-------5kVA
------- 5kVA and 6kVA UPS introduction
Extended model
( no battery model )
UHA1R-0050L
UHA1R-0060L
With 4A inner charger
3
Brief introduction
ITA 5K/6K appearance: installation rack/tower
Input mode compatible with three
Display panel
phase/single phase
input frequency 45-55Hz(rated 50)
output 220/230VAC-50Hz
output PF 0.9(5kVA)/0.8(6kVA)
support 2+1
support 3+1
volume 435*85*640
efficiency >91%
LED panel
Content
Brief introduction
Features
Principle & use
Main structure & functions
Optional parts & installation
Operation & debugging
Maintenance & troubleshooting
Features
Bypass
DSP
Note: same power source for main circuit and bypass
circuit; 220/230/240Vac multiple grid voltages and 50/60Hz
frequency mode
Block diagram
utility mode
Bypass
Bypass
Bypass
LCD model:
Note:
、Plastic panel easy put out for change LCD model without open machine;
1、
、display panel rotate for rack/tower installation.
2、
ITA 5kVA UPS –rear panel
Parallel port (With protective cover) DIP switch (With protective cover) Input MCB Battery port
USB port Ventilation hole 10A charger Intelligent card slot I/O terminal block
control port (With protective cover) (With protective cover)
Layout--module
Layout
BUS Output EMI Input EMI
Display
Toggle
Switch
Charger
Main
Power
Parallel
U16--07C1 appearance
U16
Intellislot
P aralleled address +
PE
UPS
Control port
Battery module
Plastic panel
Note::
)Standard battery model has two interface
1)
on rear part,,easy for battery parallel;
)ITA 5/6kVA standard model configured
2)
with one group U16-07C1;
)Battery cables is UPS accessories, right
3)
picture is standard battery cables.
UPS OPTIONS——
OPTIONS——1+1
1+1 POD for 1*1
Plastic panel
UPS2 input MCB UPS2 output MCB
Spec::
Power distribution function for
POD I/O terminal bolck single phase 1+1 parallel mode, ,
16A output socket (2 pcs) UPS1 I/O port (with protective cover)
provide tow C19 sockets, two 10A
external charge module terminal,
eight C13 sockets
Size: W××H××D((mm) )
10A output socket (2 rows) UPS2 I/O port External 10A charger port
×85×
430× ×625
UPS OPTIONS——
OPTIONS——3+1
3+1 POD for 1*1
Maintenance bypass MCB UPS2 input MCB UPS2 output MCB
(with protective cover) UPS1 input MCB UPS1 output MCB
Plastic panel
10A output socket 16A output socket A POD I/O terminal block (with protective cover)
(4 rows) (3 pcs)
UPS OPTIONS——
OPTIONS——3+1
3+1 POD for 3*1
Maintenance bypass MCB UPS1 input MCB UPS2 output MCB
(with protective cover) UPS2 input MCB UPS1 output MCB
Plastic panel
UPS3 input MCB UPS4 input MCB UPS3 output MCB UPS4 output MCB
Spec::
Power distribution function for
three phase 3+1 parallel mode,,
provide three C19 sockets, four
10A external charge module
terminal, sixteen C13 sockets
×H×
Size: W× ×D( (mm) )
430××170× ×625
10A output socket (4 rows) A POD I/O terminal block (with protective cover)
16A output socket (3 pcs)
UPS optional —Output POD for UPS
Output 220Vac 10A socket Output 220Vac 16A socket Input MCB Input port
ITA 10k UPS output power distribution unit ,include 6 unit C19 socket
,2 group connectors, all have circuit breakers.
UPS optional
optional——
——UPS
UPS guide rail/rack
UPS UPS
Battery
module
Support
Support base
base
UPS system installation—
installation—Rack
Installation hole 1
UPS
Screw
Installation
(6 pcs)
hole 2
Bracket
Bracket (2 pcs) amplified
UPS
Rack
UPS
Screw
Battery
(4 pcs) module
1-input 1-output
1 + 1 parallel POD
UPS
UPS1
Battery module
UPS
Battery module
UPS2
UPS system installation
installation——
——3+1
3+1 parallel
1-input 1-output
3 + 1 parallel POD
Battery module
UPS
UPS2
Battery module
UPS
Battery module
UPS3
UPS
Battery module
UPS4
Content
Brief introduction
Features
Principle & use
Main structure & functions
Optional parts & installation
Operation & debugging
Maintenance & troubleshooting
Operation ——input
——input power distribution
Three input
N U V W single output 47
UPS system installation
installation—
—parallel power
distribution
UPS system installation
installation—
—parallel power
distribution
Intellislot
P aralleled address +
PE
Intellislot
P aralleled address +
PE
Control port
Intellislot
P aralleled address +
Control port
Intellislot
P aralleled address +
UPS4
unique.
Control port
Operation——
Operation——parallel
parallel setup
2. The default setting of all the DIP switch is OFF. The DIP
switch position should be set for the parallel system according
to the descriptions listed in this Table.
DIP3 DIP2 DIP1 DIP3 DIP2 DIP1 DIP3 DIP2 DIP1 DIP3 DIP2 DIP1
DIP switch
position
ON ON ON ON
Operation——
Operation——panel
panel
8: BATTERY indicator
7: MAINS indicator 9: INVERTER indicator
3
2 Indicate Load
1 5 quantity on
utility mode
4
Indicate
capacity on
ON/SILENCE key OFF key
battery mode
fault:Fault LED
Short fault: Charger failure : Fault REPO fault : Fault LED fan/over-temperature fault
fan/over-
light, num 5 LED flashes light, num 4LED flashes light, no LED flashes :Fault light, num 3 flashes
Parallel current sharing Rectifier failure (bus high Battery fault (no battery, Battery fault (high voltage)
failure: num 2 LED flashes fault) : num 1 LED flashes reverse connection):
connection): : battery indicator flash
battery indicator flash
NOTE:
NOTE :other fault indicator please see user manual chapter 4 description
Debug—
Debug—UPS start on normal mode
1)Close utility and
bypass breaker, fan run 4)when shift to utility ,
the first, all LED flash for the utility LED flash,
three times 15s after, the inverter is
on and the inverter LED
indicator light
Press
on/silence
button for 1s
NOTE1:
NOTE1 : Check that the input cables and output cables are connected properly
and reliably, and the input cable connections are not reverse
Debug—
Debug—UPS start on utility mode
1)Close utility and bypass 4) when shift to utility ,
break, fan run the first, all the utility LED flash, 15s
LED flash for three times after , the inverter is on
and the inverter LED
indicator light
press on/silence
button for 1s to
clear fault alarm
NOTE:
NOTE :In case of BYPASS supply, UPS can not run with utility or battery!
Debug—
Debug—UPS start on battery mode
1)Close utility and bypass break,
4)after 30s the
then press on/silence button for 1
inverter is on, the
s, fan run the first, all LED flash for
inverter carry load,
three times
load indicator show
the load quantity
3)press on/silence
2)UPS report utility
button for 1s,
1s, the UPS
failure, utility LED
start on battery mode,
flash, battery LED
battery LED indicator
light
light
press
on/silence
button for 1s
NOTE3:
NOTE3 :Run on battery mode, Utility abnormal(
abnormal(A phase abnormal)
abnormal), if battery off (except battery EOD),
EOD),
then the UPS will not shift to Bypass
Debug—
Debug—UPS shutdown on utility mode
1) UPS run in Utility
mode: utility 4)the aux power still
inverter and load on, fan still run, open
LED light bypass and utility
break, All LED off, the
2) press off button UPS power off.
for 1s, the inverter
shutdown, the 3) press off button
inverter shutdown, for 10s, the bypass
UPS shift to bypass, shutdown, the utility
mode, bypass & load LED flash, UPS work
LED light on standby mode
Press
over 1seconds
NOTE:
NOTE :Bypass is not the same source with utility A phase,
phase,when bypass is abnormal or no bypass input
,UPS will shutdown directly
Debug—
Debug—UPS shutdown on battery mode
1)UPS run in battery 3)the UPS aux-
aux-power still on,
mode: battery inverter then press off button for
and load LED light 10s, the battery LED flash, 15s
after fan stop, battery mode
shutdown
Press
over 1seconds
Content
Brief introduction
Features
Principle & use
Main structure & functions
Optional parts & installation
Operation & debugging
Maintenance & troubleshooting
Production maintenance
ITA 5 kVA UPS maintenance mode is
module replace, Just replace the whole UPS
when it’s broken.
Troubleshooting table
No. Fault Possible cause Action to take
Input power not connected to the
The mains MCB is closed; however the display Check that the UPS input cables are connected properly
UPS
1 panel does not display, and the UPS does not
Use a voltmeter to confirm that the UPS input voltage is within
conduct self-test Input voltage extra low
specifications
The mains is normal; however the MAINS UPS mains MCB open Close the UPS mains MCB
2
indicator is off, and the UPS is in Battery mode Input cables improperly connected Connect the UPS input cables properly
No UPS alarm is generated; however the UPS
3 Output cables improperly connected Make sure the output cables are properly connected
has no output voltage
Press and hold the ON/SILENCE key for more than one second
After the ON/SILENCE key is pressed, the UPS Time of holding the key too short
4 till the buzzer beeps
does not start up
Overload Remove all loads and restart the UPS
Mains voltage or frequency beyond If the UPS is operating in Battery mode, note the battery back-up
5 The MAINS indicator blinks
the UPS input range time
The buzzer beeps every 0.5 second, and the
6 Overload Remove some non-priority loads
LED displays OVERLOAD
External battery switch open Close the external battery switch
External battery cables improperly
Check that the external battery cables are properly connected
connected
The FAULT indicator is on, and the LED displays
7 Check that the external battery cables are not reversely
BATTERY FAIL External battery reversely connected
connected
Contact the local service center of Emerson to replace the
Battery damaged
battery
The FAULT indicator in on, and the LED displays Contact the local service center of Emerson to replace or repair
8 Charger failed
CHARGER FAIL the charger
When the mains is normal, charge the battery for more than
Battery not fully charged
Battery discharge time is shorter than the eight hours, and then test the battery discharge time
9
standard time obviously Contact the local service center of Emerson to replace the
Battery capacity depleted
battery
Troubleshooting table
No. Fault Possible cause Action to take
1. Check that airflow blows out from the ventilation holes on the
rear panel.
2. Check that the clearances on both sides and at the back of the
The buzzer beeps, the FAULT indicator is on,
10 UPS internal overtemperature UPS are greater than .
and the LED displays TEMP OVER
3. Check that the ventilation holes on the front panel, side
panels, base plate and rear panel of the UPS are unobstructed.
4. Wait for ten minutes and restart the UPS
The buzzer beeps for a long time, the FAULT
11 indicator is on, and the LED displays OUTPUT UPS output short circuit Remove the load short circuit fault and restart the UPS
SHORT
The buzzer beeps for a long time, the FAULT
indicator is on, and the LED displays RECTIFIER The UPS needs repair. Seek technical assistance from the local
12 UPS internal fault
FAIL, INVERTER FAIL, AUX SUPPLY FAIL, or service center of Emerson
OUTPUT FAIL
Turn off the UPS and cut off the power input immediately. Seek
13 Abnormal noise or smell in UPS UPS internal fault
technical assistance from the local service center of Emerson
Battery capacity low, UPS turn-off 1. Save the load data immediately and turn off the priority load to
The UPS is about to turn off due to battery
14 imminent, and load power lost avoid losing or damaging data.
capacity shortage
imminent 2. Connect the UPS input terminal to standby AC power
The FAULT indicator is on and the buzzer beeps 1. Open the UPS mains switch.
15 Parallel address incorrect
for a long time 2. Reset the parallel address
Remove some loads and restart the UPS in approximately five
The FAULT indicator is on, the buzzer beeps for Overload
minutes
16 a long time, and the LED displays RECTIFIER
Turn off the UPS, cut off the input power and contact the local
FAIL, ABNOR BUS VOLT UPS internal fault
service center of Emerson
Fault and Maintenance-
Maintenance-1
Fault:The mains switch is closed, but the UPS provides no display
on the operation and display panel, and the UPS does not conduct self-
test
Possible cause :
1、Main supply not connected to the UPS ;
2、Input voltage too low ;
Fault and Maintenance-
Maintenance-2
Fault:Mains supply is normal, but the UTILTITY indicator is off, and the
UPS is in Battery mode
Possible cause :
1、UPS mains switch open
2、Input cables improperly connected
Fault and Maintenance-
Maintenance-3
Fault:No UPS alarm, but no UPS output voltage
LED panel display:
Possible cause :
Output cables improperly connected
Fault and Maintenance-
Maintenance-4
Fault:After pressing the ON/SILENCE key, the UPS does not start
LED panel display:
Possible cause :
1、The key holding time is too short ;
2、Overload
Fault and Maintenance-
Maintenance-5
Fault:The UTILITY indicator flashes
LED panel display:
Possible cause :
Mains voltage output or frequency side specifications
Fault and Maintenance-
Maintenance-6
Fault:The buzzer beeps every 0.5 second, and the LCD displays
OVERLOAD
Possible cause :
Overload
Fault and Maintenance-
Maintenance-7
Fault:The FAULT indicator illuminates, the LCD displays BATTERY
FAL, and the BATTERY indicator flashes
LED panel display:
Possible cause :
1、External battery breaker open;
2、External battery cables improperly connected;
3、External battery polarity reversed;
4、Battery damaged;
Fault and Maintenance-
Maintenance-8
Fault:The UPS has reduced battery time
LED panel display:
Possible cause :
1、Battery not fully charged;
2、Battery not able to hold a full charge due to age
Fault and Maintenance-
Maintenance-9
Fault:The buzzer beeps, the FAULT indicator illuminates,
and the LCD displays TEMP OVER
Possible cause :
Internal over-temperature/fan fault