Documente Academic
Documente Profesional
Documente Cultură
Analysis of Result
Fall of Potential 8.545Ω 6.242Ω 17.46Ω
E.B Curd’ts 8.780Ω 6.470Ω 17.40Ω
Slope Method 8.690Ω 6.400Ω -
Remote electrode (C2) at 30 mtrs from earth pit (C1P1).
Earth Pits are conventional type back filled 2Ft all around the electrodes.
Earth Pit No1: Located at A & B colony 50mm dia 3mtrs Long GI Pipe.
Earth Pit No2: Located in 33KV Substation 100mm dia 3mts Long GI Pipe.
Earth Pit No3: Near DG Set New 60mm dia 2mtrs Long GI pipe.
2. As per the measurement method, the potential spike is put closer than
the current spike from the earth pit. What will happen if we change the
position of the spikes?
3. Can we pour water on the spikes before we check the earth resistance
value?
A good digital earth tester (Reputed make) shall have an indicator for high
current loop resistance or high contact resistance at potential probs. A few
spoonful of water may be poured around the probe, which has been hammered
into ground, to get good conductive connection between probe and soil around
it.
4. Is it necessary to isolate the earth pit from the electrical circuit before
measuring the earth resistance value? If Yes then why and if NO then why?
Not necessary. The modern earth testers of reputed make are meant to measure
this live. Taking shut down of a station is not that easy. It requires lot of
procedure and is expensive.
5. How to check the earth resistance value in rocky soil or where earth pit is
installed in sandy soil or where there is no place to put the spikes (area
surrounding the earth pit are made of concrete / flooring is done)?
6. If multiple earth pits are done then what is the best practice to connect
with the electrical circuit? Whether all earth pits should be connected to each
other then final connection is made with electrical circuit or all the earth pits have
to be connected individually with the electrical circuit?
In multiple earth pits, all pits shall be connected to each other and then final
connection is made with electric circuit. The inter-connecting flat shall be laid at
least 500mm below the ground level and brought above the ground level and
connected to earth electrode.
7. What is the minimum accepted earth resistance value for different
applications? Are these resistance values mentioned in any standard?
The earth resistance shall be as low as possible and shall not exceed the
following limits
8. How to check the soil resistivity? Minimum how may readings should be
taken and at what points for a correct measurement of soil resistivity value ?
The mean value is calculated. In case the values lies within +/- 30% of mean
value (70% to 130%) the soil is considered to be uniform (Homogenous soil).
• CASE STUDY:
SL.NO a R ρ
Meters Ω Ohm-Meters
1 2 4.33 54.412
3 4 2.35 59.062
4 5 1.986 62.392
5 6 1.652 62.279
6 7 1.462 64.301
ρ Average 59.579
Make Model
This is not true in case of reputed make digital earth testers. This may be true
when compared with analog to digital earth testers of reputed make.
13. How does earth electrode geometry affects the earthing system?
The total surface area coming in contact with earth is the criteria.
14. How to calculate the number of earth electrodes required for any
particular application?
To carry 6 kilo amperes No.of plates required = 6000 / 570.8 = 10.5 = 11 nos.
15. How to calculate the resultant earth resistance value of the earth
electrodes if more than one pits are required to be installed?
No.of Rods F
2 1.16
3 1.29
4 1.36
8 1.68
12 1.80
16 1.92
20 2.00
24 2.16
Minimum number is two for above equipment body earthing. In case their panels
are in the same line totally only two numbers are required, one on either side and
an earth bus can run connecting two electrodes and the body of each panel can
be connected to this earth bus.
For transformer and generator neutral the number of electrode required depends
on the a) resistivity of the soil; b) the duration of fault in seconds; and c) fault
level in kiloamperes. The calculation is as described in question 14 above.
17. What are the reasons for getting high voltage between neutral and
earth points? How to correct / attend to this problem?
Remedies:
18. It is observed that even after having good earthing system in place in
any factory, when a lightning strokes occurs even some distance away / lightning
falls somewhere near the factory premises,that damages the electronic circuit &
communication system of the factory. What may be the reason for the same and
how to address this problem?
20. How to calculate the effective soil resistivity value when 50 Kg BFC
(Resistivity < 2 Ohm Meter and PH – 6.4 to 7.8) is added in to it?
Earth enhancing material reduces the soil resistivity (Thus the ground resistance)
by 10 to 90 %. Earth enhancing material is very useful in high soil resistivity area
(Rocky Area). Where the soil resistivity is more than 300 ohm – m.
For example. In this place if a pipe of 80 mm dia 3 mtrs long is installed the
ground resistance will be
Rg = 79.746
By using above earth enhancing material ρ will be 10% of 300 i.e. 30 ohm – m
and Rg = 10% of 79.746 i.e. about 8 ohms.
22. What is Faraday Cage Earthing and how and where it is done?
Faraday Cage is totally a shielded room the walls are covered with GI Chicken
mesh and this mesh is grounded. The measurements carried out in this room is
free from unwanted signals. In this cage no external signals will intervene.
24. The calculation to work out the number of earth pits required for any
application for above type of earthing?
ESD can severely impact the performance and reliability of electronic equipment.
A site can experience failures from ESD and not immediately be aware of the
problem since voltage levels that can cause component failure are below the
perception threshold of the individual. Meters are available to measure the level
of static charge on personnel and equipment. Recommended practice is to
measure static charge on personnel, furniture and other such items located in the
vicinity where the sensitive equipment is being operated. If equipment failures
are caused by ESD, recommended corrective measures include the following:
The minimum value of relative humidity (R.H) that is required for effective
control of static electricity is difficult to determinate and will vary with the
process and the surrounding conditions. However, it is believed that where
the R.H. is maintained in the range of 60 to 70% at ordinary indoor
temperatures static accumulations are not likely to reach dangerous
proportions.
ESD earthing is nothing but normal earthing and the down conductor (earth bus)
is run in the lab and each equipment body is connected to this as mentioned in b)
above.
26. How to revive an old earth pit / pits whose resistance value is more
than the permissible limits?
Where the earth pit is provided and its earth resistance is 50% more than the
commissioning value, the pit is to be treated after re-filling salt and charcoal, as
specified, and if required, damaged and corroded electrodes may be replaced /
rectified. Special care is to be taken to physically examine and test the neutral
earthing pit / electrode of power transformers.
After 10 years of installation, the treated earth pits with vertical rod electrodes are
to be inspected by digging on sample basis. The damaged / broken electrodes
need to replaced.