www.hilti.com Profis Anchor 2.7.

1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HST M8
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 47 mm, hnom = 55 mm
Material:
Evaluation Service Report: ETA 98/0001
Issued I Valid: 11/6/2015 | 11/6/2020
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 400 mm x 150 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: I profile; (L x W x T x FT) = 178 mm x 102 mm x 8 mm x 19 mm
Base material: cracked concrete, C25/30, fc = 25.00 N/mm2; h = 250 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

2 Load case/Resulting anchor forces


Load case: Design loads y

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.487 2.270 2.270 0.000
2 0.487 2.270 2.270 0.000 1 3 5
3 0.331 2.270 2.270 0.000 x
Tension Compression
4 0.331 2.270 2.270 0.000
2 4 6
5 0.175 2.270 2.270 0.000
6 0.175 2.270 2.270 0.000
max. concrete compressive strain: 0.02 [‰]
max. concrete compressive stress: 2
0.63 [N/mm ]
resulting tension force in (x/y)=(77/0): 1.988 [kN]
resulting compression force in (x/y)=(192/0): 1.179 [kN]

3 Tension load SOFA (fib (07/2011), section 10.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 0.487 12.667 4 OK
Pullout Strength* 0.487 3.043 17 OK
Concrete Breakout Strength** 1.988 14.309 14 OK
Splitting failure** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
19.000 1.500 12.667 0.487

3.2 Pullout Strength


NRk,p [kN] yc gM,p NRd,p [kN] NSd [kN]
5.000 1.095 1.800 3.043 0.487

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm]
48731 19881 2.451 71 141
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
13 0.849 0 1.000 0.998 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.700 12.405 1.800 14.309 1.988

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

4 Shear load SOFA (fib (07/2011), section 10.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 2.270 11.200 21 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 13.620 40.456 34 OK
Concrete edge failure in direction y+** 6.810 7.900 87 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
14.000 1.250 11.200 2.270

4.2 Pryout Strength


Ac,N [mm2] A0c,N [mm2] y A,N ccr,N [mm] scr,N [mm] k4
48731 19881 2.451 71 141 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 0.998 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
12.405 1.500 40.456 13.620

4.3 Concrete edge failure in direction y+


lf [mm] dnom [mm] kV a b
47 8.0 1.700 0.053 0.054
c1 [mm] c'1 [mm] Ac,V [mm2] A0c,V [mm2] y A,V
10130 167 60000 125000 0.480
y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V
0.784 1.000 2.500 0 1.000 1.000 2.500
V0Rk,c [kN] n1 gM,c VRd,c [kN] VSd [kN]
25.191 2 1.500 7.900 6.810
Note: Resistance limit acc. to fib (07/2011) Eq. (10.2-6) is governing

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.038 0.203 2.000 5 OK
concrete 0.160 0.862 1.500 87 OK
baN + baV <= 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 0.361 [kN] dN = 0.235 [mm]
VSk = 1.681 [kN] dV = 0.525 [mm]
dNV = 0.575 [mm]
Long term loading:
NSk = 0.361 [kN] dN = 0.217 [mm]
VSk = 1.681 [kN] dV = 0.799 [mm]
dNV = 0.828 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

7 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HST M8
Profile: I profile; 178 x 102 x 8 x 19 mm Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 9 mm Hole diameter in the base material: 8 mm
Plate thickness (input): 10 mm Hole depth in the base material: 65 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Seismic/Filling set
• Properly sized drill bit • Torque wrench
• Hammer

y
-89

200 200

35

75
1 3 5

80

75
2 4 6
35

250 40 40 70

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 50 40 90 150 1080 10050 4 90 -40 130 110 1000 10130
2 50 -40 90 150 1000 10130 5 130 40 170 70 1080 10050
3 90 40 130 110 1080 10050 6 130 -40 170 70 1000 10130
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 11/29/2016
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan