Contents As well as giving the basis of design there is an Annex that covers
Introduction the situation with respect to conformity with Building Regulations in
the United Kingdom.
1. Scope
It does not cover curved glass when used in the above applications.
2. Definitions and descriptions
2. Definitions and Descriptions
3. Design considerations
NOTE: Definitions 2.1.1, 2.1.2, 2.1.3 and Figure 1 are reproduced
4. Design criteria
from the appropriate Building Regulations eg Approved Document K.
5. Barrier types
2.1 Definitions
6. Glass types
2.1.1 Barrier
7. Installation
Any element of building or structure intended to prevent persons
Bibliography from falling and to retain, stop or guide persons
Annex A Conformity with U.K. Building Regulations
2.1.2 Datum
Introduction Finished level on which people may stand, e.g. floor, roof, balcony,
pitch line of stairs external ground, etc. (see Figure 1)
Glazing in protective barriers can be regarded as a ‘safety risk’ if an
individual can accidentally come into contact with it. 2.1.3 Design level
There are two specific risks that need consideration and these are: Level at which the horizontal force on the barrier is assumed to act
for the purpose of design (see Figure 1)
• Cutting and piercing injuries resulting from accidental impact;
• Falling through the glazing if the impact causes breakage
NOTE: Injuries resulting from walking into unseen glazing is
excluded from this Data Sheet. This risk can be alleviated by the
use of appropriate manifestation. Advice on manifestation can be
found in BS 6262-4:2005, GGF Publication ‘The Right Glazing in the
Right Place’ and the applicable Building Regulations.
1. Scope
This Data Sheet covers the use of glass in protective barriers (generally
referred to as balustrades) that are designed to offer protection to
people where a difference in height constitutes a falling risk.
It covers:
a. Full height protective barriers
b. Balustrades with glass infill panels
i. Fully framed Figure 1
ii. Edge supported Datum, barrier height
and design height
iii. Point/clip supported
c. Free standing glass protective barriers
Glass and Glazing Federation While every attempt is made to present up to date
information, this data sheet, produced by the Glass
and Glazing Federation, is issued for guidance but
Tel: 020 7939 9100 Fax: 0870 042 4266
without responsibility for any advice given therein or
omission therefrom or for the consequences of acting
in reliance thereon and all liability on the part of the
Glass and Glazing Federation however arising in
connection therewith is expressly disclaimed.
Guidelines for the Use of Glass in Protective Barriers
2.1.9 Baluster
Post supporting the handrail in a balustrade.
be provided, consideration should be given to the likely hazards, • Concentrated load takes into account any non-uniformity
building use and the risks to building users. of the load applied to the infill and may also represent a static
equivalent to a localised human impact (from hand, knee, elbow,
Where, in a building, more than one use of the building is etc.). It is generally given in the form of kN, applied at the most
anticipated, either the barrier design should be chosen to suit the vulnerable position on the infill area.
worst case, or more than one type of barrier should be provided,
as appropriate, to the location. NOTE 1: Line and concentrated loads are given in Eurocode
EN 1991-1-1 and are the subject of a National Annex.
3.2 Difference in levels
NOTE 2: Uniformly distributed loads are given in Eurocode
The protective barrier shall provide guarding when the EN 1991-1-4 and are the subject of a National Annex.
following apply:
NOTE 3: Minimum horizontal imposed loads for parapets, barriers
• In dwellings where the difference in adjacent level is > 600mm; and balustrades are provided in Table 2 of BS 6180: 2011
• In building other than dwellings where the difference is: N.B: Barriers shall be designed to resist the most unfavourable
likely imposed loads, i.e. line and concentrated; and wind loads
On stairs greater than two risers; without unacceptable deflections or distortions.
Other location > 380mm
4.2 Load values
3.3 Other considerations
The value of the design loads shall relate to the building usage.
The barrier selected shall be designed so as to minimise the risk of Buildings with higher usage levels will generally be designed to
persons falling, rolling, sliding or slipping through gaps in the barrier higher load levels.
and/or the infill. The design loads and building usage categories can be found in
Where barriers are used when children under five are present the applicable national Building Regulations.
gap in the barrier shall not exceed 100mm. This dimension is given
4.3 Impact loading
with the applicable Building Regulation.
In addition to the loading requirements given in 4.1, which are
NOTE 1: The 100mm is to prevent the child being held fast by the applicable to any design of barrier, where glass is used, the
guarding (see applicable Building Regulation in Bibliography [B1]) performance under impact must be considered.
NOTE 2: Any guarding protecting glazing has to prevent a sphere Impact performance of glazing is determined under material testing.
of 75mm diameter touching the glazing (see applicable building In Europe the appropriate standard is EN 12600. The classification
regulation in Bibliography [B1]) of flat glass under this test method is presented as follows:
NOTE 3: The break safe criteria for laminated safety glass and wired α(β)Ф
safety glass are that no opening through which a 76mm diameter
sphere can pass. (see EN 12600) Where:
N.B: Care should be taken to consider the possible deflection α is the highest drop height class at which the product either
under loading. did not break or broke in accordance with a) or b) of
EN 12600: 2002, Clause 4;
4. Design Criteria β is the mode of breakage (see Annex A of EN 12600);
4.1 Introduction Ф is the highest drop height class at which the product either did
not break or broke in accordance with a) of EN 12600: 2002,
The presence of protective barriers may be one of guidance for
Clause 4.
persons moving about a building. However, the majority of
protective barriers are positioned to prevent persons from falling 4.4 Impact classes
from the edges of floors, stairs, elevated walkways and roofs.
The energy level of an impact will vary according to the position of
The main requirement of a protective barrier is, therefore, to the barrier relative to the unhindered distance a body can travel in
provide containment. It performs this function by being able to a direction perpendicular to the surface of the protective barrier
resist the likely applied forces without excessive deflection and (free path - see figure 5).
without being penetrated.
The minimum impact classes that shall be used are dependent
The forces to be resisted are generally described as follows: upon the glass type and the free path.
• Line load is related to the possibility of persons leaning
against the barrier, applying a force normal to a conventional
barrier at the top edge. It is generally given in the form of kN/m
run, applied at a height above finished floor level, i.e. datum,
roughly equivalent to the waist height of an adult
• Uniformly distributed load (UDL) is related to the
pressure exerted on the infill area (that part of the barrier
below the position of application of the line load). It is generally
given in the form of kN/m2, applied over the entire infill area. Figure 5 Free path
Guidelines for the Use of Glass in Protective Barriers
For glass to be used within a free-standing glass protective barrier, 5. Barrier Types
or a barrier with a glass infill panel it MUST give containment.
Therefore the impact classes that shall be used are as follows: 5.1 General
• Free path up to 1500mm The details below relate to the most commonly used types
of barriers.
• Thermally toughened safety glass minimum
3(C)3, i.e. 6mm There are other commercial systems available that can equally
provide a suitable barrier.
• Laminated safety glass minimum 3(B)3, i.e. 6.4mm
• Free path over 1500mm 5.2 Full height glazed protective barrier
• Thermally toughened safety glass 1(C)1, i.e. 10mm 5.2.1 General
• Laminated safety glass 1(B)1, i.e. 6.8mm
This is where glazing as part of an internal or external wall
protects a difference in level. The glass may be glazed on 4-edges,
4.5 Barrier heights 2-edges or be bolt fixed. It may be single glazing or insulating
The heights of barriers above datum are shown in Figure 1. glass units.
These are given below: 5.2.2 Loading
• Single family dwelling Glass partially or totally below the barrier height shall be
• Barriers in front of a window 800mm designed to satisfy the appropriate design criteria. Any part of a
glass pane below the barrier height shall sustain the infill loads.
• Stairs, landings, ramps, edges of internal Where the barrier height is coincident with the glass, the glass
floors 900mm shall also sustain the line load applied at the appropriate height.
• External balconies, edges of roofs 1100mm N.B.The glass shall have an impact performance classification in
All other uses accordance with the safety glazing recommendations given in BS
6262-4 i.e. have an appropriate EN12600 classification. Using a
• Barriers in front of a window 800mm thin glass, e.g. 4mm toughened Class 1(C)1, does not necessarily
mean that the glass is capable of carrying all applicable loads.
• Stairs 900mm
• Other positions 1100mm NOTE: The choice of glazing type and thickness requires
consideration of other factors such as wind loading, etc.
• Balconies and stands, etc. having fixed seating within
530mm of the barrier (see figure 6) 800mm 5.2.3 Deflection
NOTE: BS 6180:2011 gives the following barrier height/ The deflection of the glass, when it is subjected to the design
building usage: loads, shall be limited to L/65 or 25mm, taking L as the longest
dimension of the glass.
• Balconies and stands, etc. having fixed seating within 530mm of
the barrier provided the sum of the barrier width and the 5.3 Barrier with glass infill panel
barrier height is greater than 975mm
5.3.1 General
In this type of protective barrier, the main frame, comprising of
the handrail and baluster, is designed to withstand the line loads
applied to the hand rail, and the glass is used to form the infill
panels. The glass in no way provides any support to the main
frame, and the handrail loads are not transferred to the glass.
5.3.2 Loading
The glass infill panel shall carry the applicable loads, i.e. UDL
and concentrated.
With external applications the wind loading shall also be
considered.
5.3.3 Support conditions
5.3.3.1 Fully framed (see figure 7) 5.3.3.4 Bolt fixed (see figure 10)
The frame section shall give a minimum of 15mm edge cover to The design of the bolt fixings is detailed in clause 7.2 of
the glass BS 6262-6: Glazing for building – Part 6: Code of practice for
special applications
• Laminated safety glass in accordance with EN 14449; NOTE Formerly England & Wales Approved Document
N – 1998 incorporating 2000 and 2010 amendments
• Laminated thermally toughened soda lime silicate safety glass in
accordance with EN 14449; Scotland –
• Laminated heat soaked thermally toughened soda lime silicate Building (Scotland) Regulations Technical Handbook –
safety glass in accordance with EN 14449. Domestic and Non-Domestic – Section 4 - Safety
• Laminated heat strengthened soda lime silicate safety glass in Section 4.4 – Pedestrian protective barriers
accordance with EN 14449
Section 4.8 – Danger from accidents
• Safety rated wired glass in accordance with EN 572-9
Northern Ireland –
NOTE: Thermally toughened safety glass and heat soaked
The Building Regulations (Northern Ireland) Statutory
thermally toughened safety glass are available for other glass
Rules – Technical Booklet H – Stairs, ramps, guarding
compositions, e.g. borosilicate, alkaline earth silicate.
and protection from impact
6.3 Limitations The Building Regulations (Northern Ireland) Statutory
Rules – Technical Booklet V - Glazing
Some types of laminated safety glass can only be used fully
framed, i.e. in full height glazing or in barriers with fully framed B2 British Standards
infill panels.
BS 6180: 2011: Barriers in and about buildings – Code
NOTE: Laminated thermally treated glasses may be used without of practice
being fully framed.
BS 6262-4: 2005 Glazing for buildings – Part 4: Safety
Safety rated wired glass can only be considered for fully framed related to human impact – Code of practice
full height barrier situations. BS 6262-6: 2005 Glazing for buildings – Part 6: Code of
All other glass types detailed above are suitable for installation in practice for special applications
conventional systems. B3 European Standards
7. Installation EN 572-9: Glass in building – Basic soda lime silicate
glass products – Part 9: Evaluation of
Care should be taken to ensure there is no glass to metal contact.
conformity/Product standard
The major points are as follows:
EN 1863-2: Glass in building – Heat strengthened soda
• Gaskets shall be used when the glass is glazed into channels lime silicate glass – Part 2: Evaluation of
• When glazed using clips, appropriate material shall be used to conformity/Product standard
prevent the clips contacting the glass surface EN 12150-2: Glass in building – Thermally toughened
• Point fixed panes require the use of a bush around the bolt and soda lime silicate safety glass – Part 2: Evaluation of
incompressible gasket between the spreader plates and the glass. conformity/Product standard
NOTE: Information on design of point support fixings can be EN 12600: Glass in building – Pendulum test – Impact
found in BS 6262-6’ test method and classification for flat glass
K4 Protection against impact with glazing EN 14449: Glass in building – Laminated glass and
laminated safety glass – Evaluation of
K5 Additional provisions for glazing in buildings conformity/Product standard
other than dwellings
EN 15682-2: Glass in building – Heat soaked thermally
Wales – toughened alkaline earth silicate safety glass – Part 2:
Evaluation of conformity/product standard
Approved Document K – Protection from falling,
collision and impact – Parts K1, and K2 BS EN 1991-1-1: EUROCODE 1: Part 1-1, General
actions – Densities, self-weight and imposed loads
NOTE: Formerly England & Wales AD K
BS EN 1991-1-4: EUROCODE 1: Part 1-4, General
Approved Document M – Access to and use of actions – Wind actions
buildings
B4 Other Documents
NOTE: Formerly England & Wales Approved Document
M– 2004 incorporating 2010 amendments Young, Warren C. and Raymond Roark. Roark’s
Approved Document N – Glazing - Safety in relation to Formula for Stress and Strain. 8th Edition,
impact, opening and cleaning – Part N1 and N2 McGraw-Hill 2012
Guidelines for the Use of Glass in Protective Barriers
Office and Work Areas – areas not susceptible to A4.2 Full height barriers
over crowding
Table A3 gives information on single glazed full height barriers.
Areas without obstacles for moving people and not
susceptible to over crowding – stairs, landing, corridors, Area in m2 for glass type
and balconies
Building Nominal Laminated Thermally Safety
3 Areas where people might congregate – areas having Occupancy Glass Safety Toughened Wired
fixed seating within 530mm of the barrier Class thickness (mm) Glass Safety Glass Glass
Areas with tables or fixed seating – restaurants and bars 1 6 3.2 3.6 2.8
8 5.7 5.8
Areas susceptible to over crowding – footways or
10 9.0 9.0
footpaths less than 3 metres wide, adjacent to
12 12.2 12.2
sunken areas
>15 No limit No limit
Retail areas – all retail areas including banks, building 2 6 1.0 2.4 n/a
societies or betting shops 8 3.6 4.0
4 Areas susceptible to over crowding – theatres, cinemas, 10 6.2 6.2
12 9.0 9.6
shopping malls, assembly areas. Footways or pavements
15 - 12.2
greater than 3 metres wide adjacent to sunken areas
16 12.2 -
>19 No limit No limit
NOTE 1: Glass panes within these sizes will satisfy the design
criteria irrespective of shape and for glazing methods which Area in m2 for glass type
support the glass panel on all edges. Building IGU Laminated Thermally Laminated
Occupancy configurarion Safety Glass - Toughened Inner leaf /
Class (mm) Inner leaf Float Safety Toughened
NOTE 2: Compliance with this table does not necessarily indicate Outer leaf Glass Outer leaf
suitability for purpose. The thickness and type of glass pane that See Note 1 Inner leaf.
Outer leaf
can be used may also be affected by other criteria, e.g. wind See note 2
loads, and these should also be taken into account when selecting
the glass. 1 4+4 n/a 2.2 n/a
6+6 4.4 4.8 4.8
8+8 9.0 9.0 9.0
NOTE 3: Thermally toughened safety glass should comply with
10+10 14.4 15.2 14.8
EN 12150 and have a classification according to EN 12600
of 1(C) 2 4+4 n/a 0.15 n/a
6+6 2.8 3.2 3.0
8+8 5.2 5.5 5.5
NOTE 4: Laminated safety glass should comply with EN 14449
10+10 9.0 9.0 9.0
and have a classification according to EN 12600 of 3(B)
3 4+4 n/a n/a n/a
NOTE 5: Laminated safety glass is assumed to be symmetrical, i.e. 6+6 n/a n/a n/a
nominal 6mm comprises two leaves of 3mm glass. 8+8 n/a 1.4 n/a
10+10 0.15 5.2 0.15
A4.3 Full height barriers 4 4+4 n/a n/a n/a
6+6 n/a n/a n/a
Table A4 gives information on full height barriers - glazed with 8+8 n/a n/a n/a
insulating glass units. 10+10 n/a 3.2 n/a
N.B.In the case of insulating glass units the loads can be shared
between the individual leaves. Advice should be sought from the
unit manufacturer.
Guidelines for the Use of Glass in Protective Barriers
1.5 1.5 10 12.4 0.8 1.5 1.5 300 n/a n/a 550 900
500 n/a n/a 950 1400
700 n/a n/a 1150 1600
Table A5 Allowable thickness for fully framed infill 900 n/a n/a 1300 1700
panels
NOTE 5: Laminated safety glass is assumed to be symmetrical, i.e. NOTE 3: Thermally toughened safety glass should comply with
nominal 6mm comprises two leaves of 3mm glass. EN 12150 and have a classification according to EN 12600 of
1(C)1.
Table A6 gives information on two-edge framed infill
panels with thermally toughened soda lime silicate NOTE 4: Compliance with this table does not necessarily indicate
safety glass suitability for purpose. The thickness and type of glass pane that
can be used may also be affected by other criteria, e.g. wind
loads, and these should also be taken into account when selecting
the glass.
Guidelines for the Use of Glass in Protective Barriers
With Handrail With Handrail Without Handrail With Handrail Without Handrail