Sunteți pe pagina 1din 38

centrifugal liquid chillers

OPERATIONS AND MAINTENANCE New Release Form 160.76-O1 (615)

MODEL YK (STYLE H)
R-134a
WITH OPTIVIEWTM CONTROL CENTER
FOR ELECTRO-MECHANICAL STARTER,
SOLID STATE STARTER AND VARIABLE SPEED DRIVE

LD15222

Issue Date:
June 15, 2015
FORM 160.76-O1
ISSUE DATE: 6/15/2015

IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.

SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:

Indicates a possible hazardous situation Identifies a hazard which could lead to


which will result in death or serious injury damage to the machine, damage to other
if proper care is not taken. equipment and/or environmental pollu-
tion if proper care is not taken or instruc-
tions and are not followed.

Indicates a potentially hazardous situa- Highlights additional information useful


tion which will result in possible injuries to the technician in completing the work
or damage to equipment if proper care is being performed properly.
not taken.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.

2 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

CHANGEABILITY OF THIS DOCUMENT


In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig-
tinuous product improvement, the information con- ging, lifting, and operating/service personnel should
tained in this document is subject to change without verify whether the equipment has been modified and
notice. Johnson Controls makes no commitment to if current literature is available from the owner of the
update or provide current information automatically equipment prior to performing any work on the chiller.
to the manual or product owner. Updated manuals, if
applicable, can be obtained by contacting the nearest Change Bars
Johnson Controls Service office or accessing the John-
son Controls QuickLIT website at http://cgproducts. Revisions made to this document are indicated with a
johnsoncontrols.com. line along the left or right hand column in the area the
revision was made. These revisions are to technical in-
It is the responsibility of rigging, lifting, and operating/ formation and any other changes in spelling, grammar
service personnel to verify the applicability of these or formatting are not included.
documents to the equipment. If there is any question

ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Variable Speed Drive – Operation 160.00-O1
Solid State Starter – Operation and Maintenance 160.00-O2
Floor Mounted MV SSS – Operation 160.00-O5
Unit Mounted MV SSS – Operation 160.00-O7
Installation – Unit 160.76-N1
Optiview™ Control Center – Operation and Maintenance 160.76-O2
Wiring Diagram – Field Connections for YK Chiller (Style H, Q3-Q7) with OptiView Control Center and
160.75-PW1
Unit-mounted SSS or remote medium Voltage SSS, Medium Voltage VSD, or Medium Voltage EMS
Wiring Diagram – Field Connections for YK Chiller (Style H) OptiView Control Center with Remote
160.75-PW2
Medium Voltage SSS
Wiring Diagram – Field Connections for YK Chiller (Style H) OptiView Control Center with Remote
160.75-PW3
Medium Voltage VSD
Wiring Diagram – Field Control Modifications for YK Chiller (Style H) 160.75-PW4
Wiring Diagram – YK Chiller (Style H) OptiView Control Center and Electro-Mechanical Starter 160.75-PW5
Wiring Diagram – YK Chiller (Style H) OptiView Control Center and SSS W/Modbus, LV VSD W/Modbus 160.75-PW6

Wiring Diagram – Field Connections Model YK Chillers (Style H, Q3-Q7) with Low Voltage VSD 160.75-PW7

Renewal Parts – Unit 160.76-RP1


Renewal Parts – OptiView Control Center 160.54-RP1

JOHNSON CONTROLS 3
FORM 160.76-O1
ISSUE DATE: 6/15/2015

NOMENCLATURE
yK 6A 6Q Q7 – EM H

STYLE (Design Level)

MOTOR CODE
POWER SUPPLY
– for 60 Hz
5 for 50 Hz

COMPRESSOR CODE*

CONDENSER CODE*

EVAPORATOR CODE*
* Refer to YK Engineering Guide for (Form 160.76-EG1)
MODEL* Shell/Motor/Compressor combinations.

4 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

TABLE OF CONTENTS

SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION........................................... 7


System Operation Description .......................................................................................................................... 7
Capacity Control................................................................................................................................................ 7

SECTION 2 - SYSTEM OPERATING PROCEDURES..............................................................................................9


Oil Heaters........................................................................................................................................................ 9
Oil Heater Operation......................................................................................................................................... 9
Checking The Oil Level In The
Oil Reservoir...................................................................................................................................................... 9
Start-Up Procedure........................................................................................................................................... 9
Start-Up............................................................................................................................................................. 9
Chiller Operation............................................................................................................................................. 11
Condenser Water Temperature
Control............................................................................................................................................................. 11
Operating Log Sheet....................................................................................................................................... 11
Operating Inspections..................................................................................................................................... 12
Need For Maintenance Or Service.................................................................................................................. 13
Stopping The System...................................................................................................................................... 13
Prolonged Shutdown....................................................................................................................................... 13

SECTION 3 - SYSTEM COMPONENTS DESCRIPTION........................................................................................15


General............................................................................................................................................................ 15
Compressor..................................................................................................................................................... 15
Capacity Control.............................................................................................................................................. 15
Compressor Lubrication System .................................................................................................................... 15
Oil Pump.......................................................................................................................................................... 15
Oil Heater........................................................................................................................................................ 19
Motor Driveline................................................................................................................................................ 19
Heat Exchangers............................................................................................................................................. 19
Refrigerant Flow Control................................................................................................................................. 19
Optional Service Isolation Valves.................................................................................................................... 20
Optional Hot Gas Bypass................................................................................................................................ 20
Optiview Control Center.................................................................................................................................. 20
Solid State Starter (Optional).......................................................................................................................... 20
Variable Speed Drive (Optional)...................................................................................................................... 20

SECTION 4 - OPERATIONAL MAINTENANCE......................................................................................................21


Oil Return System........................................................................................................................................... 21
Changing The Dehydrator............................................................................................................................... 21
The Oil Charge................................................................................................................................................ 22
Oil Charging Procedure................................................................................................................................... 22

SECTION 5 - TROUBLESHOOTING.......................................................................................................................23

SECTION 6 - MAINTENANCE.................................................................................................................................25
Renewal Parts................................................................................................................................................. 25
Checking System For Leaks........................................................................................................................... 25
Conducting R-134a Pressure Test.................................................................................................................. 25

JOHNSON CONTROLS 5
FORM 160.76-O1
ISSUE DATE: 6/15/2015

TABLE OF CONTENTS (CONT'D)


Vacuum Testing............................................................................................................................................... 26
Vacuum Dehydration....................................................................................................................................... 27
Operation......................................................................................................................................................... 27
Refrigerant Charging....................................................................................................................................... 27
Checking The Refrigerant Charge During Unit Shutdown............................................................................... 28
Handling Refrigerant For Dismantling And Repairs.........................................................................................28
Megging The Motor.......................................................................................................................................... 28
Compressor..................................................................................................................................................... 32
Electrical Controls........................................................................................................................................... 32

SECTION 7 - PREVENTIVE MAINTENANCE.........................................................................................................33


Compressor..................................................................................................................................................... 33
Compressor Motor........................................................................................................................................... 33
Greased Bearings .......................................................................................................................................... 33
Motor Re-lubrication Instruction...................................................................................................................... 33
Leak Testing.................................................................................................................................................... 34
Evaporator And Condenser............................................................................................................................. 34
Oil Return System........................................................................................................................................... 35
Electrical Controls........................................................................................................................................... 35
Temperature.................................................................................................................................................... 37

LIST OF FIGURES
Figure 1 - Compressor Prerotation Vanes��������������������������������������������������������������������������������������������������������������7
Figure 2 - Refrigerant Flow-Thru Chiller (Falling Film Evaporator)������������������������������������������������������������������������8
Figure 3 - Oil Level Indicator ���������������������������������������������������������������������������������������������������������������������������������9
Figure 4 - C
 hiller Starting Sequence And Shutdown Sequence (Em Starter And Solid State Starter)���������������� 10
Figure 5 - Chiller Starting Sequence And Shutdown Sequence (Variable Speed Drive)������������������������������������� 10
Figure 6 - Liquid Chiller Log Sheets���������������������������������������������������������������������������������������������������������������������12
Figure 7 - System Components Front View���������������������������������������������������������������������������������������������������������16
Figure 8 - System Components Rear View����������������������������������������������������������������������������������������������������������17
Figure 9 - Schematic Drawing – (Yk) Compressor Lubrication System��������������������������������������������������������������� 18
Figure 10 - Oil Return System�����������������������������������������������������������������������������������������������������������������������������21
Figure 11 - Charging Oil Reservoir With Oil���������������������������������������������������������������������������������������������������������22
Figure 12 - Evacuation Of Chiller�������������������������������������������������������������������������������������������������������������������������25
Figure 13 - Saturation Curve��������������������������������������������������������������������������������������������������������������������������������27
Figure 14 - Diagram, Megging Motor Windings���������������������������������������������������������������������������������������������������28
Figure 15 - Motor Starter Temperature And Insulation Resistances��������������������������������������������������������������������29

LIST OF TABLES
Table 1 - Operation Analysis Chart�����������������������������������������������������������������������������������������������������������������������23
Table 2 - System Pressures���������������������������������������������������������������������������������������������������������������������������������26
Table 3 - SI Metric Conversion�����������������������������������������������������������������������������������������������������������������������������37

6 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 1 - DESCRIPTION OF SYSTEM AND 1


FUNDAMENTALS OF OPERATION

System Operation Description The refrigerant vapor, which is produced by the boil-
ing action in the evaporator, flows to the compressor
The YORK Model YK Chiller is commonly applied
where the rotating impeller increases its pressure and
to large air conditioning systems, but may be used
temperature and discharges it into the condenser. Wa-
on other applications. The chiller consists of an open
ter flowing through the condenser tubes absorbs heat
motor mounted to a compressor (with integral speed
from the refrigerant vapor, causing it to condense. The
increasing gears), condenser, evaporator and variable
condenser water is supplied to the chiller from an ex-
flow control.
ternal source, usually a cooling tower. The condensed
The chiller is controlled by a modern state of the art refrigerant drains from the condenser into the liquid
Microcomputer Control Center that monitors its opera- return line, where the variable orifice meters the flow
tion. The Control Center is programmed by the opera- of liquid refrigerant to the evaporator to complete the
tor to suit job specifications. Automatic timed start-ups refrigerant circuit.
and shutdowns are also programmable to suit night-
The major components of a chiller are selected to han-
time, weekends, and holidays. The operating status,
dle the refrigerant, which would be evaporated at full
temperatures, pressures, and other information perti-
load design conditions. However, most systems will
nent to operation of the chiller are automatically dis-
be called upon to deliver full load capacity for only a
played and read on a graphic display. Other displays
relatively small part of the time the unit is in operation.
can be observed by pressing the keys as labeled on the
Control Center. The chiller with the OptiView Control Capacity Control
Center is compatible with an electro-mechanical start-
er, YORK Solid State Starter (optional), or Variable The major components of a chiller are selected for full
Speed Drive (optional). load capacities, therefore capacity must be controlled
to maintain a constant chilled liquid temperature leav-
In operation, a liquid (water or brine to be chilled) ing the evaporator. Prerotation vanes (PRV), located at
flows through the evaporator, where boiling refrigerant the entrance to the compressor impeller, compensate
absorbs heat from the liquid. The chilled liquid is then for variation in load (Refer to Figure 1 on Page 7).
piped to fan coil units or other air conditioning terminal
units, where it flows through finned coils, absorbing The position of these vanes is automatically controlled
heat from the air. The warmed liquid is then returned to through a lever arm attached to an electric motor lo-
the chiller to complete the chilled liquid circuit. cated outside the compressor housing. The automatic
adjustment of the vane position in effect provides the
performance of many different compressors to match
various load conditions from full load with vanes wide
open to minimum load with vanes completely closed.

7619A(D)

Figure 1 - Compressor Prerotation Vanes

JOHNSON CONTROLS 7
FORM 160.76-O1
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
ISSUE DATE: 6/15/2015

Refrigerant Flow-Thru Chiller


(Falling Film YK Mod G
Evaporator)
Refrigerant Flow-Thru Cross-Section Diagram
(Falling-Film Evaporator)

LEGEND
High Pressure Vapor

High Pressure Liquid Refrigerant

Low Pressure Liquid Refrigerant

Low Pressure Vapor

COMPRESSOR

HOT GAS PRE-ROTATION


BYPASS VALVE VANES

SUCTION

OPTIONAL HOT GAS


DISCHARGE BYPASS LINE

OPTIONAL LIQUID LEVEL


ISOLATION VALVE
VALVE

EVAPORATOR
CONDENSER

SUCTION
BAFFLE

LIQUID LEVEL
LIQUID LEVEL

SUB-COOLER

OPTIONAL
ISOLATION LD00924A
VALVE

Rev. 2 (10-11-2010)
Figure 2 - Refrigerant Flow-Thru Chiller (Falling Film Evaporator) Dan Sowers
dan.sowers-ext@jci.com
(717) 771-7535

8 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 2 - SYSTEM OPERATING PROCEDURES

Oil Heaters • If the oil level during operation is in the OVER


FULL region of the oil level indicator, oil should 2
If the oil heater is de-energized during a shutdown pe-
be removed from the oil reservoir, This reduces
riod, it must be energized for 12 hours prior to starting
the oil level to the OPERATING RANGE.
compressor, or remove all oil and recharge compres-
sor with new oil. (Refer to Oil Charging Procedure on • If the oil level during operation is in the LOW
Page 22.) OIL region of the oil level indicator, oil should be
added to the oil reservoir. (Refer to Oil Charging
Oil Heater Operation Procedure on Page 22.)
The oil heater operation is controlled by the OptiV-
Comply with EPA and local regulations
iew™ Control Center. The heater is turned on and off
when removing or disposing of refrigera-
to maintain the oil temperature differential to a value
tion system oil!
50°F (27.8°C) above the condenser saturation tem-
perature. This target value is maintained by the control
panel.
If the target value is greater than 160°F (71°C), the tar-
get defaults to 160°F (71°C). If the target value is less Start-Up Procedure
than 110°F (43.3°C), it defaults to 110°F (43.3°C).
Pre-Starting
To prevent overheating of the oil in the event of a con-
Prior to starting the chiller, observe the Optiview™
trol center component failure, the oil heater thermostat
Control Center – Operation and Maintenance (Form
(1HTR) is set to open at 180°F (82°C).
160.54-O1). Make sure the display reads SYSTEM
Checking The Oil Level In The READY TO START.
Oil Reservoir Vent any air from the chiller waterboxes
Proper operating oil level – During operation, the oil prior to starting the water pumps. Failure
level should fall to the OPERATING RANGE identified to do so will result in pass baffle damage.
on the vertical oil level indicator label (Refer to Figure 3
on Page 9).

Start-Up
1. If the chilled water pump is manually operated,
start the pump. The Control Center will not al-
low the chiller to start unless chilled liquid flow is
established through the unit. If the chilled liquid
pump is wired to the Microcomputer Control Cen-
ter the pump will automatically start, therefore,
this step is not necessary.
2. To start the chiller, press the COMPRESSOR
START switch. This switch will automatically
spring return to the RUN position. (If the unit
was previously started, press the STOP/RESET
side of the COMPRESSOR switch and then press
the START side of the switch to start the chill-
LD08647
er.) When the start switch is energized, the Con-
Figure 3 - Oil Level Indicator trol Center is placed in an operating mode and
any malfunction will be noted by messages on a
graphic display.

JOHNSON CONTROLS 9
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015

DISPLAY AUTO ZEROING DIFFERENTIAL


MESSAGE OIL PRESSURE TRANSDUCERS
"SYSTEM RUN"
ENERGIZE (OPEN)
OIL RETURN SOLENOID & LIQUID LINE
SOLENOID (J COMPRESSOR ONLY)
"SYSTEM PRELUBE" MAN. OIL
PUMP
** "VANES CLOSING DISABLED ** VANES CLOSING - TIME
BEFORE DEPENDENT ON INITIAL
SHUTDOWN" VANE POSITION

OIL PRESSURE CHECK


"SYSTEM
COASTDOWN"

OIL PUMP ON

"SYSTEM
SHUTDOWN" FLOW
BYPASS 150 SEC.
SWITCH (2.5 MIN)
0 10 13 45 50 110 VANES VANES 1800
START (0.17) (0.22) (0.75) (0.83) (1.83) START CLOSED (30)
TO RESTART
CLOSE
TIME IN SECONDS (MINUTES) LD06502

** Not for all shutdowns. Refer to “Display Messages” in manual Optiview™ Control Center – Operation and Maintenance (Form 160.54-O1).

Figure 4 - Chiller Starting Sequence And Shutdown Sequence (Em Starter And Solid
State Starter)

DISPLAY AUTO ZEROING DIFFERENTIAL


MESSAGE OIL PRESSURE TRANSDUCERS
"SYSTEM RUN"
ENERGIZE (OPEN)
OIL RETURN SOLENOID & LIQUID LINE
SOLENOID (J COMPRESSORS ONLY)
"SYSTEM PRELUBE" MAN. OIL
PUMP
** "VANES CLOSING DISABLED ** VANES CLOSING - TIME
BEFORE
DEPENDENT ON INITIAL
SHUTDOWN"
VANE POSITION

OIL PRESSURE CHECK


"SYSTEM
COASTDOWN"

OIL PUMP ON

"SYSTEM
SHUTDOWN" FLOW
BYPASS 150 SEC.
SWITCH (2.5 MIN)
0 10 13 45 50 110 VANES VANES 600
START (0.17) (0.22) (0.75) (0.83) (1.83) START CLOSED (10)
TO RESTART
RESTART
CLOSE (IF FIVE SUCCESSIVE
RESTARTS HAVE NOT
(ONLY AFTER FIFTH
TIME IN SECONDS (MINUTES) OCCURED) SUCCESSIVE RESTART)
LD06504

** Not for all shutdowns. Refer to “Display Messages” in manual Optiview™ Control Center – Operation and Maintenance (Form 160.54-O1).

Figure 5 - Chiller Starting Sequence And Shutdown Sequence (Variable Speed Drive)

10 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015

For display messages and information pertaining to the such as a cooling tower bypass, is not necessary for
operation refer to Optiview™ Control Center – Opera- most installations. The minimum entering condenser
tion and Maintenance (Form 160.54-O1). water temperature for full and part load conditions is
Any malfunctions which occur during specified in the chiller engineering guide. 2
STOP/RESET are also displayed. where:
% Load
Min. ECWT = LCWT – C RANGE + 5ºF + 12 ( 100 )
% Load
Min. ECWT = LCWT – C RANGE + 2.8ºC + 6.6 ( 100 )

ECWT = Entering Condensing Water Temperature


Chiller Operation
LCWT = Leaving Chilled Water Temperature
The unit capacity will vary to maintain the leaving
CHILLED LIQUID TEMPERATURE setpoint by the C Range = Condensing water temperature range at the
Pre-rotation Vanes which are modulated by an actua- given load condition.
tor under the control of the Microprocessor Board. The
vane control routine employs proportional plus deriva- At start-up, the entering condenser water temperature
tive (rate) control action. A drop in chilled liquid tem- may be as much as 25°F (14°C) colder than the stand-
perature will cause the actuator to close the Prerotation by return chilled water temperature. Cooling tower fan
Vanes to decrease chiller capacity. When the chilled cycling will normally provide adequate control of the
liquid temperature rises, the actuator will open the Pre- entering condenser water temperature on most instal-
rotation Vanes to increase the capacity of the chiller. lations.

However, the current draw (amperes) by the compres- Heat recovery chillers and chillers using optional head
sor motor is also limited to FLA setpoint by the micro- pressure control would use a signal provided by the
processor. microprocessor to control main condenser bundle heat
rejection or pressure, respectively.
If the load continues to decrease, after the Prerotation
Vanes are entirely closed, the chiller will be shut down Operating Log Sheet
by the Leaving Chilled Liquid – Low Temperature
Control. A permanent daily record of system operating condi-
tions (temperatures and pressures) recorded at regular
The coolant temperature inside any JCI-supplied liq- intervals throughout each 24 hour operating period
uid-cooled motor starter must be maintained above the should be kept.
dewpoint temperature in the equipment room to pre-
vent condensing water vapor inside the starter cabinet. An optional status printer is available for this purpose
Therefore, an additional temperature-controlled throttle or Figure 6 on Page 12 shows a log sheet used by
valve is needed in the flow path for the starter heat ex- Johnson Controls Personnel for recording test data on
changer to regulate cooling above the equipment room chiller systems. It is available from the factory in pads
dewpoint for applications using cooling sources other of 50 sheets each under Form 160.44-F7 and may be
than evaporative air-exchange methods, such as wells, obtained through the nearest Johnson Controls office.
bodies of water, and chilled water. The temperature Automatic data logging is possible by connecting the
control valve should be the type to open on increasing optional printer and programming the DATA LOG-
drive coolant temperature, fail-closed, and set for a tem- GER function.
perature above dewpoint. It can be requested as factory- An accurate record of readings serves as a valuable ref-
supplied on a chiller order by special quotation. erence for operating the system. Readings taken when
a system is newly installed will establish normal condi-
Condenser Water Temperature tions with which to compare later readings.
Control
For example, an increase in condenser approach tem-
The YORK chiller is designed to use less power by tak-
perature (condenser temperature minus leaving con-
ing advantage of lower than design temperatures that
denser water temperature) may be an indication of
are naturally produced by cooling towers throughout
dirty condenser tubes.
the operating year. Exact control of condenser water

JOHNSON CONTROLS 11
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015

Operating Inspections 7. Check the compressor motor current on the


SYSTEM Screen.
By following a regular inspection using the display
readings of the Microcomputer Control Center, and 8. Check for any signs of dirty or fouled condenser
maintenance procedure, the operator will avoid serious tubes. (The temperature difference between wa-
operating difficulty. The following list of inspections ter leaving condenser and saturated condensing
and procedures should be used as a guide. temperature should not exceed the difference re-
corded for a new unit by more than 4°F (2.2°C)).
Daily
1. Check OptiView™ Control Center displays. Weekly
1. Check the refrigerant charge. (Refer to Checking
2. If the compressor is in operation, check the bear- The Refrigerant Charge During Unit Shutdown
ing oil pressure on the SYSTEM Screen. Also on Page 28.)
check the oil level in the oil reservoir. Operating
oil level should be operating range of oil indicator. Monthly
Drain or add oil if necessary.
1. Leak check the entire chiller.
3. Check entering and leaving condenser water pres-
sure and temperatures for comparison with job Quarterly
design conditions. Condenser water temperatures 1. Perform chemical analysis of oil.
can be checked on the SYSTEM Screen.
Semi-Annually (or more often as required)
4. Check the entering and leaving chilled liquid tem-
peratures and evaporator pressure for compari- 1. Change and inspect compressor oil filter element.
son with job design conditions on the SYSTEM 2. Oil return system.
Screen.
a. Change dehydrator.
5. Check the condenser saturation temperature
(based upon condenser pressure sensed by the b. Check nozzle of eductor for foreign particles.
condenser transducer) on the SYSTEM Screen. 3. Check controls and safety cutouts.
6. Check the compressor discharge temperature on
the SYSTEM Screen. During normal operation
discharge temperature should not exceed 220°F
(104°C).

LD00467

23889A
*NOTE: These items can be printed by an electronic printer connected to the Microboard
and pressing the PRINT key on the Keypad, or automatically using the Data Logger feature.

Figure 6 - Liquid Chiller Log Sheets

12 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015

Annually (more often if necessary) 1. Push the soft shutdown key on the homescreen on
1. Drain and replace the oil in the compressor oil the OptiView panel or rapid stop with the COM-
sump. (Refer to Oil Charging Procedure on Page PRESSOR STOP/RESET switch. The compressor
22.) will stop automatically. The oil pump will contin- 2
ue to run for coastdown period. The oil pump will
2. Evaporator and Condenser. then stop automatically.
a. Inspect and clean water strainers. 2. Stop the chilled water pump (if not wired into
b. Inspect and clean tubes as required. the Microcomputer Control Center, in which
case it will shut off automatically simultaneously
c. Inspect end sheets. with the oil pump.) (The actual water pump con-
3. Compressor Drive Motor (See motor manufactur- tact operation is dependent upon the position of
ers maintenance and service instruction supplied Microboard jumper J54.)
with unit) 3. Open the switch to the cooling tower fan motors,
a. Clean air passages and windings per manu- if used.
facturers instructions.
4. The compressor sump oil heater is energized when
b. Meg motor windings – Refer to Figure 14 on the unit is stopped.
Page 28 for details.
Prolonged Shutdown
c. Lubricate per motor manufacturer recom-
mendations. If the chiller is to be shut down for an extended period
of time (for example, over the winter season), the fol-
4. Inspect and service electrical components as neces- lowing paragraphs outline the procedure to be followed.
sary.
1. Test all system joints for refrigerant leaks with a
5. Perform refrigerant analysis. leak detector. If any leaks are found, they should
If quarterly inspection indicates oil is fine, be repaired before allowing the system to stand
replacing the oil is not necessary for a long period of time.
During long idle periods, the tightness of the sys-
tem should be checked periodically.
2. If freezing temperatures are encountered while
the system is idle, carefully drain the cooling wa-
Need For Maintenance Or Service
ter from the cooling tower, condenser, condenser
If the system is malfunctioning in any manner or the pump, and the chilled water system-chilled water
unit is stopped by one of the safety controls, consult pump and coils.
the Operation Analysis Chart, Table 1 on Page 23 of
this manual. After consulting this chart, if you are un- Open the drains on the evaporator and condenser
able to make the proper repairs or adjustments to start liquid heads to assure complete drainage. (If a
the compressor or the particular trouble continues to Variable Speed Drive, drain its cooling system.
hinder the performance of the unit, please call the near- If Solid State Starter equipped drain liquid from
est Johnson Controls District Office. Failure to report starter cooling loop.)
constant troubles could damage the unit and increase 3. If freezing temperatures are encountered for peri-
the cost of repairs. ods longer than a few days, the refrigerant should
be recovered to containers to prevent leakage from
Stopping The System O-ring joints.
The Optiview™ Control Center can be programmed to 4. On the SETUP Screen, disable the clock. This
start and stop automatically (maximum, once each day) conserves the battery.
whenever desired. Refer to the Optiview™ Control
Center – Operation and Maintenance (Form 160.54- 5. Open the main disconnect switches to the com-
O1). To stop the chiller, proceed as follows: pressor motor, condenser water pump and the
chilled water pump. Open the 115 volt circuit to
the Control Center.

JOHNSON CONTROLS 13
FORM 160.76-O1
SECTION 2 - SYSTEM OPERATING PROCEDURES
ISSUE DATE: 6/15/2015

This Page Intentionally Left Blank

14 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 3 - SYSTEM COMPONENTS DESCRIPTION

General c. Low speed thrust bearing (forward and re-


verse).
The YORK Model YK Centrifugal Liquid Chiller is
completely factory-packaged including evaporator, 2. Compressor Driven Shaft (High Speed)
condenser, compressor, motor, lubrication system,
a. Forward and reverse high speed thrust
3
OptiView Control Center, and all interconnecting unit
bearing.
piping and wiring.
b. Two journal bearings.
Compressor
3. Speed Increasing Gears
The compressor is a single-stage centrifugal type pow-
ered by an open-drive electric motor. a. Meshing surfaces of drive and pinion gear
teeth.
The rotor assembly consists of a heat-treated alloy steel
drive shaft and impeller shaft with a cast aluminum, To provide the required amount of oil under the neces-
fully shrouded impeller. The impeller is designed for sary pressure to properly lubricate these parts, a motor
balanced thrust and is dynamically balanced and over- driven submersible oil pump is located in a remote oil
speed tested. The inserted type journal and thrust bear- sump.
ings are fabricated of aluminum alloy. Single helical Upon pressing of the COMPRESSOR START switch
gears with crowned teeth are designed so that more on the Control Center, the oil pump is immediately en-
than one tooth is in contact at all times. Gears are inte- ergized. After a 50 second pre-lube period, the com-
grally assembled in the compressor rotor support and pressor motor will start. The oil pump will continue to
are film lubricated. Each gear is individually mounted run during the entire operation of the compressor, and
in its own journal and thrust bearings. for 150 seconds during compressor coastdown.
The open-drive compressor shaft seal is a double bel- The submerged oil pump takes suction from the sur-
lows cartridge style with ceramic internal and atmo- rounding oil and discharges it to the oil cooler where
spheric seal faces. The seal is oil-flooded at all times heat is rejected. The oil flows from the oil cooler to
and is pressure-lubricated during operation. the oil filter. The oil leaves the filter and flows to the
emergency oil reservoir where it is distributed to the
Capacity Control
compressor bearings. The oil lubricates the compressor
Prerotation vanes (PRV) modulate chiller capacity rotating components and is returned to the oil sump.
from 100% to as low as 15% of design for normal air
conditioning applications. Operation is by an external, There is an emergency oil reservoir located at the high-
electric PRV actuator which automatically controls the est point in the lubrication system internally in the com-
vane position to maintain a constant leaving chilled liq- pressor. It provides an oil supply to the various bear-
uid temperature. ings and gears in the event of a system shutdown due
to power failure. The reservoir, located on the top of
Compressor Lubrication System the compressor, allows the oil to be distributed through
the passages by gravity flow, thus providing necessary
The chiller lubrication system consists of the oil pump, lubrication during the compressor coastdown.
oil filter, oil cooler and all interconnecting oil piping
and passages. There are main points within the com- Oil Pump
pressor which must be supplied with forced lubrication
as follows: For normal operation, the oil pump should operate at
all times during chiller operation.
1. Compressor Drive Shaft (Low Speed)
On shutdown of the system for any reason, the oil
a. Shaft seal. pump operates and continues to run for 150 seconds.
The system cannot restart during that time interval.
b. Front and rear journal bearings – one on each
side of driving gear.

JOHNSON CONTROLS 15
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015

OPTIVIEW CONTROL
CENTER

COMPRESSOR

SUCTION

RELIEF
VARIABLE
VALVES
SPEED
DRIVE

EVAPORATOR

LD15222

VARIABLE SPEED
SIGHT
OIL PUMP
GLASS
CONTROL BOX

FRONT VIEW

Figure 7 - System Components Front View

16 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015

MOTOR
COMPRESSOR

OIL FILTER
DISCHARGE
LINE

LD15223

LIQUID LINE
CONDENSER OIL PUMP
HOUSING

REAR VIEW

Figure 8 - System Components Rear View

JOHNSON CONTROLS 17
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015

COMPRESSOR ROTOR
SUPPORT SECTION

H.S.
SHAFT
SEAL
EMERGENCY
OIL RESERVE

HIGH
PRESSURE
TRANSDUCER

MAIN JOURNAL
AND THRUST
BEARING
IMPELLER

THRUST COLLAR BEARING


(PINION GEAR
HIGH SPEED SHAFT)
THRUST COVER
(PRV)
DOUBLE INLET
BELLOWS VALVES
SHAFT SEAL

LOW SPEED- THRUST


GEAR REAR COLLAR
BEARING BEARING

LOW LOW SPEED


SPEED GEAR THRUST
COVER

REFRIG.

SIGHT
HOT GLASSES
THERMISTOR

OIL OIL
HEATER COOLER
LOW OIL
ANGLE PRESSURE
DRAIN VALVE TRANSDUCER

OIL OIL SUBMERSIBLE


SUMP OIL TEMP.
PUMP OIL PUMP CONTROL
OIL SUCTION WITH 3-PHASE MOTOR
FILTER

OIL

LD15200

Figure 9 - Schematic Drawing – (Yk) Compressor Lubrication System

18 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015

Oil Heater and maintain reliable control. A specifically designed


spray distributor provides uniform distribution of re-
During long idle periods, the oil in the compressor oil
frigerant over the entire length to yield optimum heat
reservoir tends to absorb as much refrigerant as it can
transfer. The hybrid falling film evaporator design has
hold, depending upon the temperature of the oil and
suction baffles around the sides and above the falling
the pressure in the reservoir. As the oil temperature is
film section to prevent liquid refrigerant carryover into
lowered, the amount of refrigerant absorbed will be 3
the compressor.
increased. If the quantity of refrigerant in the oil be-
comes excessive, violent oil foaming will result as the A 1-1/2" (38 mm) liquid level sight glass is conve-
pressure within the system is lowered on starting. This niently located on the side of the shell to aid in deter-
foaming is caused by refrigerant boiling out of the oil mining proper refrigerant charge. The evaporator shell
as the pressure is lowered. If this foam reaches the oil contains a dual refrigerant relief valve arrangement set
pump suction, the bearing oil pressure will fluctuate at 235 psig (16.2 barg) on Q compressor models; or
with possible temporary loss of lubrication, causing the single-relief valve arrangement, if the chiller is sup-
oil pressure safety cutout to actuate and stop the sys- plied with optional refrigerant isolation valves. A 1"
tem. Refer to Optiview™ Control Center – Operation (25.4 mm) refrigerant charging valve is provided. The
and Maintenance (Form 160.54-O1). condenser is a shell and tube type, with a discharge
gas baffle to prevent direct high velocity impingement
Motor Driveline on the tubes. The baffle is also used to distribute the
The compressor motor is an open-drip-proof, squir- refrigerant gas flow properly for most efficient heat
rel cage, induction type constructed to YORK design transfer. An integral sub‑cooler is located at the bottom
specifications. 60 hertz motors operate at 3570 rpm. 50 of the condenser shell providing highly effective liquid
hertz motors operate at 2975 rpm. refrigerant subcooling to provide the highest cycle ef-
ficiency. The condenser contains dual refrigerant relief
The open motor is provided with a D-flange, cast iron valves set at 235 psig (16.2 barg).
adapter mounted to the compressor and supported by a
motor support. The removable waterboxes are fabricated of steel. The
design working pressure is 150 psig (10.3 barg) and
Motor drive shaft is directly connected to the compres- the boxes are tested at 225 psig (15.5 barg). Integral
sor shaft with a flexible disc coupling. This coupling steel water baffles are located and welded within the
has all metal construction with no wearing parts to as- waterbox to provide the required pass arrangements.
sure long life, and no lubrication requirements to pro- Stub‑out water nozzle connections with ANSI/AWWA
vide low maintenance. C-606 grooves are welded to the waterboxes. These
For units utilizing remote Electro-Mechanical starters, nozzle connections are suitable for ANSI/AWWA
a terminal box is provided for field connected conduit. C-606 couplings, welding or flanges, and are capped
Motor terminals are brought through the motor cas- for shipment. Plugged 3/4" (19 mm) drain and vent
ing into the terminal box. Jumpers are furnished for connections are provided in each waterbox.
three-lead type of starting. Motor terminal lugs are not
Refrigerant Flow Control
furnished. Overload/over current transformers are fur-
nished with all units. Refrigerant flow to the evaporator is controlled by a
variable orifice.
Heat Exchangers
A level sensor senses the refrigerant level in the con-
Evaporator and condenser shells are fabricated from denser and outputs an analog voltage to the Microboard
rolled carbon steel plates with fusion welded seams. that represents this level (0% = empty; 100% = full).
Heat exchanger tubes are internally enhanced type. Under program control, the Microboard modulates a
variable orifice to control the condenser refrigerant
The evaporator is a shell and tube type with customer level to a programmed setpoint. Other setpoints affect
process fluid flowing inside the tubes and refrigerant the control sensitivity and response. These setpoints
removing heat on the shell side via evaporation. Evap- must be entered at chiller commissioning by a qualified
orator codes 2*, 4*, 6* utilize a hybrid falling film de- service technician. Only a qualified service technician
sign. It contains a balance of falling film technology may modify these settings.
to optimize efficiency, minimize refrigerant charge,

JOHNSON CONTROLS 19
FORM 160.76-O1
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
ISSUE DATE: 6/15/2015

While the chiller is shut down, the orifice will be in the Optiview Control Center
fully open position causing the sensed level to be ap-
The OptiView Control Center is factory-mounted,
proximately 0%. When the chiller is started, after the
wired and tested. The electronic panel automatically
vane motor end switch (VMS) opens when entering
controls the operation of the unit in meeting system
SYSTEM RUN, if actual level is less than the level
cooling requirements while minimizing energy usage.
setpoint, a linearly increasing ramp is applied to the lev-
For detailed information on the Control Center, refer to
el setpoint. This ramp causes the setpoint to go from the
SECTION 2 - SYSTEM OPERATING PROCEDURES
initial refrigerant level (approximately 0%) to the pro-
of this manual.
grammed setpoint over a programmable period of time.
If the actual level is greater than the setpoint when the Solid State Starter (Optional)
VMS opens, there is no pulldown period, it immedi- The Solid State Starter is a reduced voltage starter that
ately begins to control to the programmed setpoint. controls and maintains a constant current flow to the
motor during start-up. It is mounted on the chiller. Pow-
While the chiller is running, the refrigerant level is nor-
er and control wiring between the starter and chiller
mally controlled to the level setpoint. However, any-
are factory installed. The starter enclosure is NEMA-1
time the vanes fully close (VMS closes), normal level
with a hinged access door with lock and key. Electrical
control is terminated, any refrigerant level setpoint in
lugs for incoming power wiring are provided.
effect is cancelled and the outputs to the level control
will be constant open. Variable Speed Drive (Optional)
Optional Service Isolation Valves A Variable Speed Drive can be factory packaged with
the chiller. It is designed to vary the compressor mo-
If your chiller is equipped with optional service iso-
tor speed and prerotation vane position by controlling
lation valves on the discharge and liquid line, these
the frequency and voltage of the electrical power to
valves must remain open during operation. These
the motor. Operational information is contained in the
valves are used for isolating the refrigerant charge in
Variable Speed Drive – Operation (Form 160.00-O1).
either the evaporator or condenser to allow service ac-
The control logic automatically adjusts motor speed
cess to the system. A refrigerant pump-out unit will be
and compressor prerotation vane position for maxi-
required to isolate the refrigerant.
mum part load efficiency by analyzing information fed
Isolation of the refrigerant in this system to it by sensors located throughout the chiller.
must be performed by a qualified service
technician.

Optional Hot Gas Bypass


Hot gas bypass is optional and is used to eliminate
compressor surge during light load or high head op-
eration. The OptiView control panel will automati-
cally modulate the hot gas valve open and closed as
required. Adjustment of the hot gas control valve must
be performed by a qualified service technician follow-
ing the Hot Gas Set-up procedure.
Changes in chilled water flow will require
re-adjustment of the hot gas control to
insure proper operation.

20 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 4 - OPERATIONAL MAINTENANCE

Oil Return System Changing The Dehydrator


The oil return system continuously maintains the To change the dehydrator, use the following procedure:
proper oil level in the compressor oil sump (Refer to
Figure 10 on Page 21). 1. Isolate the dehydrator at the stop valves.
2. Remove the dehydrator (Refer to Figure 10 on
High pressure condenser gas flows continuously Page 21).
through the eductor inducing the low pressure, oil rich 4
3. Assemble the new filter-drier.
liquid to flow from the evaporator, through the dehy-
drator to the compressor sump. 4. Open evaporator stop valve and check dehydrator
connections for refrigerant leaks.
5. Open all the dehydrator stop valves.

COMPRESSOR

SOLENOID VALVE

CONDENSER

EVAPORATOR

CHECK VALVE OIL EDUCTOR BLOCK

SOLENOID VALVE

STOP VALVE DEHYDRATOR

STOP VALVE

LD08578

Figure 10 - Oil Return System

JOHNSON CONTROLS 21
FORM 160.76-O1
SECTION 4 - OPERATIONAL MAINTENANCE
ISSUE DATE: 6/15/2015

The Oil Charge cover plate. (Refer to Figure 11 on Page 22) Do


not tighten the connection at the charging valve
The nominal oil charge for Q3-Q7 YK compressors is
until after the air is forced out by pumping a few
11 gallons of type YORK K or YORK H oil.
strokes of the oil pump. This fills the lines with
New YORK Refrigeration oil must be used in the cen- oil and prevents air from being pumped into the
trifugal compressor. Since oil absorbs moisture when system.
exposed to the atmosphere, it should be kept tightly
3. Open the oil charging valve and pump oil into the
capped until used.
system until oil level in the compressor oil reser-
voir is in the OVER FULL region of the oil level
Oil Charging Procedure
indicator label. Close the charging valve and dis-
During operation the compressor oil level must be connect the hand oil pump.
maintained in the OPERATING RANGE identified
on the vertical oil level indicator. If the oil level falls 4. As soon as oil charging is complete, close the
into the lower sight glass, it is necessary to add oil to power supply to the starter to energize the oil
the compressor oil reservoir. The oil should be charged heater. This will keep the concentration of refrig-
into the oil reservoir using the YORK Oil Charging erant in the oil to a minimum.
Pump – YORK Part No. 070-10654. To charge oil into When the oil reservoir is initially charged with oil, the
the oil reservoir, proceed as follows: oil pump should be started manually to fill the lines,
passages, oil cooler and oil filter. This will lower the
1. The unit must be shut down.
oil level in the reservoir. It may then be necessary to
2. Immerse the suction connection of the oil charging add oil to bring the level back into the OPERATING
pump in a clean container of new oil and connect RANGE of the oil level indicator label.
the pump discharge connection to the oil charg-
ing valve (A) located on the remote oil reservoir

OIL
CHARGING
PUMP

LD08648 LD08579
OIL CHARGING VALVE

Figure 11 - Charging Oil Reservoir With Oil

22 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 5 - TROUBLESHOOTING

Table 1 - Operation Analysis Chart


RESULTS POSSIBLE CAUSE REMEDY
1. SYMPTOM: ABNORMALLY  HIGH  DISCHARGE  PRESSURE
Temperature difference between
condensing temperature and water off Air in condenser.
condenser higher than normal.
Clean condenser tubes. Check water
Condenser tubes dirty or scaled.
conditioning.
High discharge pressure. Reduce condenser water inlet
High condenser water temperature. temperature. (Check cooling tower and 5
water circulation.)
Temperature difference between
condenser water on and water off Increase the quantity of water through
Insufficient condensing water flow.
higher than normal, with normal the condenser to proper value.
evaporator pressure.
2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURE
Temperature difference between Check for leaks and charge refrigerant
Insufficient charge of refrigerant.
leaving chilled water and refrigerant in into system.
evaporator greater than normal with
Variable orifice problem. Remove obstruction.
high discharge temperature.
Temperature difference between leaving
chilled water and refrigerant in the
Evaporator tubes dirty or restricted. Clean evaporator tubes.
evaporator greater than normal with
normal discharge temperature.
Check prerotation vane motor operation
Temperature of chilled water too low
Insufficient load for system capacity. and setting of low water temperature
with with low motor amperes.
cutout.
3. SYMPTOM: HIGH EVAPORATOR PRESSURE
Check the prerotation vane motor
Prerotation vanes fail to open.
positioning circuit.
High chilled water temperature. Be sure the vanes are wide open
System overload. (without overloading the motor) until the
load decreases.
4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHED
Check rotation of oil pump (Electrical
Oil pump running in wrong direction.
Low oil pressure displayed on control Connections).
center; compressor will not start. Troubleshoot electrical problem with oil
Oil pump not running.
pump VSD.
5. SYMPTOM: UNUSUALLY HIGH OIL PRESSURE DEVELOPS WHEN OIL PUMP RUNS
Unusually high oil pressure is
displayed when the oil pressure High oil pressure. Transducer Replace low or high oil pressure
display key is pressed when the oil defective. transducer.
pump is running.

JOHNSON CONTROLS 23
FORM 160.76-O1
SECTION 5 - TROUBLESHOOTING
ISSUE DATE: 6/15/2015

TABLE 1 - OPERATION ANALYSIS CHART (CONT'D)

RESULTS POSSIBLE REMEDY


6. SYMPTOM: OIL PUMP VIBRATES OR IS NOISY
Oil pump vibrates or is extremely noisy
Oil not reaching pump suction inlet in
with some oil pressure when pressing Check oil level.
sufficient quantity.
OIL PRESSURE display key.
When oil pump is run without
an oil supply it will vibrate
and become extremely noisy.
Worn or failed oil pump. Repair/Replace oil pump.

7. SYMPTOM: REDUCED OIL PUMP CAPACITY


Excessive end clearance pump.
Inspect and replace worn parts.
Oil pump pumping capacity. Other worn pump parts.
Partially blocked oil supply inlet. Check oil inlet for blockage.
8. SYMPTOM: OIL PRESSURE GRADUALLY DECREASES (Noted by Observation of Daily Log Sheets)
When oil pump VSD frequency
increases to 55 + hz to maintain target Oil filter is dirty. Change oil filter.
oil pressure.
9. SYMPTOM: OIL PRESSURE SYSTEM CEASES TO RETURN AN OIL/REFRIGERANT SAMPLE
Filter-drier in oil return system dirty. Replace old filter-drier with new.
Oil refrigerant return not functioning. Remove jet, inspect for dirt.
Jet or orifice of oil return jet clogged.
Remove dirt using solvent and replace.
10. SYMPTOM: OIL PUMP FAILS TO DELIVER OIL PRESSURE
No oil pressure registers when pressing
Faulty oil pressure transducer.
OIL PRESSURE display key when oil Replace oil pressure transducer.
Faulty wiring/connectors.
pump runs.

24 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 6 - MAINTENANCE

Renewal Parts To test with R-134a, proceed as follows:


For any required Renewal Parts, refer to the Renewal 1. With no pressure in the system, charge R-134a gas
Parts – Unit (Form 160.75-RP1). into the system through the charging valve to a
pressure of 2 PSIG (14 kPa).
Checking System For Leaks
2. Build up the system pressure with dry nitrogen to
Leak Testing During Operation approximately 75 to 100 PSIG (517 to 690 kPa).
The refrigerant side of the system is carefully pressure To be sure that the concentration of refrigerant has
tested and evacuated at the factory. reached all part of the system, slightly open the oil
charging valve and test for the presence of refrig-
After the system has been charged, the system should erant with a leak detector.
be carefully leak tested with a R-134a compatible leak
detector to be sure all joints are tight. 3. Test around each joint and factory weld. It is im-
portant that this test be thoroughly and carefully 6
If any leaks are indicated, they must be repaired im- done, spending as much time as necessary and us-
mediately. Usually, leaks can be stopped by tighten- ing a good leak detector.
ing flare nuts or flange bolts. However, for any major
repair, the refrigerant charge must be removed. (Refer 4. To check for refrigerant leaks in the evaporator
to Handling Refrigerant For Dismantling And Repairs and condenser, open the vents in the evaporator
on Page 28) and condenser heads and test for the presence of
refrigerant. If no refrigerant is present, the tubes
Conducting R-134a Pressure Test and tube sheets may be considered tight. If refrig-
erant is detected at the vents, the heads must be
With the R-134a charge removed and all known leaks
removed, the leak located (by means of soap test
repaired, the system should be charged with a small
or leak detector) and repaired.
amount of R-134a mixed with dry nitrogen so that
electronic leak detector can be used to detect any leaks
too small to be found by the soap test.

EVACUATION AND DEHYDRATION OF UNIT

27385A(D)

STOP VALVE

CHARGING
VALVE
WET BULB TEMPERATURE
INDICATOR OR VACUUM GAUGE VACUUM PUMP

LD00949

Figure 12 - Evacuation Of Chiller

JOHNSON CONTROLS 25
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

Table 2 - System Pressures

*GAUGE ABSOLUTE
BOILING
INCHES OF TEMPERATURES
MERCURY (HG) OF
MILLIMETERS OF
BELOW ONE PSIA MICRONS WATER
MERCURY (HG)
STANDARD °F
ATMOSPHERE
0 14.696 760. 760,000 212
10.24" 9.629 500. 500,000 192
22.05" 3.865 200. 200,000 151
25.98" 1.935 100. 100,000 124
27.95" .968 50. 50,000 101
28.94" .481 25. 25,000 78
29.53" .192 10. 10,000 52
29.67" .122 6.3 6,300 40
29.72" .099 5. 5,000 35
WATER
29.842" .039 2. 2,000 15 FREEZES
29.882" .019 1.0 1,000 +1
29.901" .010 .5 500 –11
29.917" .002 .1 100 –38
29.919" .001 .05 50 –50
29.9206" .0002 .01 10 –70
29.921" 0 0 0
*One standard atmosphere = 14.696 Psia NOTES: PSIA = Lbs. per sq. in. gauge pressure
= 760 mm Hg. absolute pressure at 32°F = Pressure above atmosphere
= 29.921 inches Hg. absolute at 32°F PSIA = Lbs. per sq. in. absolute pressure
= Sum of gauge plus atmospheric pressure

Vacuum Testing DO NOT USE STEAM. A suggested method is


After the pressure test has been completed, the vacuum to connect a hose between the source of hot water
test should be conducted as follows: under pressure and the evaporator head drain con-
nection, out the evaporator vent connection, into
1. Connect a high capacity vacuum pump, with in- the condenser head drain and out the condenser
dicator, to the system charging valve as shown in vent. To avoid the possibility of causing leaks, the
Figure 12 on Page 25 and start the pump. (Re- temperature should be brought up slowly so that
fer to Vacuum Dehydration on Page 27.) the tubes and shell are heated evenly.
2. Open wide all system valves. Be sure all valves to 5. Close the system charging valve and the stop
the atmosphere are closed. valve between the vacuum indicator and the vac-
uum pump. Then disconnect the vacuum pump
3. Operate the vacuum pump in accordance with
leaving the vacuum indicator in place.
VACUUM DEHYDRATION until a wet bulb
temperature of +32°F or a pressure of 5 mm Hg 6. Hold the vacuum obtained in Step 3 in the system
is reached. Refer to Table 2 on Page 26 for cor- for 8 hours; the slightest rise in pressure indicates a
responding values of pressure. leak or the presence of moisture, or both. If, after 24
hours the wet bulb temperature in the vacuum indi-
4. To improve evacuation circulate hot water (not
cator has not risen above 40°F (4.4°C) or a pressure
to exceed 125°F, 51.7ºC) through the evaporator
of 6.3 mm Hg, the system may be considered tight.
and condenser tubes to thoroughly dehydrate the
shells. If a source of hot water is not readily avail- 7. If the vacuum does not hold for 8 hours within the
able, a portable water heater should be employed. limits specified in Step 6 above, the leak must be
found and repaired.

26 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

Be sure the vacuum indicator is valved off taken place the pressure and temperature will continue
while holding the system vacuum and be to drop until eventually a temperature of 35°F (1.6°C)
sure to open the valve between the vacuum or a pressure of 5 mm Hg. is reached.
indicator and the system when checking
the vacuum after the 8 hour period. When this point is reached, practically all of the air has
been evacuated from the system, but there is still a small
amount of moisture left. In order to provide a medium
Vacuum Dehydration for carrying this residual moisture to the vacuum pump,
To obtain a sufficiently dry system, the following in- nitrogen should be introduced into the system to bring
structions have been assembled to provide an effective it to atmospheric pressure and the indicator temperature
method for evacuating and dehydrating a system in the will return to approximately ambient temperature. Close
field. Although there are several methods of dehydrating off the system again, and start the second evacuation.
a system, we are recommending the following, as it pro- The relatively small amount of moisture left will be
duces one of the best results, and affords a means of ob- carried out through the vacuum pump and the tem-
taining accurate readings as to the extent of dehydration. perature or pressure shown by the indicator should
drop uniformly until it reaches a temperature of 35°F 6
The equipment required to follow this method of dehy-
dration consists of a wet bulb indicator or vacuum gauge, (1.6°C) or a pressure of 5 mm Hg.
a chart showing the relation between dew point tempera- When the vacuum indicator registers this temperature
ture and pressure in inches of mercury (vacuum), (Refer or pressure, it is a positive sign that the system is evac-
to Table 2 on Page 26) and a vacuum pump capable of uated and dehydrated to the recommended limit. If this
pumping a suitable vacuum on the system. level cannot be reached, it is evident that there is a leak
somewhere in the system. Any leaks must be corrected
Operation
before the indicator can be pulled down to 35°F or 5
Dehydration of a refrigerant system can be obtained mm Hg. in the primary evacuation.
by this method because the water present in the system
reacts much as a refrigerant would. By pulling down During the primary pulldown, keep a careful watch on
the pressure in the system to a point where its satu- the wet bulb indicator temperature, and do not let it fall
ration temperature is considerably below that of room below 35°F (1.6°C). If the temperature is allowed to
temperature, heat will flow from the room through the fall to 32°F (0°C), the water in the test tube will freeze,
walls of the system and vaporize the water, allowing and the result will be a faulty temperature reading.
a large percentage of it to be removed by the vacuum
pump. The length of time necessary for the dehydra-

NITROGEN ADDED
tion of a system is dependent on the size or volume of
INDICATOR READING -°F

SEC ACUA
PRIM
the system, the capacity and efficiency of the vacuum ARY

EV
EVAC

ON
UATI
pump, the room temperature and the quantity of water ON

DAR ION
present in the system. By the use of the vacuum indi-
T
Y
cator as suggested, the test tube will be evacuated to
the same pressure as the system, and the distilled water
will be maintained at the same saturation temperature
as any free water in the system, and this temperature
can be observed on the thermometer.
If the system has been pressure tested and found to be
TIME
tight prior to evacuation, then the saturation tempera- LD00474

ture recordings should follow a curve similar to the typ-


ical saturation curve shown as Figure 13 on Page 27. Figure 13 - Saturation Curve

The temperature of the water in the test tube will drop


as the pressure decreases, until the boiling point is Refrigerant Charging
reached, at which point the temperature will level off To avoid the possibility of freezing liquid within the
and remain at this level until all of the water in the evaporator tubes when charging an evacuated system,
shell is vaporized. When this final vaporization has only refrigerant vapor from the top of the drum or cyl-

JOHNSON CONTROLS 27
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

inder must be admitted to the system pressure until the The refrigerant charge level must be checked after the
system pressure is raised above the point correspond- pressure and temperature have equalized between the
ing to the freezing point of the evaporator liquid. For condenser and evaporator. This would be expected to be
water, the pressure corresponding to the freezing point 4 hours or more after the compressor and water pumps
is 8.54 PSIG (58.9 kPa) for R-134a (at sea level). are stopped. The level should visible in the sight glass.
While charging, every precaution must be taken to pre- Charge the refrigerant in accordance with the meth-
vent moisture laden air from entering the system. Make od shown under the REFRIGERANT CHARGING,
up a suitable charging connection from new copper tub- above. The refrigerant level should be observed and
ing to fit between the system charging valve and the fit- the level recorded after initial charging.
ting on the charging drum. This connection should be
Handling Refrigerant For Dismantling
as short as possible but long enough to permit sufficient
And Repairs
flexibility for changing drums. The charging connection
should be purged each time a full container of refriger- If it becomes necessary to open any part of the refriger-
ant is connected and changing containers should be done ant system for repairs, it will be necessary to remove
as quickly as possible to minimize the loss of refrigerant. the charge before opening any part of the unit. If the
chiller is equipped with optional valves, the refrigerant
Refrigerant may be furnished in cylinders containing can be isolated in either the condenser or evaporator /
either 30, 50, 125, 1,025 or 1750 lbs. (13.6, 22.6, 56.6, compressor while making any necessary repairs.
464 or 794 kg) of refrigerant.
Megging The Motor
The nameplate on the chiller contains the
correct refrigerant charge information While the main disconnect switch and compressor mo-
for the chiller. tor starter are open, meg the motor as follows:
1. Using a megohm meter (megger), meg between
phases and each phase to ground (Refer to Figure 14
on Page 28); these readings are to be interpreted
Checking The Refrigerant Charge using the graph shown in Figure 15 on Page 29.
During Unit Shutdown 2. If readings fall below shaded area, remove exter-
The refrigerant charge is specified for each chiller model. nal leads from motor and repeat test.
Charge the correct amount of refrigerant and record the Motor is to be megged with the starter at
level in the evaporator sight glass. ambient temperature after 24 hours of
idle standby.
The refrigerant charge should always be checked and
trimmed when the system is shut down.

MEGOHM
BETWEEN MEGOHM
WINDINGS METER

MAIN DISCONNECT
(OPEN) MEGOHM EACH
WINDING TO GROUND
STARTER (OPEN)
MEGOHM METER
LD00475

Figure 14 - Diagram, Megging Motor Windings

28 JOHNSON CONTROLS
Minimum Insulation Resistance vs. Temperature (per IEEE Std 43)
Open Motors

1. Megger readings should be taken after Megger voltage has been applied one minute.
FORM 160.76-O1

2. If insulation resistance lies to the right of the applicable curve the motor is acceptable for use.

JOHNSON CONTROLS
ISSUE DATE: 6/15/2015

3. If insulation resistance lies to the left of the applicable curve, the motor should not be run. The motor
should be heated to 250°F in an effort to remove moisture and obtain an acceptable reading at room
ambient. This can be done either by baking in a forced hot air oven or, if proper voltage is available,
apply 5 - 10% of rated voltage to motor windings.

4. A
 ny gradual or abrupt decrease in Megger readings over an extended period of time is an indication of
deterioration of insulation and / or moisture absorption or oil / dirt contamination.

5. Megger readings of individual phase coils of 200 - 600V motors should be made with coils not under
test being grounded.

LEGEND
A 2
 00 - 600V
DELTA CONN.
B 2
 300V
(Entire Windings)
C 2
 00 - 600V

TEMPERATURE – °F
(Per Phase)
Note 5
D 3
 300 - 4160V
(Entire Windings)

Figure 15 - Motor Starter Temperature And Insulation Resistances


MEGOHMS

29
SECTION 6 - MAINTENANCE

LD00476
6
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

Condensers And Evaporators General Tube Fouling


Maintenance of condenser and evaporator shells is im- Fouling of the tubes can be due to deposits of two types
portant to provide trouble free operation of the chiller. as follows:
The water side of the tubes in the shell must be kept
clean and free from scale. Proper maintenance such as 1. Rust or sludge – which finds its way into the
tube cleaning, and testing for leaks, is covered on the tubes and accumulates there. This material usu-
following pages. ally does not build up on the inner tube surfaces
as scale, but does interfere with the heat transfer.
Chemical Water Treatment Rust or sludge can generally be removed from the
tubes by a thorough brushing process.
Since the mineral content of the water circulated
through evaporators and condensers varies with almost 2. Scale – due to mineral deposits. These deposits,
every source of supply, it is possible that the water be- even though very thin and scarcely detectable
ing used may corrode the tubes or deposit heat resistant upon physical inspection, are highly resistant to
scale in them. Reliable water treatment companies are heat transfer. They can be removed most effec-
available in most larger cities to supply a water treat- tively by circulating an acid solution through the
ing process which will greatly reduce the corrosive and tubes.
scale forming properties of almost any type of water.
Tube Cleaning Procedures
As a preventive measure against scale and corrosion
and to prolong the life of evaporator and condenser Brush Cleaning of Tubes
tubes, a chemical analysis of the water should be made If the tube consists of dirt and sludge, it can usually be
preferably before the system is installed. A reliable wa- removed by means of the brushing process. Drain the
ter treatment company can be consulted to determine water sides of the circuit to be cleaned (cooling wa-
whether water treatment is necessary, and if so, to fur- ter or chilled water) remove the heads and thorough-
nish the proper treatment for the particular water con- ly clean each tube with a soft bristle bronze or nylon
dition. brush. DO NOT USE A STEEL BRISTLE BRUSH. A
steel brush may damage the tubes.
Cleaning Evaporator And Condenser Tubes
Improved results can be obtained by admitting water
Evaporator into the tube during the cleaning process. This can be
It is difficult to determine by any particular test wheth- done by mounting the brush on a suitable length of 1/8"
er possible lack of performance of the water evaporator pipe with a few small holes at the brush end and con-
is due to fouled tubes alone or due to a combination necting the other end by means of a hose to the water
of troubles. Trouble which may be due to fouled tubes supply.
is indicated when, over a period of time, the cooling
The tubes should always be brush cleaned before acid
capacity decreases and the split (temperature differ-
cleaning.
ence between water leaving the evaporator and the
refrigerant temperature in the evaporator) increases. A Acid Cleaning Of Tubes
gradual drop-off in cooling capacity can also be caused
by a gradual leak of refrigerant from the system or by a If the tubes are fouled with a hard scale deposit, they
combination of fouled tubes and shortage of refrigerant may require acid cleaning. It is important that before
charge. An excessive quantity of oil in the evaporator acid cleaning, the tubes be cleaned by the brushing
can also contribute to erratic performance. process described above. If the relatively loose foreign
material is removed before the acid cleaning, the acid
Condenser solution will have less material to dissolve and flush
from the tubes with the result that a more satisfactory
In a condenser, trouble due to fouled tubes is usually
cleaning job will be accomplished with a probable sav-
indicated by a steady rise in head pressure, over a pe-
ing of time.
riod of time, accompanied by a steady rise in condens-
ing temperature, and noisy operation. These symptoms
may also be due to foul gas buildup. Purging will re-
move the foul gas revealing the effect of fouling.

30 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

Acid cleaning should only be performed 3. With nitrogen or dry air, blow out the tubes to
by an expert. Please consult your local clear them of traces of refrigerant laden moisture
water treatment representative for as- from the circulation water. As soon as the tubes
sistance in removing scale buildup and are clear, a cork should be driven into each end
preventative maintenance programs to of the tube. Pressurize the dry system with 50 to
eliminate future problems. COMMER- 100 PSIG (345 to 690 kPa) of nitrogen. Repeat
CIAL ACID CLEANING this with all of the other tubes in the suspected
section or, if necessary, with all the tubes in the
In many major cities, commercial organizations now evaporator or condenser. Allow the evaporator or
offer a specialized service of acid cleaning evaporators condenser to remain corked up to 12 to 24 hours
and condensers. If acid cleaning is required, YORK before proceeding. Depending upon the amount
recommends the use of this type of organization. The of leakage, the corks may blow from the end of a
Dow Industries Service Division of the Dow Chemical tube, indicating the location of the leakage. If not,
Company, Tulsa, Oklahoma, with branches in principal if will be necessary to make a very thorough test
cities is one of the most reliable of these companies. with the leak detector.
6
Testing For Evaporator And Condenser Tube 4. After the tubes have been corked for 12 to 24
Leaks hours, it is recommended that two men working
at both ends of the evaporator carefully test each
Evaporator and condenser tube leaks in R-134a sys-
tube – one man removing corks at one end and
tems may result in refrigerant leaking into the water
the other at the opposite end to remove corks and
circuit, or water leaking into the shell depending on the
handle the leak detector. Start with the top row of
pressure levels. If refrigerant is leaking into the water,
tubes in the section being investigated. Remove
it can be detected at the liquid head vents after a period
the corks at the ends of one tube simultaneously
of shutdown. If water is leaking into the refrigerant,
and insert the exploring tube for 5 seconds – this
system capacity and efficiency will drop off sharply. If
should be long enough to draw into the detec-
a tube is leaking and water has entered the system, the
tor any refrigerant gas that might have leaked
evaporator and condenser should be valved off from
through the tube walls. A fan placed at the end of
the rest of the water circuit and drained immediately to
the evaporator opposite the detector will assure
prevent severe rusting and corrosion. The refrigerant
that any leakage will travel through the tube to
system should then be drained and purged with dry ni-
the detector.
trogen to prevent severe rusting and corrosion. If a tube
leak is indicated, the exact location of the leak may be 5. Mark any leaking tubes for later identification.
determined as follows:
6. If any of the tube sheet joints are leaking, the leak
1. Remove the heads and listen at each section of should be indicated by the detector. If a tube sheet
tubes for a hissing sound that would indicate gas leak is suspected, its exact location may be found
leakage. This will assist in locating the section of by using a soap solution. A continuous buildup of
tubes to be further investigated. If the probable bubbles around a tube indicates a tube sheet leak.
location of the leaky tubes has been determined,
treat that section in the following manner (if the
location is not definite, all the tubes will require
investigations).
2. Wash off both tube heads and the ends of all tubes
with water.
Do not use carbon tetrachloride for this
purpose since its fumes give the same
flame discoloration that the refrigerant
does.

JOHNSON CONTROLS 31
FORM 160.76-O1
SECTION 6 - MAINTENANCE
ISSUE DATE: 6/15/2015

Compressor
Maintenance for the compressor assembly consists rings can contact the impeller and account for some
of checking the operation of the oil return system and aluminum particles to accumulate in the oil filter, espe-
changing the dehydrator, checking and changing the oil, cially during the initial start up and first several months
checking and changing the oil filters, checking the op- of operation. However, if aluminum particles continue
eration of the oil heater, checking the operation of the oil to accumulate and the same conditions continue to stop
pump, and observing the operation of the compressor. the unit operation after a new filter is installed, notify
the nearest Johnson Controls office to request the pres-
Internal wearing of compressor parts could be a seri- ence of a Johnson Controls Service Technician.
ous problem caused by improper lubrication, brought
about by restricted oil lines, passages, or dirty oil fil- Electrical Controls
ters. If the unit is shutting down on (HOT) High Oil
Temperature or Low Oil Pressure (OP), change the oil For information covering the OptiView™ Control
filter element. Examine the oil filter element for the Center operation, refer to the Optiview™ Control Cen-
presence of aluminum particles. Aluminum gas seal ter – Operation and Maintenance (Form 160.54-O1).

32 JOHNSON CONTROLS
FORM 160.76-O1
ISSUE DATE: 6/15/2015

SECTION 7 - PREVENTIVE MAINTENANCE

It is the responsibility of the owner to provide the nec- Motor Re-lubrication Instruction
essary daily, monthly and yearly maintenance require-
All motor manufacturers have slightly different re-
ments of the system.
quirements for the exact amount of grease to be added,
IMPORTANT – If a unit failure occurs and the exact interval for re-greasing. The suggested
due to improper maintenance during the amount should be 1.5 cubic inches of grease, and the
warranty period; Johnson Controls will interval should be 1000 hours to 1400 hours between
not be liable for costs incurred to return re-lubrications. York Optiview control panels provide
the system to satisfactory operation. a warning message to re-lubricate bearings at 1000
hours. When the run clock reaches 1400 hours without
In any operating system it is most important to pro- lubrication, software will shut down the chiller until
vide a planned maintenance and inspection of its func- re-lubrication has been acknowledged.
tioning parts to keep it operating at its peak efficiency.
Therefore, the following maintenance should be per- Grease Gun Calibration -
formed when prescribed. Grease guns should be calibrated to determine the
number of pumps required to get 1.5 cubic inches of
Compressor grease. This can be accomplished by forming an open- 7
1. Oil Filter – When oil pump VSD frequency in- top cardboard cube, one inch by one inch by one inch.
creases to 55 hz to maintain target oil pressure. Pump grease into this container until grease is level
with the top, counting the number of pumps. When
When the oil filter is changed, it should be in- the grease is level with the top, this is the amount for
spected thoroughly for any aluminum particles one cubic inch. Multiply this number of pumps times
which would indicate possible bearing wear. 1.5 to get the number of pumps for York chiller motor
If aluminum particles are found this should be bearings.
brought to the attention of the nearest Johnson
Over-greasing can be as detrimental as
Controls office for their further investigation and
lack of greasing. A bearing housing that
recommendations.
is totally filled with grease can run 20 de-
2. Oil Changing – The oil in the compressor must grees centigrade higher temperature than
be changed annually or earlier if it becomes dark one with the proper amount of grease.
or cloudy. However, quarterly oil analysis can
eliminate the need for an annual change provided
Type of Grease –
the analysis indicates there is no problem with the
oil. All standard York chiller motors utilize a polyurea
grease, formulated for high-speed rolling element
Compressor Motor bearings. Only two greases are approved by all our
1. Check motor mounting screws frequently to in- motor manufacturers, and these are:
sure tightness. 1st Choice: Exxon / Mobil Polyrex EM -
2. Meg motor windings annually to check for dete- Grainger Part Number 5XB54
rioration of windings. 2nd Choice: Texaco / Chevron SRI #2
Greased Bearings There are a few exceptions, such as Reliance Q-frame
Motor Operation and Maintenance manuals are sup- motors built from 1997 to 2003, and some special or-
plied with the chillers providing maintenance sched- der motors such as high-voltage motors from ABB. In
ules and instructions for the specific motors. The fol- these cases use only the grease called for by the mo-
lowing are lubrication schedules for the most common tor manufacturer. In the case of those Reliance mo-
motors: tors, there is a metal tag affixed to the motor calling for

JOHNSON CONTROLS 33
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015

Texaco Premium RB. This is a lithium based lubricant Mixing different greases is not recom-
and absolutely should never be mixed with polyurea mended
grease. If you are unable to locate this specific Texa-
co product, another approved lithium based grease is
Shell Alvania RL in NLGI #3.
The motors on York chillers must utilize the greas- Additional information on motor lubrica-
es mentioned above. Approval of any other type of tion and other service issues can be found
grease will not be granted. Typically, we also receive in the A-C Motors Instruction Manual.
requests to use synthetic grease products, often from
very well-recognized major grease manufacturers. Un-
fortunately, none of these greases have been approved.
It is not recommended to mix synthetic greases with
mineral oil based grease, which is the type of grease Leak Testing
that is inside the motor bearings as shipped from the The unit should be leak tested monthly. Any leaks
York factory. found must be repaired immediately.
Procedure – Evaporator And Condenser
Re-lubrication should be done with the motor shut The major portion of maintenance on the condenser
down with NO rotor rotation. This helps to assure and evaporator will deal with the maintaining the wa-
grease is placed in between the balls of the bearing. If ter side of the condenser and evaporator in a clean
the rotor is spinning certain bearing housing designs condition.
can force the grease to escape around the clearance
holes where the rotor shaft passes through the bearing The use of untreated water in cooling towers, closed
housing cap. This type of design will cause grease to water systems, etc. frequently results in one or more of
collect inside the motor. Other bearing designs may the following:
not allow any of the grease to penetrate to the bearing
housing if the rotor is spinning. 1. Scale Formation.
2. Corrosion or Rusting.
Absolutely NEVER pump grease until you see old
grease exiting at the relief port. Only pump the re- 3. Slime and Algae Formation.
quired number of strokes as determined above.
It is therefore to the benefit of the user to provide for
After the proper amount of grease has been added, proper water treatment to provide for a longer and
open the bearing relief port plug typically loated be- more economical life of the equipment. The following
low the bearing, and run the motor for 30-45 minutes recommendation should be followed in determining
before re-installing the plug. It is not necessary to see the condition of the water side of the condenser and
old grease coming out from the relief port. evaporator tubes.

Operating Temperature – 1. The condenser tubes should be cleaned annually


or earlier if conditions warrant. If the temperature
Normal operating temperature for grease lubricated difference between the water off the condenser
bearings on York chillers is 40-65 degrees centigrade, and the condenser liquid temperature is more
or 100-150 degrees Fahrenheit. It is normal to see the than 5°-6°F (3°-4°C) greater than the difference
temperature run higher immediately after re-lubrica- recorded on a new unit, it is a good indication that
tion, and then come down as much as 20 degrees C the condenser tubes require cleaning. Refer to
after a few hours of operation. Bearing RTDs should SECTION 6 - MAINTENANCE of this manual for
be set to shutdown the motor at 90 degrees C (194F). condenser tube cleaning instructions.
A warning programmed at 65C can be an indication
that something is not right and operation should be
checked.

34 JOHNSON CONTROLS
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015

2. The evaporator tubes under normal circumstances Oil Return System


will not require cleaning. If the temperature dif-
1. Change the dehydrator in the oil return system
ference between the refrigerant and the chilled
semi-annually or earlier if the oil return system
water increases slowly over the operating season,
fails to operate.
it is an indication that the evaporator tubes may be
fouling or that there may be a water bypass in the 2. When the dehydrator is changed, the nozzle of the
waterbox requiring gasket replacement or refrig- eductor should be checked for any foreign par-
erant may have leaked from the chiller. ticles that may be obstructing the jet.
3. Heat recovery condenser tubes should be evalu- Electrical Controls
ated similiar to evaporator tubes when the heating
circuit is a treated, closed loop. Fouling could be 1. All electrical controls should be inspected for ob-
detected as ability to meet heat load requirements vious malfunctions.
decreases. 2. It is important that the factory settings of controls
(operation and safety) not be changed. If the set-
tings are changed without Johnson Controls ap-
proval, the warranty will be jeopardized.

JOHNSON CONTROLS 35
36
MAINTENANCE REQUIREMENTS FOR YORK YK CHILLERS

Procedure Daily Weekly Monthly Yearly Other

Record operating conditions (on applicable Log Form) X


Check oil levels X
Check refrigerant levels X
SECTION 7 - PREVENTIVE MAINTENANCE

Check oil return system operation X


Check operation of motor starter X
Check sump heater and thermostat operation X
Check three-phase voltage and current balance X
1
Verify proper operation/setting/calibration of safety controls X
Verify condenser and evaporator water flows X
Leak check and repair leaks as needed1 X
Check and tighten all electrical connections X
Megohm motor windings X
Replace oil filter and oil return filter/driers X
Clean or backflush heat exchanger (VSD, SSS Applications) X
Replace starter coolant (VSD, SSS Applications) X
Replace or clean starter air filters if applicable X2
Perform oil analysis on compressor lube oil1 X
Perform refrigeration analysis1 X
Perform vibration analysis X
Clean tubes X2
Perform Eddy current testing and inspect tubes 2-5 Years
Lubricate motor Refer to motor manufacturer’s recommendations

For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls Service Office. A record of all procedures being successfully car-
ried out (as well as operating logs) must be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.

1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment.
2
More frequent service may be required depending on local operating conditions.
160.54-MR1 (611)
Supersedes 160.54-MR1 (801)
Issue Date: June 20, 2011

JOHNSON CONTROLS
ISSUE DATE: 6/15/2015
FORM 160.76-O1
FORM 160.76-O1
SECTION 7 - PREVENTIVE MAINTENANCE
ISSUE DATE: 6/15/2015

The following factors can be used to convert from


English to the most common SI Metric values.

Table 3 - SI Metric Conversion

Measurement Multiply English Unit By Factor To Obtain Metric Unit

Capacity Tons Refrigerant Effect (ton) 3.516 Kilowatts (kW)

Power Horsepower 0.7457 Kilowatts (kW)

Flow Rate Gallons / Minute (gpm) 0.0631 Liters / Second (l/s)

Feet (ft) 304.8 Meters (m)


Length
Inches (in) 25.4 Millimeters (mm)

Weight Pounds (lbs) 0.4538 Kilograms (kg)

Velocity Feet / Second (fps) 0.3048 Meters / Second (m/s)

Feet of Water (ft) 2.989 Kilopascals (kPa)


Pressure Drop
Pounds / Square Inch (psi) 6.895 Kilopascals (kPa)

Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range

JOHNSON CONTROLS 37
P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2015 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.76-O1 (615)
Issue Date: June 15, 2015
New Release

S-ar putea să vă placă și