TO PMS

NO. TYPE OF SIGNAL SIGNAL DESCRIPTION SDI SDO SAI SAO

FEEDER VFD FEEDER- TYPE M6


IED MICROLOGIC 6.2E / VFD ALTIVAR 630
PROTOCOL MODBUS TCP / IP (VFD) / MODBUS RTU (MICROLOGIC)
1 STATUS VFD/MOTOR RUNNING 1
2 STATUS VFD/MOTOR STOPPED 1
3 ALARM VFD TRIP 1
4 STATUS MCCB ON 1
5 TRIP/ALARM PROTECTION RELAY OPERATED (37) 1
6 TRIP/ALARM PROTECTION RELAY OPERATED (49) 1
7 TRIP/ALARM PROTECTION RELAY OPERATED (46) 1
8 TRIP/ALARM PROTECTION RELAY OPERATED- motor stall error 1
9 ALARM VFD COMMUNICATION FAILURE 1

10 TRIP/ALARM UNDER VOLTAGE (27) OPERATED 1


11 TRIP/ALARM OVER CURRENT (51P/50P) OPERATED 1
12 MEASUREMENTS LINE CURRENT La 1
LINE CURRENT Lb 1
LINE CURRENT Lc 1
13 MEASUREMENTS Active Load (kW) 1
14 MEASUREMENTS POWER FACTOR 1
15 MEASUREMENTS MOTOR run time 1
TOTAL 11 0 6 0
MS TO HCP Register Address
HDI HDO HAI HAO logic Bit Value Test
Address Address

3201 2 ok
3201 5 ok
3201 3 ok
5202 2 ok
7121 100
7121 16
7121 33 ok
7121 148 ok
PMS will detect this as
comm fail
16113 6 ok
12004 1
12015
12016
12017
3294 OK
13787 OK
3246 OK
0 0 0 0

from micrologic