Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 1(8)
CONTROLLER CAN NODES
BATTERY MONITOR BATTERY MONITOR
Its’ compact design and easy connection to the control
system through the CAN bus, makes it perfect for both co-
located and remote battery banks. Battery temperature is
measured by the embedded temperature probe – no external
sensor and wiring required.
The unit has 4 voltage measurement inputs used for battery
symmetry monitoring based on midpoint or block
measurements. Furthermore the battery monitor has inputs
for monitoring one battery shunt and battery breaker.
FLEXIMONITOR FLEXIMONITOR
The FlexiMonitor is a multipurpose, additional and optional CAN
Node for Eltek Smartpack2 and Smartpack S based control
systems.
FlexiMonitor adds many advanced features to your control
system, such as high-accuracy current measurements,
symmetry and voltage measurements down to battery cell
level, high voltage fuse sensing, more control & alarm outputs,
additional temperature measurements and more.
For more details, refer to the Fleximonitor datasheet, Doc #
242100.603.DS3.
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 2(8)
Doc 242100.CAN.DS3-rev 7
CONTROLLER CAN NODES
CAN POWER CAN POWER
All nodes are powered by the distributed power supplied on
the CAN bus by the Smartpack and Smartpack2 basic
controllers.
If the CAN bus needs to be isolated or additional CAN bus
power is need, the CAN power module can be added to
supplement the available power. The CAN power module is
mandatory if any CAN control units are to be connected to a
Compack controller.
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 3(8)
Doc 242100.CAN.DS3-rev 7
CONTROLLER CAN NODES
ADDITIONAL TECHNICAL SPECIFICATIONS
CAN POWER
Input 20 - 75Vdc (Screw terminals)
Outputs +/-15V, 500mA (Dual RJ45 connector)
Functionality o Isolates the power distributed on the CAN bus
o Increase power available for the CAN nodes in the system
AC MAINS MONITOR
3 mains current sensor ports (for LEM HAL or equivalent)
o Sensor reference 0V
o Signal 0-4 Vpp (45-65 Hz)
o Sensor supply - -15 V
o Sensor supply + 15 V
BATTERY MONITOR
Inputs o 4x Symmetry Voltage (0 - 60V)
o 1x Fuse failure detect, NO/NC or Diode Matrix
o 1x Current sense
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 4(8)
Doc 242100.CAN.DS3-rev 7
CONTROLLER CAN NODES
ADDITIONAL TECHNICAL SPECIFICATIONS
LOAD MONITOR
Inputs o 8x Configurable (Fuse failure)
o 8x Current sense
Accuracy based on resolution (calibrated) Current (200A): +/- 1A
Functionality o Fuse failure: NO, NC or Diode Matrix
o Current sense: 50mV or 60mV shunt
SW Part number 402087.009
Max. CAN Power consumption 120mA
Dimensions (WxDxH) 155.5 x 70.5 x 31 mm (6.12 x 2.78 x 1.22 “)
I/O MONITORS: 1
-OUTDOOR, 2
-TYPE 2 AND 3
-TYPE 3
6 configurable inputs:
“digital”, voltage/current measurement:
FLEXIMONITOR
Part number 242100.603
Relay Extension Board, 8 outputs 242100.604
Relay Extension Board, 4 outputs 242100.605
Mounting:
DIN Rail clips 282523
Screw hole (M4) clips 282524 (vertical) or 315068 (horizontal)
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 5(8)
Doc 242100.CAN.DS3-rev 7
CONTROLLER CAN NODES
ADDITIONAL TECHNICAL SPECIFICATIONS
ALL CAN NODES
Max. nodes 14 units of same type can be added a single CAN bus
(Also see CAN Power)
Mounting Slotted groove for post mounting or DIN rail/Velcro (for Battery Monitor)
Visual Indication: o GREEN: Power
3xLED (1xLED CAN Power) o YELLOW: Warning
o RED: Alarm (Flashing LED: insufficient power)
SW Upload tools o From the controller’s storage device, via the front panel,
(Smartpack2 Master’s SD card or Smartpack S Flash memory)
OR
o From a PC, using FWLoader app. (Ver ≥3.25) and “IXXAT USB-to-
CAN Converter” (p/n: 208565)
APPLICABLE STANDARDS
Electrical safety IEC 60950-1
UL 60950-1
CSA C22.2
EMC IEC 61000-6-1
IEC 61000-6-2
IEC 61000-6-3 /A1
IEC 61000-6-4
ETSI EN 300 386 v1.3.3
FCC Part 15B Subpart 109
Environment 2002/95/EC (RoHS) & 2002/96/EC (WEEE)
ETS 300 019-2-1 Class 1.2
ETS 300 019-2-2 Class 2.3
ETS 300 019-2-3 Class 3.2
PART NUMBERS
Part No. Description
242100.300 Battery Monitor
242100.301 Load Monitor
242100.304 I/O Monitor (Outdoor)
242100.502 I/O Monitor Type 2
242100.306 I/O Monitor Type 3
242100.603 Fleximonitor
242100.303 CAN Power
242100.305 AC Mains Monitor
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 6(8)
Doc 242100.CAN.DS3-rev 7
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 7(8)
Doc 242100.CAN.DS3-rev 7
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2015 – www.eltek.com 8(8)
Doc 242100.CAN.DS3-rev 7