GENERAL NOTES: (ELECTRICAL)

Bldg. Inspectors
02-05-2013
AS-NOTED
1. ALL ELECTRICAL DEVICES FOR THE PRE-ACTION SYSTEM TO BE MOUNTED AND INSTALLED PER

12-153
SD SD

DRC
PER NFPA 72 AND THE DEVICE MOUNTING DETAILS SHOWN ON THIS SHEET.
SD

PARP
2. ALL WIRING FROM THE DEVICES TO THE RELEASING PANEL TO BE DONE IN ACCORDANCE WITH ALL
APPLICABLE CODES, THE LOCAL AUTHORITY AND THE SPECIFICATIONS.

3. ALL WIRING FROM RELEASING PANEL TO FACP AND POWER WIRING TO BE DONE BY OTHERS.

BELL
SD

ELECTRIC BELL TO BE LOCATED ABOVE RELEASING

SYSTEM SENSOR PHOTOELECTRIC SMOKE DETECTOR, 2 WIRE 2W-B


PANEL AS SHOWN ON THE MOUNTING DETAIL SHOWN
ON THIS SHEET. SHOWN BESIDE PARP FOR CLARITY.

MECH/ELECTRICAL ROOM

VIKING RELEASING CONTROL PANEL, MULTI HAZARD VFR-400


SYSTEM SENSOR 6" ELECTRIC BELL 24 VDC, RED 22M24-6
SEQUENCE OF OPERATION
1. PRE-ACTION SYSTEM DESIGNED AS A DOUBLE INTERLOCK ELECTRIC/ELEC-PNUEMATIC:
SD (2) OPERATIONS NEED TO HAPPEN BEFORE THE SOLENOID VALVE ACTIVATES THE
SD DELUGE VALVE AND ACTIVATES THE FIRE SPRINKLER SYSTEM:
a - SMOKE DETECTOR IS ACTIVATED.
b - LOW PRESSURE SWITCH IS ACTIVATED DUE TO THE LOSS OF AIR IN THE SPRINKLER
SYSTEM BECAUSE OF SPRINKLER ACTIVATION.

2. IF SMOKE DETECTOR IS ACTIVATED A SUPERVISORY ALARM IS SENT TO THE FACP AND


THE LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED.
SECURE STORAGE ROOM STORAGE AREA 3. IF LOW PRESSURE SWITCH IS ACTIVATED A SUPERVISORY ALARM IS SENT TO THE FACP

WITH (2) 12V BATTERIES


SD
AND LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED.

4. IF A CONTROL VALVE IS MOVED FROM ITS OPEN POSITION A SUPERVISORY ALARM IS


IS SENT TO THE FACP AND LOCAL ALARM (ELECTRIC BELL) IS ACTIVATED.

5. IN THE CONDITION THAT A SMOKE DETECTOR AND THE LOSS OF AIR PRESSURE BELOW
20 PSI IS MET THE SOLENOID VALVE IS TRIPPED AND THE DELUGE VALVE IS OPEN, ALARM
PRESSURE SWITCH SENDS A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A FLOWING
CONDITION INITIATING BUILDING FIRE ALARM SYSTEM.
6. IF EMERGENCY RELEASE LOCATED ON TRIM OF DELUGE VALVE IS PULLED SOLENOID IS ENERGIZED
TRIPPING THE DELUGE VALVE AND A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A

BELL
FLOWING CONDITION. (NO WATER IS SENT INTO THE PIPING OR DISCHARGED UNTIL A SPRINKLER

PARP
IS ACTIVATED.)

SD
(7) -

(1) -

(1) -
EOLR
5.1K
BASEMENT - DETECTION PLAN
1/4"=1'-0"

SD

SD

EOLR
5.1K SD

TS SD

TS SD

AC POWER SUPPLY HOT - BLACK


120 VAC 60 Hz
165 VAC MAX EOLR EOLR
NEUTRAL - WHITE 5.1K TS 5.1K SD
220 VAC 50Hz
185 VAC MAX A A A A
CIRCUIT IS NON-POWER EARTH GROUND - GREEN
LIMITED AND SUPERVISED
EOLR EOLR EOLR
120 OHM 5.1K LAS TS APS SD 5.1K 5.1K
(BY OTHERS)

N L + - + - S + - + - + - + - + - + - + -
24 VNR DC RS-485 AUX. POWER SUP1 SUP2 ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VR DC

SYMBOL LEGEND
SD SMOKE DETECTOR
7 ZONE 1 OUTPUT 1
APS ALARM PRESSURE SWITCH POTTER ELECTRIC PS10-2A
1 ZONE 2 OUTPUT 2
TS TAMPER SWITCH INTERNAL ON BUTTERFLY VALVES
4 ZONE 3 OUTPUT 3
LAS LOW AIR PRESSURE SWITCH POTTER ELECTRIC PS40-2A PROGRAM RUN
1 MODE MODE
ZONE 4 OUTPUT4
SOL PRE-ACTION SYSTEM RELEASING SOLENOID VALVE SCROLL-UP
1 BUZZER SILENCE
AC POWER SUPERVISORY 1
BELL ELECTRIC BELL 24VDC WITH BACK BOX POWER TBL SUPERVISORY 2
1 LAMP
TEST
SYSTEM TBL COMMON ALARM
PARP PRE-ACTION SYSTEM RELEASING PANEL VIKING VFR-400 SET SCROLL-DOWN
1 SUP TBL ALARM SILENCE BUZZER SILENCE
GROUND STEADY DISCHARGED
FAULT FLASHING PRE-
NOTE: DISCHARGED
TAMPER SWITCHES ARE INTERNALLY WIRED
INTO EACH BUTTERFLY VALVE. SELECT SIGNAL SILENCE

CABLE TYPES FUNCTION SYSTEM RESET

VIEWING ANGLE

A PAIGE ELECTRIC 4547OARE 16/2 FPLP SLC CABLE (NON SHIELDED)

B PAIGE ELECTRIC 454719ARE 14/2 FPLP NAC CABLE

OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4


BAT+ BAT- - + - + - + - + com no nc com no nc com no com no

BATTERY CABLE
OBSERVE POLARITY BELL SOL 5.1K 5.1K
EOLR EOLR WIRED TO BUILDING

BLACK
RED +
BLACK - B B FIRE ALARM CONTROL PANEL

RED
NON-POWERED LIMITED (BY OTHERS)
AND SUPERVISED
5.1K 5.1K
EOLR EOLR

+ - + -
POS NEG POS NEG

12V BATTERY 12V BATTERY PRE-ACTION SYSTEM RELEASING CONTROL PANEL


NOT TO SCALE