Thickness Design of Column Base Plate Connections Structv lle Eng neer ng
4,470 l kes

(EC3)
L ke Page

by Ubani Obinna Ranks on October 05, 2017 in Eurocode 3, Steel Structures


Be the f rst of your fr ends to l ke th s

GOOGLE+ BADGE

Ubani Obinna Ranks


Ubani Obinna Ranks

Follow

184 followers

ABOUT ME

Ubani Obinna Ranks


Problem Statement
Follow 184
It is required to specify the appropriate thickness of a base plate to support a UC 203 x 203 x 60 subjected to the following
Purpose driven personality
loads. The connection is assumed to be pinned with four bolts outside the column profile.
Bachelors Degree (B.Eng) i
The supporting concrete is to have a grade fck = 25 N/mm2 Engineering from Nnamdi Azikiwe Univers
Passionate about civil engineering profes
experienced in structural analysis and des
View my complete profile

http://www.structv lle.com/2017/10/th ckness-des gn-of-column-base-plate.html?m=1 1/4


19.03.2018 Th ckness Des gn of Column Base Plate Connect ons (EC3) - Structv lle...

Characteristic force from permanent action Gk = 620 kN

Characteristic force from leading variable action  Qk = 132 kN

Partial Factor for loads (BS EN 1990 NA 2.2.3.2 Table NA.A1.2(B))


Permanent action γG = 1.35 (unfavourable)

Variable action γG = 1.5


FOLLOW BY EMAIL
Reduction factor ξ = 0.925

Enter your email address to subscribe to this blog


At ultimate limit state; notifications of new posts by email.

NEd = 1.35Gk + 1.5Qk Email address...

NEd = 1.35(620) + 1.5(132) = 1035 kN


SUBMIT

Column Dimensions and Properties


Depth (d) = 209.6mm POPULAR POSTS
Width (b) = 205.8mm
Analysis and Design of Cur
Thickness of web (tw) = 9.4mm
Circular Beams in a Reserv
Thickness of ange = (tf) = 14.2mm

Root radius (r) = 10.2mm


Preparation of Bar Bending
Perimeter of section = 1206.4mm For Floor Slabs
Area of section = 76.4 cm2

PRACTICAL ANALYSIS AN
Partial factor for resistance OF STEEL ROOF TRUSSES
γm0 = 1.0 EUROCODE 3: A SAMPLE

γm1 = 1.25
What is wrong with this se
structural detailing?
Base Plate Details

Strength of concrete = 25 N/mm2 Analysis of Trusses Using D


Foundation bearing strength fcd = αccfck/γc Stiffness Method: A Solved

Take αcc = 0.85 (for axial compression)

γc = 1.5 Thickness Design of Colum


Plate Connections (EC3)

Therefore;

fcd = (0.85 × 25)/1.5 = 14.167 N/mm2 How to Prepare the Gener


Arrangement (GA) of a Bui

Area of base plate required Ac0 = NEd / fcd = (1035 × 1000)/14.167 = 73057.104 mm2
How to Design Roof Purlin
Example
Effective Area = 4c2 + (Section Perimeter × c) + Section Area

RECENT POPULAR COM

http://www.structv lle.com/2017/10/th ckness-des gn-of-column-base-plate.html?m=1 2/4


19.03.2018 Th ckness Des gn of Column Base Plate Connect ons (EC3) - Structv lle...
Where c is the cantilever outstand of the effective area. This is shown below; Thickness Design of Colum
Using Prokon Software
 Ubani Obinna Ranks  Mar

Analysis of Industrial Gable


 Ubani Obinna Ranks  Mar

Design of Piles in Sand: Cas


Lekki Pennisula, Lagos Nige
 Ubani Obinna Ranks  Mar

  Linear Interpolation for Stru


Engineers (Gregory-Newto
Difference Formular)
 Ubani Obinna Ranks  Feb

Sinking of Supports of Prop


Cantilever Beams
 Ubani Obinna Ranks  Feb

FOLLOW US

 Facebook
73057.104  = 4c2 + 1206.4c + 7640
On solving;
 Twitter
c = 46.924 mm

 Google+
Check;
(h - 2tf)/2 = (209.6 - 2 × 14.2) / 2 = 90.6mm Follow up on Linkedin

Since 90.6mm > 46.924 mm, there is no overlap between the anges.
 Follow us on Instagram

Thickness of base plate (tp)

tp = c[3fcd / (fyγm0)]0.5 FACEBOOK

tp = 46.924 × [(3 × 14.167) / (275 × 1.0)]0.5 = 18.447 mm


Structv lle Eng neer ng
4,470 l kes
Therefore provide a base plate of thickness tp = 20 mm in S275 material (since tp is less than 40mm).

Connection of base plate to column L ke Page

It is assumed that the axial force is transferred by direct bearing, which is achieved by normal fabrication processes. Only
Be the f rst of your fr ends to l ke th s
nominal welds are required to connect the base plate to the column, though in practice full profile 6mm fillet welds are
often used.

Thank you visiting Structville today!!!


BLOG ARCHIVE
Our facebook page is at www.facebook.com/structville

October (6)
Share This:  Facebook  Twitter  Google+  Pinterest  Linkedin

TAGS
RECOMMENDED ARTICLES
BEAMS (22) BRIDGES (5)

Thickness Design of Column Base Plate Using Prokon Software CABLE STRUCTURES (1) COLUMN (9)
Last year, I made a submission here on how to carry out the thickness design of column base plates.See post
CONSTRUCTION (12) DYNAMIC ANALYSIS
below;Thickness Design of Column Base Plat...

ENGINEERING MATHEMATICS (1) EUROCO


Analysis of Industrial Gable Frames
1.0 IntroductionIndustrialization is one of the major keys to development and sustainable economy. Industrial EUROCODE 3 (8) EUROCODE 7 (1)
structures are usually very easy to iden...
FORCE METHOD (9) FOUNDATIONS (5)

Analysis of Elevated Steel Tank Using Staad Pro


FRAMES (17) GEOTECHNICAL ENGINEERIN
Overhead steel tank is one of the most adopted water storage system due to lots of reasons. The speed and
ease of construction, exibility in support... GUIDES (7) INFORMATIVE POSTS (9)

Design Example of Steel Beams According to Eurocode 3 PLASTIC ANALYSIS (1) PROGRAMMING

IntroductionThis post deals with the design of simply supported I-beam section subjected to permanent and PROMOTIONS (4) QUANTITY ESTIMATION
variable loads according to Eurocode 3. The ...

http://www.structv lle.com/2017/10/th ckness-des gn-of-column-base-plate.html?m=1 3/4


19.03.2018 Th ckness Des gn of Column Base Plate Connect ons (EC3) - Structv lle...

REINFORCED CONCRETE DESIGN (28)

 NEWER ARTICLE OLDER ARTICLE  STAAD PRO (5)


Analysis Of Sub-Frames Using Stiffness Method: A Solved How To Design Roof Purlins: A Solved Example
STATICALLY DETERMINATE STRUCTURES (10)
Example
STATICALLY INDETERMINATE STRUCTURES (1

NO COMMENTS:  STEEL STRUCTURES (12)

STRUCTURAL ANALYSIS (46) TRUSSES (

Enter your comment...

Comment as: Unknown (Goo S gn out

Publ sh Prev ew Not fy me

İsa: “Sana rahat ver r m” - Bu rahatılığı nasıl alırsın?


Çok k ş yorgun olarak yaşıyor, yardım arıyor. İsa yardımcı olab l r. kampusweb.com

PAGES ABOUT ME CONTACT FORM

Name
Home Ubani Obinna Ranks
Follow 184
Our Products and Services Email *
Purpose driven personality with a
About Us
Bachelors Degree (B.Eng) in Civil
Engineering from Nnamdi Azikiwe University, Awka. Message *
Disclaimer
Passionate about civil engineering profession, and
Our Policies experienced in structural analysis and design.
View my complete profile

Send

Copyright © 2018 Structville...      

http://www.structv lle.com/2017/10/th ckness-des gn-of-column-base-plate.html?m=1 4/4

S-ar putea să vă placă și