Sunteți pe pagina 1din 8

30th International Conference on Lightning Protection - ICLP 2010

(Cagliari, Italy - September 13th -17th, 2010)

(PHOTOVOLTAIC SURGE PROTECTIVE DEVICE (SPD) AND GROUNDING


PHOTOVOLTAIC SYSTEM
Vincent Crevenat
ABB France, Bagneres de Bigorre, France
Vincent.crevenat@fr.abb.com

grounding system for photovoltaic application can be


ABSTRACT
either isolated or grounded (one of the polarity is
These last years Photovoltaic systems and all renewable connected to ground).
technologies are worldwide growing topics. Up to now d.c. insulated system was the principal system
Some countries have developed this technology since more used in this field, but since new technologies of
than 15 years but it is a real explosion phenomenon since photovoltaic cells have appeared on the market, the
only 2 years. This pushes all systems or devices
manufacturers to start developing solutions quickly.
grounding of one polarity is used. This impacts
Standardization organizations are also involved by this new converters technology, the human being protection
technical trend and start to develop specific standards for solutions and of course the SPD choice itself.
specific Photovoltaic solutions. But as always in such a case, In addition, the converter technology using or not an
market is asking technological solution faster than insulating transformer between the a.c and d.c is also a
standardization organization can write standards. This is of factor to consider in SPD selection.
course the case for Surge Protective Devices (SPD) intended The end of life behavior of the SPD can impact the
to be used on DC side of photovoltaic systems. choice of the SPD depending on converter technology
Concerning the SPD for photovoltaic application, two main and grounding system.
subjects can be highlighted for their selection:
In this paper, all possible configurations for SPD will be
• SPD’s technology to deal with specific d.c. electrical shown, the grounding solution will be detailed and the
characteristics for Photovoltaic. impact on SPD architecture will be explained linked with
• Architecture configuration of the SPD depending on its end of life behavior.
photovoltaic grounding system, converter technology
and SPD end of life behavior. 2 CONVERTER/INVERTER TECHNOLOGY
The first subject will not be treated in this paper. ABOUT A.C./D.C. SEPARATION
The aim of this paper is not to describe any standard for
SPDs, but is to describe one specific aspect (second bullet) Two main categories of converter concern our subject
linked to both MOV (Metal Oxide Varistor) based SPDs and can be divided as follow: Converters with
and photovoltaic installation on d.c. side. Only the grid transformer and converters without transformer
connected PV system are considered in this paper, but some (transformer-less)
points can be extrapolated to off-grid systems Efficiency of converters is one of the major
characteristics for the manufacturers and mainly the
1 INTRODUCTION users.
The efficiency of transformer-less is about 98% where it
Even if standards for photovoltaic SPD are not all is about 95% for converters with transformers. Of course,
published the standardization work on this field is one of the transformer-less converters are also less expensive.
the most in advance compared to other technologies such Using a transformer in the conversion process can be
as fault protection for instance. assumed as a loss of productivity and extra cost in some
situations. But today on the field, for technical and safety
Architecture of SPDs for any application is based on reasons, converter using transformers are used as often as
several constraints, but the grounding of the network is transformer-less converters. One of the major advantages
one major input. In PV application, two grounding family of having a galvanic separation is that in case of earth
systems can be identified (much less than for a.c. power fault on d.c. side, the fault is not conducted to the a.c.
system where the use of single and multi phase side.
transformers can significantly increase the number of As a reminder, it is good to know that in case of earth d.c;
grounding system). Firstly, for photovoltaic system, only fault, inverters have to disconnect a.c. grid from
polarity (+) and polarity (-) are existing. d.c. side conversion unit.

1304-1
In the following sub clauses, the reader will see the switches insure the withstand. Thus surge withstand can
principle diagrams and will find the possible impacts on be considered as weak (few hundreds of volts above the
SPD selection maximum working voltage of the used switches. ei:
1200V for 800V IGBT). It should be borne in mind that
generally semiconductor failure behavior is a pure short
2.1 Galvanic separation between a.c. and d.c.
circuit.
networks
An earth fault on d.c. side will automatically create the
In this architecture, the transformer can be low or high disconnection from a.c grid, but the time reaction can be
frequency. In that last case, there is a second stage for long and can create a current thought the PE wire able to
energy conversion. destroy switches if the fault occurs when the line is
connected to the faulty d.c. conductor (via the switch). In
(-) (L) addition and even if the switches are still in working
order, this can create a dangerous voltage for human
being on a.c. side because the time reaction of the
(+) (N) ~ inverter is not linked to human being ‘withstand’ as
RCDs can be for instance.
As a conclusion, this inverter technology requests real
technical investigations if using a SPD able to create a
(PE) short circuit between active cables and ground even if it
is temporary (Temporary means more than 0,1s: see IEC
60364-4-41 part 411.3.2.2.)
Figure 1
3 GROUNDING D.C. SYSTEMS
Concerning surge, the voltage withstand between a.c. and
d.c. is linked to the insulation characteristic of the As introduction, ungrounded system is a simpler
transformer and thus can be considered as good (ei: 4- technical solution concerning the human being protection
6kV or more depending on the transformer). and fire protection (against fire created by an earth fault).
One advantage of this solution is that in case of d.c. earth Bonding to ground one of the d.c. polarity (generally the
fault no current (a.c. or d.c.) can flows into the ground positive for technology and electro-corrosion purpose) is
and thus, the human being safety is not impacted. Of sometime needed for specific photovoltaic cells
course, in that case, the maintenance has to be done as technology. Because of human being safety, the
soon as possible, but this situation could be maintained grounding of one polarity is not always as evident as a
without problem for a long period. This case is direct connection to ground.
comparable to first fault for IT system in a.c. grid. And of course, grounding system methods for
Theoretically, the production of electricity could be Photovoltaic impacts the selection of the SPD
maintained, but because of inverters protection and safety configuration.
rule (precaution principle) this is stopped. 3.1 Ungrounded d.c. system
2.2 No galvanic separation between a.c. and d.c. This system can be compared to IT system in a.c.
networks network. This means that no active cable on d.c. side of
The functional insulation is reached through the the photovoltaic installation is connected to ground. The
semiconductor switches (ie:IGBT) constituting the H installation must adhere to safety Class II standards
bridge. (double insulation).

(-) (L) (-) (L)

~
(+) (N)
(+) (N) ~
(PE)

Figure 2
(PE)

About surge between a.c; and d.c. network only these


Figure 3

1304-2
usually realized in the inverter it self, and only one time.
About the mode of protection that have to be considered, But no rule is really addressing this subject.
it is clear that protections between the positive and
negative polarity themselves and between active cables (-) (L)
and ground have to be given.
Even if this ungrounded system is a good solution for
protection against direct contact and could be maintained
for a long time period if the inverter technology permits it (+) (N) ~
(see 2.1), earth fault must be avoided. Using an SPD
connected to ground can turn this isolated system to
grounded system in case of its fault and should not be
impacted by a real earth fault. Thus specific requirements (PE)
are requested to avoid this:
• The SPD must not create a connection between one
polarity and ground in case of fault. It must be Figure 4
disconnected or disconnect itself or alternatively
short circuit all active cables to not create dangerous Concerning surge and theoretically, only one SPD seems
voltage for too long time. to be needed between active cables. In practice, the
• The SPD must be designed to withstand the connection is realized inside the converter for functional
maximum voltage between its actives connections reasons and does not consider the surges aspect such as:
and the ground in case of earthing fault (This can be • the connection has to be as straight as possible
defined as a kind of TOV withstand mode for a.c. • as short as possible
SPDs). • must be able to carry surge or lightning current
These two requirements force to select specific • etc…
configuration depending also on voltage withstanding of In addition this connection is usually unique and not
each part of the SPD repeated all along the cable from the inverter to the PV
For instance, it is practically impossible to fulfill these generator witch leads (as mentioned previously) to have
two requirements with V configuration (see 5.2) using oscillation phenomenon or coupling aspect able to create
varistors, because they lead to pass tow different tests in dangerous surges if no additional SPDs are connected.
same electrical condition but with different pass criteria Another aspect to consider for SPD is that the short
where one is “withstand” and the other is “fail” (safe). circuit condition with the full current is not only to be
considered between (+) and (-), but it has also to be
3.2 Grounded d.c. system considered between the ungrounded polarity and the
All grounding methods suggested below are possible and ground itself.
can be selected depending on specific system design In some location, this type of direct connection is
requirements and national or regional codes. forbidden because the insulation of all active cables must
Note that PV system manufacturers prefer to perform all be checked (even the one connected to earth). One
grounding methods within the inverter whenever alternative solution proposed in that case is to use a
possible. Of course if the distance between the contactor to realize this connection in order to perform a
connection of the d.c. polarity and the ground is long, daily insulation test (see figure 5). This contactor is
surge protection choice has to take in account the risk of automatically open during a short period and when no
surge caused by oscillation phenomenon or coupling power is coming from PV cells (ie: during night period).
principle already described in published general lightning
and surge protection standard [1 to 2] . (-) (L)
Grounded d.c. systems require a galvanic separation such
as transformer-based inverter (also called grid-isolated
inverter. see 2.1). If not, each time an electronic switch is
“on”, the a.c. network is connected to earth and this (+) (N) ~
alternatively through phase(s) and Neutral. This situation
is not permitted.
3.2.1 Via a direct connection
(PE)
This is the easiest way to realize the d.c. grounding
system and it consists in using a solid conductive part
connecting the ground cable to one polarity. This is

1304-3
Figure 5 from the d.c.(+) terminal and ground.
For safety reasons and up to now, this third solution is
In that case the connection cannot be considered as a used by law in some countries.
connection from the surge or lightning current point of Concerning surge, and in addition, for the same reason
view. Thus, the SPD must propose the protection mode explained for direct grounding system, using this solution
between active cables (+&-) and the protection mode leads to consider the high risk that this fuse blows
between active cables themselves. because of surge (2A fuse blows under a 8/20 wave shape
current of less than 800 Amperes ). As the maintenance
3.2.2 Via a resistor on photovoltaic installation is not instantaneous due to
One solution to have one pulled polarity to ground is to the fact that they are generally in a wide field or top of
use a resistor between the d.c.(+) terminal and ground (or buildings for example, the grounding system turns to
(-)). ungrounded system and have the same requirements
In practice, depending on the power of the PV generator, concerning surge protection (protection mode of the
the resistor value is from few tenth of kilo Ohms to few SPD) than an ungrounded system (see§3.1).
hundreds of kilo Ohms 3.3 Conclusion on system grounding impact for
protection modes needs
(-) (L) As a conclusion, it is clear that in spite of the different
grounding system appearance, all protection modes are
always needed. Thus protection level is requested
(+) (N) ~ between these leads:
• (+) to (-)
• (+) to Ground
Resistor • (-) to Ground
(PE) This forbids the use of SPD providing only one
protection mode as I configuration SPDs (see 5.1) which
can be proposed to protect direct grounded d.c. system
Figure 6 for cost saving.
This solution has the advantage of not having the real 4 END OF LIFE BEHAVIOR OF SPD
short circuit condition between the ungrounded polarity
and the ground. General rule for all type of SPD is that when end of life
Of course concerning surges, the high value of the (EOL) is occurring, SPD must not create hazard. Usually,
resistor can be considered as an open circuit and thus typical a.c. SPDs are not allowed to finish in short circuit
must be protected by an SPD as it was an ungrounded or at least have to be protected by a backup fuse.
d.c. system Due to specifics condition of d.c voltage and in addition
to the specific random value of the current, when SPDs
reach their end of life, specific solutions are possible.
3.2.3 Via a fuse Today SPDs dedicated for PV application have officially
(from standard project [5]) 2 possible modes for their end
of life behavior: Short Circuit Mode and Open Circuit
(-) (L) Mode. In reality and from the author position, a third
behavior is possible which is a combination of these: A
sequence of a short circuit mode and an open circuit
(+) (N) ~ mode where the time of the short circuit state can be from
milliseconds to several minute or even hours. In this
document we will call this mode: 2 States Modes of
EOL behavior.

(PE) 4.1 Short Circuit Mode of EOL behavior (SCM)


From product test procedure [5], one of the short circuit
mode failure behavior pass criteria defined as follows:
Figure 7 The surface temperature rise at the hottest point shall not
exceed 120 K during the test. Steady state conditions are
considered to be reached if the change in temperature is less
Connect a small d.c. fuse (usually 2A) between this lead then 2 K within 10 min. The surface temperature rise shall not

1304-4
exceed 80 K over ambient temperature 5 min after the end of 4.3 2 States Mode of EOL mode of behavior
the test. (2SM)
This means that the short circuit mode is a real short
This EOL mode of behavior in not today addressed for
circuit intentionally created by the SPD when it reaches
testing in literature. This EOL mode can be created
its end of life and this state has to be stable for an
intentionally (eg: by a switch) or can be reached
unknown duration (Intent of the stability temperature
randomly by the fact of using only one MOV
check)
(considering it can turn to sudden short circuit). This can
We can point out few aspects of this EOL behavior.
occurs in case of unique MOV with its disconnector(s)
• In case of maintenance the SPD can be very hot (but between connections where the short circuit condition is
less than 120°K) and thus, the maintenance staff can created ((+) to (-) or (-) to ground for direct grounded
be injured when simply touching the SPD. system). Different short circuit conditions (depending on
• In case of pluggable SPDs, the maintenance staff can sun radiation) have to be withstood up to a certain energy
create an electrical d.c arc that can hurt him (eg: where a specific disconnector operates (and of course
removing pluggable cartridge). quenches the short circuit current). The difference
But the main aspect studied in this paper is that between intentional and random 2 states mode is that for
depending on grounding system (part 3), SPD the first (intentional short circuit) the energy to withstand
configuration (part 5) and converter technology (part 2), is well known and defined whereas for the second
dangerous situations can appear for human being and (random short circuit) it depends to the MOV component
converter. itself. Which is not mastered except if the component is
encapsulated in a fire proof envelope.
4.2 Open Circuit Mode of EOL mode of In case of a SPD 2 states mode branch directly
behavior(OCM) connecting active cables and ground, it can creates like
Open circuit mode of EOL is maybe the best solution not an earth fault for duration depending on the time when
to create problem in the installation such as dangerous the disconnection energy level is reached. This time can
voltage or inverter destruction coming from a connection be very long and thus the EOL state should be considered
of one active cable to ground. However this is also the as a possible permanent state (Definition of permanent
most difficult technical solution due to the specific nature can be : as soon as it can create danger. eg: Few minutes
of the photovoltaic generator. Indeed, to cut a d.c. current to several hours)
created by photovoltaic generator which can reach 1000V For this type of EOL behavior, it should be remembered
is not a easy task. For figuration, to quench a d.c. arc with to be recalled that the user can simply be injured because
a voltage of 1000V and a current of only 8 amperes the of maintenance activity during short circuit state (See
distance between 2 copper contacts must be higher than 4.1).
200 millimeters!
5 POSSIBLE ARCHITECTURE
From product test procedure [4]&[5], it is possible to
CONFIGURATION FOR SPDS
check if a fail state SPD is able to disconnect or to be
disconnected. Principle is based on the fact that usually Several configurations can be found on the field today.
between the 2 polarities (+)&(-), there are 2 MOVs with
5.1 I configuration
their own thermal disconnector. Assumption is that both
MOVs in series cannot turn to sudden sort circuit in one Only one element comprising an MOV and its thermal
time and thus, the remaining ‘alive’ MOV is suddenly disconnector is used
connected to the normal voltage of the photovoltaic
generator. In this condition, the MOV must be able to +/-
disconnect safely with a time constraint. Knowing this, it
is clear that architecture of SPDs using only one MOV
between polarities is not really addressed by this test
procedure even if, to not forbid technology, a test using a + / - / PE
50% degraded MOV is proposed to simulate the same
test stress. But this last test does not consider that MOV Figure 8
can turn suddenly to short circuit whereas once know that
this can occur in real life.
The protection mode is reduced at its minimum, (only
The conclusion is that only SPDs with 2 MOVs with their
one) the only grounding system where it could
own thermal disconnection system in series are able to be
theoretically protect is the direct grounding system where
declared as open circuit mode. This, except if a real short
this element in connected between polarities. But in
circuit test is performed (witch is not the case in present
practice, and for the raison explain in sub clause 3.3, this
EOL test procedures).

1304-5
configuration does not reply to the surge protection but the EOL will lead to the fuse blowing which will in
needs. addition create maintenance costs.
In addition, for that configuration Open Circuit Mode Ground connection through a resistor looks like the
(OCM) is not possible for MOV based SPDs if no real system that better corresponds to this architecture as soon
short circuit test is performed. Based on possible test as EOL test is performed with the adequate resistor
available today, we will assume that in this case, only (because “ungrounded polarity to PE” short circuit
Short Circuit Mode (SCM) and the 2 States Mode (2SM) current is very limited by the few kilo Ohms resistor).
are possible (see 4.2). But again, in case the element connected in the resistor
This will lead to forbid this configuration for installation parallel branch is a sudden short circuit no EOL check is
using a transformer-less inverter in case of connection in possible.
between active cables and ground (see 2.2). In all cases, As a conclusion, this configuration seems to be the
if a connection from active cables to ground is realized simplest but in facts requires deep investigation to
by the SPD it will stop electrical production due to specify it and in not suitable for many situations.
inverter safety requirement.
5.3 L configuration
As a conclusion, this configuration (alone) does not fit to
any PV applications. 2 elements are connected from one polarity to ground in
Note that it can be a part of the assembly detailed in the series and the other polarity is connected to the common
following sub clauses. point.
5.2 ‘V configuration
2 elements are independently connected from the + /-+/-
polarities to ground and have common point to earth.

+/- +/-

PE

Figure 10
PE
Concerning the protection modes, they can all be
Figure 9 declared but these protection modes are not symmetrical.
This is not a blocking point if the protection level given
All protection modes can be declared and thus this point by the highest current path is compatible with the
is not a blocking aspect. equipment to protect.
In case of ungrounded system using a transformer-less For this configuration OCM is not possible for the MOV
inverter, SCM and 2SM SPDs cannot be used for raison SPD branch connected between polarities if no real short
explained in § 2.2. circuit test is performed (see 4.2).
In case of ungrounded system with galvanic separation, In case of ungrounded and transformer-less system, the
the SCM can be acceptable for safety but will stop the branch connected to ground cannot have SCM or 2SM
electricity production up to the maintenance action. The (see 2.2)
2SM can be acceptable as well as the OCM. But In case of ungrounded system with galvanic separation,
independently of the EOL behavior, the technical the same remark as L configuration has to be made.
feasibility will be very low knowing that each branch of This configuration can be used for d.c. grounded system.
the SPD has to withstand the maximum voltage in case of As a conclusion, this configuration as the V configuration
earth fault (not created by SPD) and in the same time has requires deep investigation, but a L configuration SPD
to reach its EOL mode in case one branch turns to sudden with OCM mode for the branch connected to ground and
short circuit. These 2 requirements are in perfect SCM or 2SM for the branch connected between (+) and
opposition and independent of EOL behavior. (-), is possible. We simply recall that 2SM behavior I is
For grounded system, different situations have to be not addressed today in testing procedure for MOV SPDs
considered. intended to be connected between live d.c. source PV
In case of direct grounding, again, this configuration generator.
cannot be declared with the OCM for the branch where 5.4 ∆ configuration
short circuit condition can occur if no real short circuit
test is performed. So, only SCM and 2SM are really Combination of I, V or L configuration.
possible on the above mentioned branch.
For the Fuse grounding the same analysis can be made

1304-6
End Of Life (MOV SPD)

Architecture

Earth fault

Protection
Branch

modes
+/- +/-

SCM or

OCM
2SM
I (+) to (-) // // // Only one
(+) to (-) possible not possible // All
PE L
(+) to Gnd possible not possible Yes All
Figure 11 (+) to (-) possible possible // All
V (+) to Gnd possible not possible Yes All
All protection modes can be declared and thus this point (-) to Gnd possible not possible Yes All
(+) to (-) possible not possible // All
is not a blocking aspect. D (+) to Gnd possible not possible Yes All
But this configuration cumulates all the disadvantages of (-) to Gnd possible not possible Yes All
the L and V configuration concerning the end of life (+) to (-) possible possible // All
Y (+) to Gnd possible possible No All
behavior linked to converter technology and grounding
(-) to Gnd possible possible No All
aspects.
Thus, unless not to e comply with some rules described
Table 1
below, it is impossible to use this configuration.
5.5 Y configuration On each branch of all configurations the table 1 shows
A floating point is connecting 3 elements to create this Y the possible end of life mode behavior and the impact on
connection. The 3 elements are not always identical. possible earth fault. In this table 1, the protection mode
aspect is also addressed.
+/- +/-
+/- +/- Earth fault consequences SPD Short circuit (+ -)

Grounding
Converter
typology

Production

Production
Converter

Converter
Human

Human
or
Transformer-less Danger Danger Stop // Burns Stop
Ungrounded
// // Stop // Burns Stop
PE Direct grounding // // Stop // Burns Stop
PE Transformer
Fuse grounding // // Stop // Burns Stop
Resistor // // Stop // Burns Stop
Figure 12
Table 2
All protection modes can be declared and thus this point
is not a blocking aspect. The table 2 shows the risk of the effect of a possible earth
For configuration authorize all EOL behaviors. fault on converters, human and on electric production. As
These EOL mode can be different depending on the well as the risk of the effect of a possible short circuit due
branch that are tested and thus this can lead to several to SPD end of life.
solutions This table 2 is not to be considered if the earth fault and
This configuration is the only possible solution for the the SCM or 2SM are avoided which is only possible with
inverter using the transformerless technology. In addition Y configuration as shown in table 1.
to the EOL open circuit principal for at least the branches
connected between positive and negative polarity; 7 CONCLUSIONS

6 SYNTHESIS A deep analysis of the grounding aspect, inverter


technology, EOL behavior of the SPD shows that SPD
In the following tables, a sum up of all detailed points configuration is a crucial aspect for SPD selection.
discussed in previous chapters is given. Today, because of market demands, many solutions are
on the field and do not follow these specific safety or
functional requirements. The consequence is of course a
risk of creating more problems because of SPD than
because of surge… which is not in lightning specialist
goal list.
Following this study, it exists different SPD
configurations possible depending on several factors:
Grounding d.c. system, inverter technology and SPD end
of life. Considering the MOV base SPDs, only one SPD
configuration is suitable for all types of photovoltaic

1304-7
installations. As advice from the writer and knowing the
different possible installations, it is more reasonable to
always select the SPD with the Y configuration OCM.

8 REFERENCES
[1] IEC 62305-4 Protection against lightning - Electrical
and electronic systems within structures
[2] IEC 61643-12 ed2 Low-voltage surge protective
devices – Part 12: Surge protective devices
connected to low-voltage power distribution systems
– Selection and application principles
[3] UTE C 60-74-51 : Parafoudres basse tension – Partie
-51: Parafoudres connectés aux installations de
générateurs photovoltaïques –Exigences et essais
[4] UTE C 15-712 installations électriques à basse
tension guide pratique - installations photovoltaïques
[5] prEN 50539-11:2010: Low-voltage surge protective
devices - Surge protective devices for specific
application including d.c. – Part 11: Requirements
and tests for SPDs in photovoltaic applications

1304-8

S-ar putea să vă placă și