joint.
NOTE: NOTE is used to provide additional
information to aid in the performance of the Double Loop
procedure or operation of the door, but not
necessarily safety related.
Door
Wall
Loop layout

There are a number of loop layouts


that can be used. Figure 1 shows a
single loop layout. It can be used on
doors without metal parts on the Floor Loop
door panels.
Figure 2

A double loop layout consists of two


individual loops. The loops should be
the same size or within 25% of each
other in size. They should be an
equal distance from the metal parts
Single Loop of the door panel. We suggest 18”.
Also the two individual loops should
be connected in parallel at the
control box.

The rectangle is a common shape


used for a loop. Figure 3 shows

4
some things to consider when laying detect high bed vehicles better than
out a rectangular loop. a 1-1/2’ wide loop. See figure 4.

Height increases as Field


the length of the Height
short leg increases

Long Leg

Short Leg Figure 4

There are times when cross traffic


will cause problems with a standard
Figure 3
rectangular loop extending out from
The long leg is generally the distance the door. Target loops, which are
away from the door. It should extend small loops located in a specific
away from the door far enough to area, may help solve these
allow the door to open before the problems. See figure 5.
vehicle reaches the door. The
Target Loop
following formula can be used to Door
calculate the ideal distance the loop
should extend away from the door.
Door opening time in seconds
multiplied by the speed of the
approaching vehicle in mph Cross
multiplied by 1.47 (1.47 converts Traffic
mph to ft per sec) equals the ideal Wall
distance away from the door. The
loop should not be longer than this. If Figure 5
it is shorter traffic will need to slow to
increase safety.

The short leg of the loop should be


between 1-1/2’ and 7’. The loop Loop Installation
should be slightly smaller than the
vehicles being detected. Small Loops are generally installed by saw
vehicles may be lost in the field if the cutting the floor, installing wire and
loop is too wide. Another sealing the wire into the cut. There
consideration is that field height is are also preformed loops available in
related to the width of the loop. The various sizes that can be installed
wider the loop the higher the field is during the installation of new floors.
above the loop. A 6’ wide loop will

5
Before installing the loop make sure If there is any doubt about the
the customer and dealer agree on potential operation of a loop, install a
the layout. Each application is temporary loop on the floor before
different and many variables can cutting the floor. Use the correct
affect the operation of the loop. number of wraps of wire, tape the
wire to the floor and protect the wire.
Installation Considerations Test with and without a typical
vehicle. Also test the loop by turning
There are a number of things that on electrical equipment such as heat
can cause problems with loop mats that are in the area. See the
operation. Avoid the following following instructions for the correct
situations if possible. number of wraps. Refer to the
schematic supplied with the door
Avoid installing the loop wires when making connections.
directly on metal objects such as
reinforcing steel, conduits or pipes Layout the loop on the floor.
that are in the floor. Loop wires
should be a minimum 2” above metal
objects in the floor. Never run loop
wires below metal objects. Metal Check the floor for wires, heat mats or
objects running at right angles to the other hidden obstructions before cutting
loop wires will have less effect on the concrete. Follow the saw operating
procedures as outlined by the saw
loop operation than metal running
manufacturer.
parallel to the loop wires.
Cut the floor using the proper saw
Electrical cables or heat mats may and blade. A walk behind saw with a
cause false impulses to the loop diamond, carbide or abrasive saw
resulting in erratic operation. Avoid blade could be used. The groove
installing loops around these objects. should be 3/16” to 1/4” wide by 1-
1/2” to 2” deep.
If there are steel inspection covers or
grids such as manhole covers in the Cut the loop as it is laid out on the
area of the loop, sensitivity may be floor. Miter the corners. Avoid
reduced. Also a cover may move corners of less than 90 degrees.
due to vibration or traffic away from They put more strain on the wire and
the door. The movement could be may cause a highly sensitive area in
sensed by the loop causing the door the loop. The feeder slot allows the
to open when it shouldn’t. ends of the loop wire to run to the
control box. It may have to be cut
Test Loop
wider to allow for the twists in the
feeder wire. See figure 6.

The disconnect must be in the “OFF”


position and properly locked and tagged
before connecting the loop wires.

6
slot. Wrap the wire around the loop
the correct number of times. Twist
the feeder wire a minimum of 5
Feeder Slot twists per foot. The twists must
extend back to the control box.
Failure to twist the wire may result in
erratic loop operation. The feeder
Miter Corners
wires can be routed to the control
box in conduit after they leave the
Figure 6 feeder slot cut in the floor. See figure
8.
Clean and dry the slot in the floor.

Determine the number of turns of Feeder Wire


wire that should go into the loop. A Figure 8
loop is one continuous piece of wire
wrapped around the slot in the floor Splicing the wire or feeder is not
a number of times. Using the wrong recommended. If splicing is required
number of turns could affect the the joint must be soldered and
sensitivity of the loop. See the chart waterproofed.
in Figure 7.
If the loop is installed over an
expansion joint or crack in the floor
leave a loop in the wire at that point.
The extra wire will allow the floor to
move without breaking the wire. The
saw cut may have to be expanded at
that point to allow for the extra wire.
Figure 7

The wire used should have a rating


for direct burial. Use a wire with The disconnect must be in the “OFF”
waterproof and abrasion resistant position and properly locked and tagged
before connecting the loop wires.
insulation. If moisture penetrates the
insulation due to poor insulation or To ensure that there are no
damage during installation the loop problems with the loop connect the
operation may be affected. The wire feeder wires to the terminal strip in
should be 16 gauge, 19 strand the control box and test the loop
copper with crosslink polyethylene operation before sealing the slot in
insulation (XLPE) or equivalent. the floor. If you have two loops they
are connected in parallel. Refer to
Install the wire in the slot. Allow the schematic supplied with the door
enough wire for the feeder wire. The when making connections. See the
feeder wire will extend from the loop section on loop detector set up if
to the control box. Do not damage or required.
twist the wire when it is placed in the

7
Fill the slot in the floor. The wires Channel 2

must be tight in the slot. If the wires Service Connector

are loose vibration may cause false Green LED

activation of the loop. Use backer Red LED


8 Frequency
7 Presence Mode
rod and sealant suitable for the 6 Sensitivity B
5 Sensitivity A
application. Backer rod is a foam rod 4 Frequency
3 Presence Mode
sized to fit snug in the slot. It holds 2 Sensitivity B
1 Sensitivity A
the wire tight in the slot but will flex Green LED

slightly if the floor shifts. The backer Red LED

rod is installed over the wire and the


sealant over the backer rod. The
sealant should be somewhat flexible Channel 1

when cured but not soft enough to


allow debris to be pushed through to Figure 10
the wire. The sealant should be
Bondo P606 sealer or equivalent. Sensitivity Adjustment
Bondo speed set P610 is added if
the loop is installed in a cold The sensitivity adjustment allows you
temperature (below freezing). Figure to determine how much a vehicle
9 shows wires sealed in the saw cut. has to change the loop field before
the door will open. A higher
sensitivity may be necessary to pick
up smaller vehicles like bicycles
while a lower setting will work for
large fork trucks. Keep the setting as
low as possible but high enough to
pick up traffic passing through the
door. If it set too high there may be
Figure 9 false tripping of the loop. See figure
11 for sensitivity adjustments.
The loop should be ready for
operation. Refer to the schematic
supplied with the door when making Sensitivity level Channel 1: DIP-
connections. Adjust the detector as switch 1, 2
required. See Detector Set Up. Channel 2: DIP-
switch 5, 6
Detector Set Up 1 Low (0,27% ∆f/f) ON
1 8

OFF/OFF
2 (0,09% ∆f/f) ON

Figure 10 shows an overview of the 1

ON/OFF
8

loop detector. The detector shown is


3 (0,03% ∆f/f) ON

a 2-channel detector. A 1-channel


1 8

OFF/ON
detector will only have dip switches 4 High (0,01% ∆f/f) ON
1 8
1 – 4 and one red and one green ON/ON
LED. Settings are separate but
adjusted the same way for both Figure 11
detectors.
Presence Mode

8
The LED’s on the detector indicate
This setting allows you to determine various operating conditions of the
how long a vehicle can be parked on detector. The green LED indicates
the loop before the detector tunes the detector is operable. The red
the vehicle out and the door closes. LED indicates the loop is activated.
Possible settings are 5 minutes or See figure 14 for the various
infinite. If the detector is set for 5 conditions.
minutes a vehicle parked on the loop
for more than 5 minutes will no Green LED Red LED Detector
longer be detected and the door will Condition
close. See figure 12 for settings. Off Off No supply
voltage
Holding time Channel 1: DIP- Flashes Off Indicates loop
switch 3 frequency – at
Channel 2: DIP- start-up
switch 7 On Off Detector ready,
5 minutes ON
1 8 nothing detected
OFF
On On Detector ready,
infinite
ON
1 8 ON vehicle detected
Off On Problem with
Figure 12 wiring in floor

Frequency
Figure 14

Crosstalk can happen between Connections/Outputs


adjacent loops. During crosstalk the
operation of one loop interferes with The input and output connections of
the operation of a loop close to it. the loop detector are done through
Frequency settings are used to allow plug-in connectors on the detector
2 loops installed close to each to and main control circuit board. Floor
work properly. The frequency wiring connects to a terminal strip in
settings of the 2 loop detectors the control box.
should be different. Use figure 13 to
adjust the frequency. Loop Troubleshooting

Frequency Channel 1: DIP- If there is a problem with loop


switch 4 operation check the following:
Channel 2: DIP-
switch 8
Determine if the detector operates
low ON
1 8
properly.
OFF
high
ON
1 8 ON If the detector is good and/or the
detector LED’s indicate a problem
Figure 13 with the in floor wiring troubleshoot
LED-Display
the floor wiring.

9
Look for loose connections in the
control box or damage to the wire
above the floor.

Check the wiring under the floor with


an insulation tester or Meg
Ohmmeter. A meg ohmmeter is
capable of pushing high voltage
through the wire, which will bleed
Figure 17
through abrasions or cuts to ground.
A standard meter is not capable of Check for leakage between the wire
pushing the high voltage. and floor. Scratch the concrete and
measure between the floor and the
Check for continuity. Remove the wire. If the reading is anything but
feeder wires from the terminal strip. maximum indicates leakage. See
See figure 15. figure 18.

Remove Floor
Wires
.
Figure 15

Measure continuity between the two


wires. The meter reading should be
near zero. The wire will have some
Floor
resistance. A broken wire will show
very high resistance. See figure 16.
Figure 18

If you found leakage or a broken wire


you most likely will have to replace
the in floor wiring.
If wire is not
broken meter
should read
near zero
Figure 16

If the wire is not broken check for


leakage to the conduit. There should
be no leakage. See figure 17.

10

S-ar putea să vă placă și