Documente Academic
Documente Profesional
Documente Cultură
MODEL YK (STYLE H)
R-134a
WITH OPTIVIEWTM CONTROL CENTER
FOR ELECTRO-MECHANICAL STARTER,
SOLID STATE STARTER AND VARIABLE SPEED DRIVE
LD15222
Issue Date:
June 15, 2015
FORM 160.76-O1
ISSUE DATE: 6/15/2015
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Variable Speed Drive – Operation 160.00-O1
Solid State Starter – Operation and Maintenance 160.00-O2
Floor Mounted MV SSS – Operation 160.00-O5
Unit Mounted MV SSS – Operation 160.00-O7
Installation – Unit 160.76-N1
Optiview™ Control Center – Operation and Maintenance 160.76-O2
Wiring Diagram – Field Connections for YK Chiller (Style H, Q3-Q7) with OptiView Control Center and
160.75-PW1
Unit-mounted SSS or remote medium Voltage SSS, Medium Voltage VSD, or Medium Voltage EMS
Wiring Diagram – Field Connections for YK Chiller (Style H) OptiView Control Center with Remote
160.75-PW2
Medium Voltage SSS
Wiring Diagram – Field Connections for YK Chiller (Style H) OptiView Control Center with Remote
160.75-PW3
Medium Voltage VSD
Wiring Diagram – Field Control Modifications for YK Chiller (Style H) 160.75-PW4
Wiring Diagram – YK Chiller (Style H) OptiView Control Center and Electro-Mechanical Starter 160.75-PW5
Wiring Diagram – YK Chiller (Style H) OptiView Control Center and SSS W/Modbus, LV VSD W/Modbus 160.75-PW6
Wiring Diagram – Field Connections Model YK Chillers (Style H, Q3-Q7) with Low Voltage VSD 160.75-PW7
JOHNSON CONTROLS 3
FORM 160.76-O1
ISSUE DATE: 6/15/2015
NOMENCLATURE
yK 6A 6Q Q7 – EM H
MOTOR CODE
POWER SUPPLY
– for 60 Hz
5 for 50 Hz
COMPRESSOR CODE*
CONDENSER CODE*
EVAPORATOR CODE*
* Refer to YK Engineering Guide for (Form 160.76-EG1)
MODEL* Shell/Motor/Compressor combinations.
4 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
TABLE OF CONTENTS
SECTION 5 - TROUBLESHOOTING.......................................................................................................................23
SECTION 6 - MAINTENANCE.................................................................................................................................25
Renewal Parts................................................................................................................................................. 25
Checking System For Leaks........................................................................................................................... 25
Conducting R-134a Pressure Test.................................................................................................................. 25
JOHNSON CONTROLS 5
FORM 160.76-O1
ISSUE DATE: 6/15/2015
LIST OF FIGURES
Figure 1 - Compressor Prerotation Vanes��������������������������������������������������������������������������������������������������������������7
Figure 2 - Refrigerant Flow-Thru Chiller (Falling Film Evaporator)������������������������������������������������������������������������8
Figure 3 - Oil Level Indicator ���������������������������������������������������������������������������������������������������������������������������������9
Figure 4 - C
hiller Starting Sequence And Shutdown Sequence (Em Starter And Solid State Starter)���������������� 10
Figure 5 - Chiller Starting Sequence And Shutdown Sequence (Variable Speed Drive)������������������������������������� 10
Figure 6 - Liquid Chiller Log Sheets���������������������������������������������������������������������������������������������������������������������12
Figure 7 - System Components Front View���������������������������������������������������������������������������������������������������������16
Figure 8 - System Components Rear View����������������������������������������������������������������������������������������������������������17
Figure 9 - Schematic Drawing – (Yk) Compressor Lubrication System��������������������������������������������������������������� 18
Figure 10 - Oil Return System�����������������������������������������������������������������������������������������������������������������������������21
Figure 11 - Charging Oil Reservoir With Oil���������������������������������������������������������������������������������������������������������22
Figure 12 - Evacuation Of Chiller�������������������������������������������������������������������������������������������������������������������������25
Figure 13 - Saturation Curve��������������������������������������������������������������������������������������������������������������������������������27
Figure 14 - Diagram, Megging Motor Windings���������������������������������������������������������������������������������������������������28
Figure 15 - Motor Starter Temperature And Insulation Resistances��������������������������������������������������������������������29
LIST OF TABLES
Table 1 - Operation Analysis Chart�����������������������������������������������������������������������������������������������������������������������23
Table 2 - System Pressures���������������������������������������������������������������������������������������������������������������������������������26
Table 3 - SI Metric Conversion�����������������������������������������������������������������������������������������������������������������������������37
6 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
System Operation Description The refrigerant vapor, which is produced by the boil-
ing action in the evaporator, flows to the compressor
The YORK Model YK Chiller is commonly applied
where the rotating impeller increases its pressure and
to large air conditioning systems, but may be used
temperature and discharges it into the condenser. Wa-
on other applications. The chiller consists of an open
ter flowing through the condenser tubes absorbs heat
motor mounted to a compressor (with integral speed
from the refrigerant vapor, causing it to condense. The
increasing gears), condenser, evaporator and variable
condenser water is supplied to the chiller from an ex-
flow control.
ternal source, usually a cooling tower. The condensed
The chiller is controlled by a modern state of the art refrigerant drains from the condenser into the liquid
Microcomputer Control Center that monitors its opera- return line, where the variable orifice meters the flow
tion. The Control Center is programmed by the opera- of liquid refrigerant to the evaporator to complete the
tor to suit job specifications. Automatic timed start-ups refrigerant circuit.
and shutdowns are also programmable to suit night-
The major components of a chiller are selected to han-
time, weekends, and holidays. The operating status,
dle the refrigerant, which would be evaporated at full
temperatures, pressures, and other information perti-
load design conditions. However, most systems will
nent to operation of the chiller are automatically dis-
be called upon to deliver full load capacity for only a
played and read on a graphic display. Other displays
relatively small part of the time the unit is in operation.
can be observed by pressing the keys as labeled on the
Control Center. The chiller with the OptiView Control Capacity Control
Center is compatible with an electro-mechanical start-
er, YORK Solid State Starter (optional), or Variable The major components of a chiller are selected for full
Speed Drive (optional). load capacities, therefore capacity must be controlled
to maintain a constant chilled liquid temperature leav-
In operation, a liquid (water or brine to be chilled) ing the evaporator. Prerotation vanes (PRV), located at
flows through the evaporator, where boiling refrigerant the entrance to the compressor impeller, compensate
absorbs heat from the liquid. The chilled liquid is then for variation in load (Refer to Figure 1 on Page 7).
piped to fan coil units or other air conditioning terminal
units, where it flows through finned coils, absorbing The position of these vanes is automatically controlled
heat from the air. The warmed liquid is then returned to through a lever arm attached to an electric motor lo-
the chiller to complete the chilled liquid circuit. cated outside the compressor housing. The automatic
adjustment of the vane position in effect provides the
performance of many different compressors to match
various load conditions from full load with vanes wide
open to minimum load with vanes completely closed.
7619A(D)
JOHNSON CONTROLS 7
FORM 160.76-O1
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 6/15/2015
LEGEND
High Pressure Vapor
COMPRESSOR
SUCTION
EVAPORATOR
CONDENSER
SUCTION
BAFFLE
LIQUID LEVEL
LIQUID LEVEL
SUB-COOLER
OPTIONAL
ISOLATION LD00924A
VALVE
Rev. 2 (10-11-2010)
Figure 2 - Refrigerant Flow-Thru Chiller (Falling Film Evaporator) Dan Sowers
dan.sowers-ext@jci.com
(717) 771-7535
8 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
Start-Up
1. If the chilled water pump is manually operated,
start the pump. The Control Center will not al-
low the chiller to start unless chilled liquid flow is
established through the unit. If the chilled liquid
pump is wired to the Microcomputer Control Cen-
ter the pump will automatically start, therefore,
this step is not necessary.
2. To start the chiller, press the COMPRESSOR
START switch. This switch will automatically
spring return to the RUN position. (If the unit
was previously started, press the STOP/RESET
side of the COMPRESSOR switch and then press
the START side of the switch to start the chill-
LD08647
er.) When the start switch is energized, the Con-
Figure 3 - Oil Level Indicator trol Center is placed in an operating mode and
any malfunction will be noted by messages on a
graphic display.
JOHNSON CONTROLS 9
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015
OIL PUMP ON
"SYSTEM
SHUTDOWN" FLOW
BYPASS 150 SEC.
SWITCH (2.5 MIN)
0 10 13 45 50 110 VANES VANES 1800
START (0.17) (0.22) (0.75) (0.83) (1.83) START CLOSED (30)
TO RESTART
CLOSE
TIME IN SECONDS (MINUTES) LD06502
** Not for all shutdowns. Refer to “Display Messages” in manual Optiview™ Control Center – Operation and Maintenance (Form 160.54-O1).
Figure 4 - Chiller Starting Sequence And Shutdown Sequence (Em Starter And Solid
State Starter)
OIL PUMP ON
"SYSTEM
SHUTDOWN" FLOW
BYPASS 150 SEC.
SWITCH (2.5 MIN)
0 10 13 45 50 110 VANES VANES 600
START (0.17) (0.22) (0.75) (0.83) (1.83) START CLOSED (10)
TO RESTART
RESTART
CLOSE (IF FIVE SUCCESSIVE
RESTARTS HAVE NOT
(ONLY AFTER FIFTH
TIME IN SECONDS (MINUTES) OCCURED) SUCCESSIVE RESTART)
LD06504
** Not for all shutdowns. Refer to “Display Messages” in manual Optiview™ Control Center – Operation and Maintenance (Form 160.54-O1).
Figure 5 - Chiller Starting Sequence And Shutdown Sequence (Variable Speed Drive)
10 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015
For display messages and information pertaining to the such as a cooling tower bypass, is not necessary for
operation refer to Optiview™ Control Center – Opera- most installations. The minimum entering condenser
tion and Maintenance (Form 160.54-O1). water temperature for full and part load conditions is
Any malfunctions which occur during specified in the chiller engineering guide. 2
STOP/RESET are also displayed. where:
% Load
Min. ECWT = LCWT – C RANGE + 5ºF + 12 ( 100 )
% Load
Min. ECWT = LCWT – C RANGE + 2.8ºC + 6.6 ( 100 )
However, the current draw (amperes) by the compres- Heat recovery chillers and chillers using optional head
sor motor is also limited to FLA setpoint by the micro- pressure control would use a signal provided by the
processor. microprocessor to control main condenser bundle heat
rejection or pressure, respectively.
If the load continues to decrease, after the Prerotation
Vanes are entirely closed, the chiller will be shut down Operating Log Sheet
by the Leaving Chilled Liquid – Low Temperature
Control. A permanent daily record of system operating condi-
tions (temperatures and pressures) recorded at regular
The coolant temperature inside any JCI-supplied liq- intervals throughout each 24 hour operating period
uid-cooled motor starter must be maintained above the should be kept.
dewpoint temperature in the equipment room to pre-
vent condensing water vapor inside the starter cabinet. An optional status printer is available for this purpose
Therefore, an additional temperature-controlled throttle or Figure 6 on Page 12 shows a log sheet used by
valve is needed in the flow path for the starter heat ex- Johnson Controls Personnel for recording test data on
changer to regulate cooling above the equipment room chiller systems. It is available from the factory in pads
dewpoint for applications using cooling sources other of 50 sheets each under Form 160.44-F7 and may be
than evaporative air-exchange methods, such as wells, obtained through the nearest Johnson Controls office.
bodies of water, and chilled water. The temperature Automatic data logging is possible by connecting the
control valve should be the type to open on increasing optional printer and programming the DATA LOG-
drive coolant temperature, fail-closed, and set for a tem- GER function.
perature above dewpoint. It can be requested as factory- An accurate record of readings serves as a valuable ref-
supplied on a chiller order by special quotation. erence for operating the system. Readings taken when
a system is newly installed will establish normal condi-
Condenser Water Temperature tions with which to compare later readings.
Control
For example, an increase in condenser approach tem-
The YORK chiller is designed to use less power by tak-
perature (condenser temperature minus leaving con-
ing advantage of lower than design temperatures that
denser water temperature) may be an indication of
are naturally produced by cooling towers throughout
dirty condenser tubes.
the operating year. Exact control of condenser water
JOHNSON CONTROLS 11
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015
LD00467
23889A
*NOTE: These items can be printed by an electronic printer connected to the Microboard
and pressing the PRINT key on the Keypad, or automatically using the Data Logger feature.
12 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015
Annually (more often if necessary) 1. Push the soft shutdown key on the homescreen on
1. Drain and replace the oil in the compressor oil the OptiView panel or rapid stop with the COM-
sump. (Refer to Oil Charging Procedure on Page PRESSOR STOP/RESET switch. The compressor
22.) will stop automatically. The oil pump will contin- 2
ue to run for coastdown period. The oil pump will
2. Evaporator and Condenser. then stop automatically.
a. Inspect and clean water strainers. 2. Stop the chilled water pump (if not wired into
b. Inspect and clean tubes as required. the Microcomputer Control Center, in which
case it will shut off automatically simultaneously
c. Inspect end sheets. with the oil pump.) (The actual water pump con-
3. Compressor Drive Motor (See motor manufactur- tact operation is dependent upon the position of
ers maintenance and service instruction supplied Microboard jumper J54.)
with unit) 3. Open the switch to the cooling tower fan motors,
a. Clean air passages and windings per manu- if used.
facturers instructions.
4. The compressor sump oil heater is energized when
b. Meg motor windings – Refer to Figure 14 on the unit is stopped.
Page 28 for details.
Prolonged Shutdown
c. Lubricate per motor manufacturer recom-
mendations. If the chiller is to be shut down for an extended period
of time (for example, over the winter season), the fol-
4. Inspect and service electrical components as neces- lowing paragraphs outline the procedure to be followed.
sary.
1. Test all system joints for refrigerant leaks with a
5. Perform refrigerant analysis. leak detector. If any leaks are found, they should
If quarterly inspection indicates oil is fine, be repaired before allowing the system to stand
replacing the oil is not necessary for a long period of time.
During long idle periods, the tightness of the sys-
tem should be checked periodically.
2. If freezing temperatures are encountered while
the system is idle, carefully drain the cooling wa-
Need For Maintenance Or Service
ter from the cooling tower, condenser, condenser
If the system is malfunctioning in any manner or the pump, and the chilled water system-chilled water
unit is stopped by one of the safety controls, consult pump and coils.
the Operation Analysis Chart, Table 1 on Page 23 of
this manual. After consulting this chart, if you are un- Open the drains on the evaporator and condenser
able to make the proper repairs or adjustments to start liquid heads to assure complete drainage. (If a
the compressor or the particular trouble continues to Variable Speed Drive, drain its cooling system.
hinder the performance of the unit, please call the near- If Solid State Starter equipped drain liquid from
est Johnson Controls District Office. Failure to report starter cooling loop.)
constant troubles could damage the unit and increase 3. If freezing temperatures are encountered for peri-
the cost of repairs. ods longer than a few days, the refrigerant should
be recovered to containers to prevent leakage from
Stopping The System O-ring joints.
The Optiview™ Control Center can be programmed to 4. On the SETUP Screen, disable the clock. This
start and stop automatically (maximum, once each day) conserves the battery.
whenever desired. Refer to the Optiview™ Control
Center – Operation and Maintenance (Form 160.54- 5. Open the main disconnect switches to the com-
O1). To stop the chiller, proceed as follows: pressor motor, condenser water pump and the
chilled water pump. Open the 115 volt circuit to
the Control Center.
JOHNSON CONTROLS 13
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015
14 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
JOHNSON CONTROLS 15
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015
OPTIVIEW CONTROL
CENTER
COMPRESSOR
SUCTION
RELIEF
VARIABLE
VALVES
SPEED
DRIVE
EVAPORATOR
LD15222
VARIABLE SPEED
SIGHT
OIL PUMP
GLASS
CONTROL BOX
FRONT VIEW
16 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015
MOTOR
COMPRESSOR
OIL FILTER
DISCHARGE
LINE
LD15223
LIQUID LINE
CONDENSER OIL PUMP
HOUSING
REAR VIEW
JOHNSON CONTROLS 17
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015
COMPRESSOR ROTOR
SUPPORT SECTION
H.S.
SHAFT
SEAL
EMERGENCY
OIL RESERVE
HIGH
PRESSURE
TRANSDUCER
MAIN JOURNAL
AND THRUST
BEARING
IMPELLER
REFRIG.
SIGHT
HOT GLASSES
THERMISTOR
OIL OIL
HEATER COOLER
LOW OIL
ANGLE PRESSURE
DRAIN VALVE TRANSDUCER
OIL
LD15200
18 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015
JOHNSON CONTROLS 19
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015
While the chiller is shut down, the orifice will be in the Optiview Control Center
fully open position causing the sensed level to be ap-
The OptiView Control Center is factory-mounted,
proximately 0%. When the chiller is started, after the
wired and tested. The electronic panel automatically
vane motor end switch (VMS) opens when entering
controls the operation of the unit in meeting system
SYSTEM RUN, if actual level is less than the level
cooling requirements while minimizing energy usage.
setpoint, a linearly increasing ramp is applied to the lev-
For detailed information on the Control Center, refer to
el setpoint. This ramp causes the setpoint to go from the
SECTION 2 - SYSTEM OPERATING PROCEDURES
initial refrigerant level (approximately 0%) to the pro-
of this manual.
grammed setpoint over a programmable period of time.
If the actual level is greater than the setpoint when the Solid State Starter (Optional)
VMS opens, there is no pulldown period, it immedi- The Solid State Starter is a reduced voltage starter that
ately begins to control to the programmed setpoint. controls and maintains a constant current flow to the
motor during start-up. It is mounted on the chiller. Pow-
While the chiller is running, the refrigerant level is nor-
er and control wiring between the starter and chiller
mally controlled to the level setpoint. However, any-
are factory installed. The starter enclosure is NEMA-1
time the vanes fully close (VMS closes), normal level
with a hinged access door with lock and key. Electrical
control is terminated, any refrigerant level setpoint in
lugs for incoming power wiring are provided.
effect is cancelled and the outputs to the level control
will be constant open. Variable Speed Drive (Optional)
Optional Service Isolation Valves A Variable Speed Drive can be factory packaged with
the chiller. It is designed to vary the compressor mo-
If your chiller is equipped with optional service iso-
tor speed and prerotation vane position by controlling
lation valves on the discharge and liquid line, these
the frequency and voltage of the electrical power to
valves must remain open during operation. These
the motor. Operational information is contained in the
valves are used for isolating the refrigerant charge in
Variable Speed Drive – Operation (Form 160.00-O1).
either the evaporator or condenser to allow service ac-
The control logic automatically adjusts motor speed
cess to the system. A refrigerant pump-out unit will be
and compressor prerotation vane position for maxi-
required to isolate the refrigerant.
mum part load efficiency by analyzing information fed
Isolation of the refrigerant in this system to it by sensors located throughout the chiller.
must be performed by a qualified service
technician.
20 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
COMPRESSOR
SOLENOID VALVE
CONDENSER
EVAPORATOR
SOLENOID VALVE
STOP VALVE
LD08578
JOHNSON CONTROLS 21
FORM 160.76-O1
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 6/15/2015
OIL
CHARGING
PUMP
LD08648 LD08579
OIL CHARGING VALVE
22 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
SECTION 5 - TROUBLESHOOTING
JOHNSON CONTROLS 23
FORM 160.76-O1
SECTION 5 - TROUBLESHOOTING
ISSUE DATE: 6/15/2015
24 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
SECTION 6 - MAINTENANCE
27385A(D)
STOP VALVE
CHARGING
VALVE
WET BULB TEMPERATURE
INDICATOR OR VACUUM GAUGE VACUUM PUMP
LD00949
JOHNSON CONTROLS 25
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
*GAUGE ABSOLUTE
BOILING
INCHES OF TEMPERATURES
MERCURY (HG) OF
MILLIMETERS OF
BELOW ONE PSIA MICRONS WATER
MERCURY (HG)
STANDARD °F
ATMOSPHERE
0 14.696 760. 760,000 212
10.24" 9.629 500. 500,000 192
22.05" 3.865 200. 200,000 151
25.98" 1.935 100. 100,000 124
27.95" .968 50. 50,000 101
28.94" .481 25. 25,000 78
29.53" .192 10. 10,000 52
29.67" .122 6.3 6,300 40
29.72" .099 5. 5,000 35
WATER
29.842" .039 2. 2,000 15 FREEZES
29.882" .019 1.0 1,000 +1
29.901" .010 .5 500 –11
29.917" .002 .1 100 –38
29.919" .001 .05 50 –50
29.9206" .0002 .01 10 –70
29.921" 0 0 0
*One standard atmosphere = 14.696 Psia NOTES: PSIA = Lbs. per sq. in. gauge pressure
= 760 mm Hg. absolute pressure at 32°F = Pressure above atmosphere
= 29.921 inches Hg. absolute at 32°F PSIA = Lbs. per sq. in. absolute pressure
= Sum of gauge plus atmospheric pressure
26 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
Be sure the vacuum indicator is valved off taken place the pressure and temperature will continue
while holding the system vacuum and be to drop until eventually a temperature of 35°F (1.6°C)
sure to open the valve between the vacuum or a pressure of 5 mm Hg. is reached.
indicator and the system when checking
the vacuum after the 8 hour period. When this point is reached, practically all of the air has
been evacuated from the system, but there is still a small
amount of moisture left. In order to provide a medium
Vacuum Dehydration for carrying this residual moisture to the vacuum pump,
To obtain a sufficiently dry system, the following in- nitrogen should be introduced into the system to bring
structions have been assembled to provide an effective it to atmospheric pressure and the indicator temperature
method for evacuating and dehydrating a system in the will return to approximately ambient temperature. Close
field. Although there are several methods of dehydrating off the system again, and start the second evacuation.
a system, we are recommending the following, as it pro- The relatively small amount of moisture left will be
duces one of the best results, and affords a means of ob- carried out through the vacuum pump and the tem-
taining accurate readings as to the extent of dehydration. perature or pressure shown by the indicator should
drop uniformly until it reaches a temperature of 35°F 6
The equipment required to follow this method of dehy-
dration consists of a wet bulb indicator or vacuum gauge, (1.6°C) or a pressure of 5 mm Hg.
a chart showing the relation between dew point tempera- When the vacuum indicator registers this temperature
ture and pressure in inches of mercury (vacuum), (Refer or pressure, it is a positive sign that the system is evac-
to Table 2 on Page 26) and a vacuum pump capable of uated and dehydrated to the recommended limit. If this
pumping a suitable vacuum on the system. level cannot be reached, it is evident that there is a leak
somewhere in the system. Any leaks must be corrected
Operation
before the indicator can be pulled down to 35°F or 5
Dehydration of a refrigerant system can be obtained mm Hg. in the primary evacuation.
by this method because the water present in the system
reacts much as a refrigerant would. By pulling down During the primary pulldown, keep a careful watch on
the pressure in the system to a point where its satu- the wet bulb indicator temperature, and do not let it fall
ration temperature is considerably below that of room below 35°F (1.6°C). If the temperature is allowed to
temperature, heat will flow from the room through the fall to 32°F (0°C), the water in the test tube will freeze,
walls of the system and vaporize the water, allowing and the result will be a faulty temperature reading.
a large percentage of it to be removed by the vacuum
pump. The length of time necessary for the dehydra-
NITROGEN ADDED
tion of a system is dependent on the size or volume of
INDICATOR READING -°F
SEC ACUA
PRIM
the system, the capacity and efficiency of the vacuum ARY
EV
EVAC
ON
UATI
pump, the room temperature and the quantity of water ON
DAR ION
present in the system. By the use of the vacuum indi-
T
Y
cator as suggested, the test tube will be evacuated to
the same pressure as the system, and the distilled water
will be maintained at the same saturation temperature
as any free water in the system, and this temperature
can be observed on the thermometer.
If the system has been pressure tested and found to be
TIME
tight prior to evacuation, then the saturation tempera- LD00474
JOHNSON CONTROLS 27
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
inder must be admitted to the system pressure until the The refrigerant charge level must be checked after the
system pressure is raised above the point correspond- pressure and temperature have equalized between the
ing to the freezing point of the evaporator liquid. For condenser and evaporator. This would be expected to be
water, the pressure corresponding to the freezing point 4 hours or more after the compressor and water pumps
is 8.54 PSIG (58.9 kPa) for R-134a (at sea level). are stopped. The level should visible in the sight glass.
While charging, every precaution must be taken to pre- Charge the refrigerant in accordance with the meth-
vent moisture laden air from entering the system. Make od shown under the REFRIGERANT CHARGING,
up a suitable charging connection from new copper tub- above. The refrigerant level should be observed and
ing to fit between the system charging valve and the fit- the level recorded after initial charging.
ting on the charging drum. This connection should be
Handling Refrigerant For Dismantling
as short as possible but long enough to permit sufficient
And Repairs
flexibility for changing drums. The charging connection
should be purged each time a full container of refriger- If it becomes necessary to open any part of the refriger-
ant is connected and changing containers should be done ant system for repairs, it will be necessary to remove
as quickly as possible to minimize the loss of refrigerant. the charge before opening any part of the unit. If the
chiller is equipped with optional valves, the refrigerant
Refrigerant may be furnished in cylinders containing can be isolated in either the condenser or evaporator /
either 30, 50, 125, 1,025 or 1750 lbs. (13.6, 22.6, 56.6, compressor while making any necessary repairs.
464 or 794 kg) of refrigerant.
Megging The Motor
The nameplate on the chiller contains the
correct refrigerant charge information While the main disconnect switch and compressor mo-
for the chiller. tor starter are open, meg the motor as follows:
1. Using a megohm meter (megger), meg between
phases and each phase to ground (Refer to Figure 14
on Page 28); these readings are to be interpreted
Checking The Refrigerant Charge using the graph shown in Figure 15 on Page 29.
During Unit Shutdown 2. If readings fall below shaded area, remove exter-
The refrigerant charge is specified for each chiller model. nal leads from motor and repeat test.
Charge the correct amount of refrigerant and record the Motor is to be megged with the starter at
level in the evaporator sight glass. ambient temperature after 24 hours of
idle standby.
The refrigerant charge should always be checked and
trimmed when the system is shut down.
MEGOHM
BETWEEN MEGOHM
WINDINGS METER
MAIN DISCONNECT
(OPEN) MEGOHM EACH
WINDING TO GROUND
STARTER (OPEN)
MEGOHM METER
LD00475
28 JOHNSON CONTROLS
Minimum Insulation Resistance vs. Temperature (per IEEE Std 43)
Open Motors
1. Megger readings should be taken after Megger voltage has been applied one minute.
FORM 160.76-O1
2. If insulation resistance lies to the right of the applicable curve the motor is acceptable for use.
JOHNSON CONTROLS
ISSUE DATE: 6/15/2015
3. If insulation resistance lies to the left of the applicable curve, the motor should not be run. The motor
should be heated to 250°F in an effort to remove moisture and obtain an acceptable reading at room
ambient. This can be done either by baking in a forced hot air oven or, if proper voltage is available,
apply 5 - 10% of rated voltage to motor windings.
4. A
ny gradual or abrupt decrease in Megger readings over an extended period of time is an indication of
deterioration of insulation and / or moisture absorption or oil / dirt contamination.
5. Megger readings of individual phase coils of 200 - 600V motors should be made with coils not under
test being grounded.
LEGEND
A 2
00 - 600V
DELTA CONN.
B 2
300V
(Entire Windings)
C 2
00 - 600V
TEMPERATURE – °F
(Per Phase)
Note 5
D 3
300 - 4160V
(Entire Windings)
29
SECTION 6 - MAINTENANCE
LD00476
6
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
30 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
Acid cleaning should only be performed 3. With nitrogen or dry air, blow out the tubes to
by an expert. Please consult your local clear them of traces of refrigerant laden moisture
water treatment representative for as- from the circulation water. As soon as the tubes
sistance in removing scale buildup and are clear, a cork should be driven into each end
preventative maintenance programs to of the tube. Pressurize the dry system with 50 to
eliminate future problems. COMMER- 100 PSIG (345 to 690 kPa) of nitrogen. Repeat
CIAL ACID CLEANING this with all of the other tubes in the suspected
section or, if necessary, with all the tubes in the
In many major cities, commercial organizations now evaporator or condenser. Allow the evaporator or
offer a specialized service of acid cleaning evaporators condenser to remain corked up to 12 to 24 hours
and condensers. If acid cleaning is required, YORK before proceeding. Depending upon the amount
recommends the use of this type of organization. The of leakage, the corks may blow from the end of a
Dow Industries Service Division of the Dow Chemical tube, indicating the location of the leakage. If not,
Company, Tulsa, Oklahoma, with branches in principal if will be necessary to make a very thorough test
cities is one of the most reliable of these companies. with the leak detector.
6
Testing For Evaporator And Condenser Tube 4. After the tubes have been corked for 12 to 24
Leaks hours, it is recommended that two men working
at both ends of the evaporator carefully test each
Evaporator and condenser tube leaks in R-134a sys-
tube – one man removing corks at one end and
tems may result in refrigerant leaking into the water
the other at the opposite end to remove corks and
circuit, or water leaking into the shell depending on the
handle the leak detector. Start with the top row of
pressure levels. If refrigerant is leaking into the water,
tubes in the section being investigated. Remove
it can be detected at the liquid head vents after a period
the corks at the ends of one tube simultaneously
of shutdown. If water is leaking into the refrigerant,
and insert the exploring tube for 5 seconds – this
system capacity and efficiency will drop off sharply. If
should be long enough to draw into the detec-
a tube is leaking and water has entered the system, the
tor any refrigerant gas that might have leaked
evaporator and condenser should be valved off from
through the tube walls. A fan placed at the end of
the rest of the water circuit and drained immediately to
the evaporator opposite the detector will assure
prevent severe rusting and corrosion. The refrigerant
that any leakage will travel through the tube to
system should then be drained and purged with dry ni-
the detector.
trogen to prevent severe rusting and corrosion. If a tube
leak is indicated, the exact location of the leak may be 5. Mark any leaking tubes for later identification.
determined as follows:
6. If any of the tube sheet joints are leaking, the leak
1. Remove the heads and listen at each section of should be indicated by the detector. If a tube sheet
tubes for a hissing sound that would indicate gas leak is suspected, its exact location may be found
leakage. This will assist in locating the section of by using a soap solution. A continuous buildup of
tubes to be further investigated. If the probable bubbles around a tube indicates a tube sheet leak.
location of the leaky tubes has been determined,
treat that section in the following manner (if the
location is not definite, all the tubes will require
investigations).
2. Wash off both tube heads and the ends of all tubes
with water.
Do not use carbon tetrachloride for this
purpose since its fumes give the same
flame discoloration that the refrigerant
does.
JOHNSON CONTROLS 31
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015
Compressor
Maintenance for the compressor assembly consists rings can contact the impeller and account for some
of checking the operation of the oil return system and aluminum particles to accumulate in the oil filter, espe-
changing the dehydrator, checking and changing the oil, cially during the initial start up and first several months
checking and changing the oil filters, checking the op- of operation. However, if aluminum particles continue
eration of the oil heater, checking the operation of the oil to accumulate and the same conditions continue to stop
pump, and observing the operation of the compressor. the unit operation after a new filter is installed, notify
the nearest Johnson Controls office to request the pres-
Internal wearing of compressor parts could be a seri- ence of a Johnson Controls Service Technician.
ous problem caused by improper lubrication, brought
about by restricted oil lines, passages, or dirty oil fil- Electrical Controls
ters. If the unit is shutting down on (HOT) High Oil
Temperature or Low Oil Pressure (OP), change the oil For information covering the OptiView™ Control
filter element. Examine the oil filter element for the Center operation, refer to the Optiview™ Control Cen-
presence of aluminum particles. Aluminum gas seal ter – Operation and Maintenance (Form 160.54-O1).
32 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015
It is the responsibility of the owner to provide the nec- Motor Re-lubrication Instruction
essary daily, monthly and yearly maintenance require-
All motor manufacturers have slightly different re-
ments of the system.
quirements for the exact amount of grease to be added,
IMPORTANT – If a unit failure occurs and the exact interval for re-greasing. The suggested
due to improper maintenance during the amount should be 1.5 cubic inches of grease, and the
warranty period; Johnson Controls will interval should be 1000 hours to 1400 hours between
not be liable for costs incurred to return re-lubrications. York Optiview control panels provide
the system to satisfactory operation. a warning message to re-lubricate bearings at 1000
hours. When the run clock reaches 1400 hours without
In any operating system it is most important to pro- lubrication, software will shut down the chiller until
vide a planned maintenance and inspection of its func- re-lubrication has been acknowledged.
tioning parts to keep it operating at its peak efficiency.
Therefore, the following maintenance should be per- Grease Gun Calibration -
formed when prescribed. Grease guns should be calibrated to determine the
number of pumps required to get 1.5 cubic inches of
Compressor grease. This can be accomplished by forming an open- 7
1. Oil Filter – When oil pump VSD frequency in- top cardboard cube, one inch by one inch by one inch.
creases to 55 hz to maintain target oil pressure. Pump grease into this container until grease is level
with the top, counting the number of pumps. When
When the oil filter is changed, it should be in- the grease is level with the top, this is the amount for
spected thoroughly for any aluminum particles one cubic inch. Multiply this number of pumps times
which would indicate possible bearing wear. 1.5 to get the number of pumps for York chiller motor
If aluminum particles are found this should be bearings.
brought to the attention of the nearest Johnson
Over-greasing can be as detrimental as
Controls office for their further investigation and
lack of greasing. A bearing housing that
recommendations.
is totally filled with grease can run 20 de-
2. Oil Changing – The oil in the compressor must grees centigrade higher temperature than
be changed annually or earlier if it becomes dark one with the proper amount of grease.
or cloudy. However, quarterly oil analysis can
eliminate the need for an annual change provided
Type of Grease –
the analysis indicates there is no problem with the
oil. All standard York chiller motors utilize a polyurea
grease, formulated for high-speed rolling element
Compressor Motor bearings. Only two greases are approved by all our
1. Check motor mounting screws frequently to in- motor manufacturers, and these are:
sure tightness. 1st Choice: Exxon / Mobil Polyrex EM -
2. Meg motor windings annually to check for dete- Grainger Part Number 5XB54
rioration of windings. 2nd Choice: Texaco / Chevron SRI #2
Greased Bearings There are a few exceptions, such as Reliance Q-frame
Motor Operation and Maintenance manuals are sup- motors built from 1997 to 2003, and some special or-
plied with the chillers providing maintenance sched- der motors such as high-voltage motors from ABB. In
ules and instructions for the specific motors. The fol- these cases use only the grease called for by the mo-
lowing are lubrication schedules for the most common tor manufacturer. In the case of those Reliance mo-
motors: tors, there is a metal tag affixed to the motor calling for
JOHNSON CONTROLS 33
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015
Texaco Premium RB. This is a lithium based lubricant Mixing different greases is not recom-
and absolutely should never be mixed with polyurea mended
grease. If you are unable to locate this specific Texa-
co product, another approved lithium based grease is
Shell Alvania RL in NLGI #3.
The motors on York chillers must utilize the greas- Additional information on motor lubrica-
es mentioned above. Approval of any other type of tion and other service issues can be found
grease will not be granted. Typically, we also receive in the A-C Motors Instruction Manual.
requests to use synthetic grease products, often from
very well-recognized major grease manufacturers. Un-
fortunately, none of these greases have been approved.
It is not recommended to mix synthetic greases with
mineral oil based grease, which is the type of grease Leak Testing
that is inside the motor bearings as shipped from the The unit should be leak tested monthly. Any leaks
York factory. found must be repaired immediately.
Procedure – Evaporator And Condenser
Re-lubrication should be done with the motor shut The major portion of maintenance on the condenser
down with NO rotor rotation. This helps to assure and evaporator will deal with the maintaining the wa-
grease is placed in between the balls of the bearing. If ter side of the condenser and evaporator in a clean
the rotor is spinning certain bearing housing designs condition.
can force the grease to escape around the clearance
holes where the rotor shaft passes through the bearing The use of untreated water in cooling towers, closed
housing cap. This type of design will cause grease to water systems, etc. frequently results in one or more of
collect inside the motor. Other bearing designs may the following:
not allow any of the grease to penetrate to the bearing
housing if the rotor is spinning. 1. Scale Formation.
2. Corrosion or Rusting.
Absolutely NEVER pump grease until you see old
grease exiting at the relief port. Only pump the re- 3. Slime and Algae Formation.
quired number of strokes as determined above.
It is therefore to the benefit of the user to provide for
After the proper amount of grease has been added, proper water treatment to provide for a longer and
open the bearing relief port plug typically loated be- more economical life of the equipment. The following
low the bearing, and run the motor for 30-45 minutes recommendation should be followed in determining
before re-installing the plug. It is not necessary to see the condition of the water side of the condenser and
old grease coming out from the relief port. evaporator tubes.
34 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015
JOHNSON CONTROLS 35
36
MAINTENANCE REQUIREMENTS FOR YORK YK CHILLERS
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls Service Office. A record of all procedures being successfully car-
ried out (as well as operating logs) must be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment.
2
More frequent service may be required depending on local operating conditions.
160.54-MR1 (611)
Supersedes 160.54-MR1 (801)
Issue Date: June 20, 2011
JOHNSON CONTROLS
ISSUE DATE: 6/15/2015
FORM 160.76-O1
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS 37
P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2015 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.76-O1 (615)
Issue Date: June 15, 2015
New Release