Sunteți pe pagina 1din 1
NOISE LEVEL ELMACO transformers are friends 10 the environment conditions, For this reason the noise created by ELMACO transformers in service are within the minimum level according to DIN 42540. + THE NOISE LEVELS MEASURED AT | M FOR TRANSFORMER UP TO 1600 KYA _Rated power (KYA) Noise level (4B) | 25 up to 50 63 up to 100 125 up to 160 200 up to 250 315 up to 400 500 up to 630 800 up to 1000 1250 up to 1600 _ 3 46 47 48 50 52 54 56 « THE NOISE LEVELS AT 3 M FOR TRANSFORMERS UP TO 5000 KVA Rated power (KVA) Noise level (dB) 2000 $2 2500 53 3150 55 4000 56 5000 57 INSULATION LEVEL: « The following table indicates the testing voltage for different system voltage of transformers according to TEC-60076 System highest Power frequency Impulse test Voltage (KVA) rms Test (kv) rms Voltage (KV) peak Ld 3 8 | 3.6 16 45 72 22 60 12 28 75 24 50 125 36 70, 170