Date:………………..
Office Use:
Name …….………….……...…… Application Ref No. ………………………
Age ….………………..…..…… Score ………/20 (……..%)
Total Experience ….… Gulf Experience …… Remarks Passed / Failed /
Borderline
Company Introduction:
Arabian Airconditioning Contracting is a leading Grade A Electro-mechanical Contractor in
Qatar and currently engaged in various projects like Office Buildings, Villas, Hospitals,
Schools, Banks etc. The Company intends to recruit skilled Tradesman with good track
record. The Company intends to double the manpower shortly due to award of various new
projects.
The minimum cut-off lever will be atleast 80% marks in the written test and answer majority
of Technical questions during the direct interview with the Employer.
Please study following 20 objective type questions and write down your answers within 15 minutes time
limit for this written test
2) For supporting horizontal ducts, what size of threaded rod, steel Angle you will use and
what will be the spacing between supports …?….
Duct Size Threaded Rod M.S. Sheet Angle size Max. spacing between
Diameter (mm) (mm) supports
Upto 400mm ……8…mm Ø …25..…. x …25...…. x3 . ………3…….Meter
….…
400 to 600mm ……8…mm Ø …40..…. x 40…...…. x4 . ………3…….Meter
….…
600 to 1000mm ……10…mm …40..…. x …40...…. x4 . ………2.5…….Meter
Ø ….…
1000 to 1500mm ……10…mm …40..…. x40 …...…. x4 . ………2.5…….Meter
Ø ….…
3) What thickness of GI sheet you will use for following duct sizes …?….
a) Ducts with max. size 1000 upto 1500 mm … (……20…….G)
1.0……..mm
b) Ducts with max. size 800 upto 1000 mm …… (……22…….G)
0.8…..mm
c) Ducts with max. size 600 upto 800 mm …… (……22…….G)
0.8…..mm
d) Ducts with max. size upto 600 mm …….0.8….. (……22…….G)
mm
4) What minimum gauge / thickness of sheet you will use for kitchen exhaust ductwork …d
?…
) 24 G b) 18 G c) 22 G d) 20 G *
5) Curtain type Fire damper will not have one of the following … d ?….
a) Actuator b) Fuse link c) Latching device d) Spring clip *
Page-2
16) 2 way control valves for FCU and AHU should be installed…
a) upstream of equip b) Downstream of equip c) In bypass *
19) Why Grade A ASTM Standard pipe to A53 and A106 are generally not used in HVAC
application
a) High cost b) High Tensile strength c) Low tensile strength
20) Please match the correct answers for Chilled water piping system
a. Minimum pipe velocity 4 Ft / 100 Ft b
b. Maximum pressure drop 1.5 FPS a
c. Δ T for Chilled water 100 Psi d
d. Minimum pipe testing pressure 10 – 20o F c