The Vector Surge Relay


The vector surge relay is used to decouple synchronous generators from the grid utility in case of grid Search
failure.
L1 L2 L3 L4
Synchronous generators are generally operated in parallel with the grid utility. This ensures greater Mechtechnik

reliability and enables the generator to export power to the grid. In this condition, there is a chance, of
a momentary interruption of the grid supply which may result for a few milliseconds. Such temporary
interruptions can be caused to mal-operation of the circuit breakers on the grid transformer side.

For a synchronous generator, running in parallel with the grid utility, such a temporary interruption and
restoration of the supply can be dangerous. As the restoration of the supply can be asynchronous i.e.
the generator and the grid are now not in a synchronised condition. The can lead to the consequences
of wrong synchronization such as damage to the generator or the prime mover.

The vector surge relay prevents this condition by decoupling the generator from the grid as soon as
the grid supply fails. This is an extremely fast acting relay with an operating time of less than 300ms
from relay operation to breaker opening.

Principle:

The vector surge relay functions by monitoring the rate of change of


the rotor displacement angle of the generator. During parallel
operation there is an angular difference between the terminal phase
voltage (Up) and the internal synchronous voltage of the generator
(Ui). This is due to the fact that the generator rotor is magnetically
coupled to the generator stator and is forced to rotate at the grid
frequency. The angle between the vector of the mains voltage Up
and synchronous electro-motive force is known as the rotor
displacement angle.

This angle is constantly varying and is dependent on the torque


produced by the generator rotor. In the case of the grid failure, there
is sudden change in the rotor displacement angle.

This causes a surge in the generator voltage shown in the figure.


The relay works by monitoring the time taken between the zero-crossings in the waveform. Under
normal operation, the time interval between two consecutive zero-crossings is almost constant. During
the grid failure, the vector surge which occurs causes a delay in the zero-crossing. This delay is
detected by a highly sensitive timer inside the relay and the relay operates.

The relays are usually set to operate for a change in the rotor displacement angle of 0 to 20 degrees