ATT
TP 76300, Section F
FF FF
FF FF
FF FF
FW FW
FW = Fire-Rated Wall FF = Fire Rated Floor
T-Rating
The time it takes for the non-fire side to reach approximately 400 ºF
(325ºF above ambient)
To receive either rating the firestop must pass the hose stream test
Optional Ratings:
L-Rating
The amount of air leakage through the firestop system at ambient and 400°F
W-Rating
Determines the effectiveness of a firestop system to restrict the flow of
Water.
Assembly is subjected to hose stream test. Assembly results after hose stream.
ZERO
Only Firestop
Systems
have ratings!
● Through Penetrations
● Annular space
● Percent fill
c c c c c c c c c
c c c c c c c c c c
c c c c c c c c c c (Ao)= 42 =16 in2
c c c `c c c c c c c
c c c c c c c c c c (Aw)=[3.14 x (.1252)] x 85= 4.17 in2
c c c c c `` c c
c c c c c c c (%f)=(4.17 / 16) x 100 = 26.1%
c c c c c
c c c c cc cc cc c cc c c
Actual fill rate
Before
After
¼ inch bead of
Putty Stick
Label on cover
plate
e r
f t
A
The following will demonstrate a firestop system installation for 12” x 24”
openings in a gypsum wall assembly. All openings must be framed out
prior to installation of the firestop system.
Always follow specific Technical Practice requirements for installation.
F S -6 5 7 F IR E B L O C K S
H IL T I C P 6 7 5 T -S E P A R A T O R B A R
R O T A T IN G L A T C H
P O S IT IO N E D A C R O S S
T -S E P A R A T O R B A R
M A X . 6 " A B O V E /B E L O W T -B A R
H IL T I C P 6 7 5 Z -F R A M E
H IL T I C P 6 1 9 T P U T T Y C A B L E R A C K 2 " S T R IN G E R
A LL AR O UN D
After installation of Putty smoke seal, apply Fire Blocks into opening
around cable tray penetration as per previous instructions.
Install up to 3 rows (6” total height) of Fire Blocks (5” deep) above
cables flush with back edge of Z-Frame.
F S -6 5 7 F IR E B L O C K S
H IL T I C P 6 7 5 T -S E P A R A T O R B A R
R O T A T IN G L A T C H
P O S IT IO N E D A C R O S S
T -S E P A R A T O R B A R
M A X . 6 " A B O V E /B E L O W T -B A R
H IL T I C P 6 7 5 Z -F R A M E
C A B L E R A C K 2 " S T R IN G E R
H IL T I C P 6 1 9 T P U T T Y
ALL AROUND
F S -657 F IR E B LO C K S
H ILT I C P 675 T -S E P A R A T O R B A R
R O T A T IN G LA T C H
P O S IT IO N E D A C R O S S
T -S E P A R A T O R B A R
M A X . 6" A B O V E /B E LO W T -B A R
H ILTI C P 675 Z -F R A M E
Firestop
Board
Board spacer bent
(used as handle)
Putty
Roll
Turn
latch
T-Bar Latch
T - Separator bar
(behind putty strip)
Fire
Block
Installer completes
Installer determines
and sends RFTA
opening does not meet
request form to Hilti
standard system
Installation is
HILTI Engineer
completed in manner
creates solution;
specified by Telco
sends to installer
staff