Air System Sizing Summary for EQ ONCOLOGICOS

Project Name: HMUA 09/18/2010


Prepared by: O.K. CLIMA LTDA 08:02a.m.

Air System Information


Air System Name ........................ EQ ONCOLOGICOS Number of zones ........................................................... 1
Equipment Class .......................................... CW AHU Floor Area .............................................................. 154,7 ft²
Air System Type ............................................. SZCAV Location ........................................ Envigado, Colombia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ...................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space CFM .................. Individual peak space loads Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 1,8 Tons Load occurs at ................................................. Jun 1500
Total coil load ....................................................... 21,5 MBH OA DB / WB ................................................... 84,0 / 70,0 °F
Sensible coil load .................................................. 14,3 MBH Entering DB / WB ........................................... 72,5 / 62,1 °F
Coil CFM at Jun 1500 ........................................... 832 CFM Leaving DB / WB ............................................ 53,2 / 52,3 °F
Max block CFM .................................................... 832 CFM Coil ADP .................................................................. 51,0 °F
Sum of peak zone CFM ........................................ 832 CFM Bypass Factor ........................................................ 0,100
Sensible heat ratio .............................................. 0,666 Resulting RH ............................................................... 60 %
ft²/Ton ................................................................... 86,4 Design supply temp. ................................................. 58,0 °F
BTU/(hr-ft²) ......................................................... 139,0 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10,0 °F rise ..................................... 4,30 gpm Max zone temperature deviation ................................ 0,0 °F

Central Heating Coil Sizing Data

Max coil load ......................................................... 5,1 MBH Load occurs at ................................................. Jun 0100
Coil CFM at Jun 0100 ........................................... 832 CFM BTU/(hr-ft²) ............................................................... 32,8
Max coil CFM ....................................................... 832 CFM Ent. DB / Lvg DB ............................................ 53,3 / 60,2 °F
Water flow @ 20,0 °F drop ................................... 0,51 gpm

Supply Fan Sizing Data

Actual max CFM ................................................... 832 CFM Fan motor BHP ........................................................ 0,48 BHP
Standard CFM ...................................................... 687 CFM Fan motor kW .......................................................... 0,36 kW
Actual max CFM/ft² ............................................... 5,38 CFM/ft² Fan static ................................................................. 2,00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 250 CFM CFM/person ........................................................... 62,42 CFM/person
CFM/ft² ................................................................. 1,61 CFM/ft²

Hourly Analysis Program v.4,3 Page 1 of 1