>> L-TRI 5
up to 36 kV
Selection Guide
AREVA T&D
Terms of delivery
The General Terms of Delivery, as amended, shall apply.
Illustrations
The illustrations are not binding for delivery.
>> Contents
INTRODUCTION
The L-TRI 5 range of switch disconnectors
Main applications for L-TRI 5
4
4
4
Special features of L-TRI 5 4
Type designation 5
Product range 12/17.5 kV 6
Product range 24/36 kV 7
Product range 12/24 kV to IEC 62271-105 8
DESCRIPTION 9
Cable disconnector L-TRI 5...-D 9
Transformer disconnector L-TRI 5...-UH-KS-A 10
Switch disconnector L-TRI 5...-KS-AA 11
Transformer disconnector L-TRI 5...-UH-D 11
Transformer disconnector L-TRI 5F...-UH-KS-A 12
Integrated cable disconnector and earth switch 13
Integrated transformer disconnector and
earth switch 14
ACCESSORIES 15
Auxiliary switch HS 3 15
Standard attachment variants for auxiliary switches 16
Signalling switch MSKM 17
Breaking-current shunt release 17
(operating current release AA)
Capacitor dividers 18
Clamping lever 18
Manual drives 19
Motor drives 19
Plug-in board 19
SELECTION TABLES 24
Characteristic values of switch disconnectors
(cable disconnectors) 24
Characteristic values of switch disconnectors
(transformer disconnectors) 26
3
>> Introduction
The L-TRI 5 range of switch discon- L-TRI 5 switch disconnectors are > high reliability and long service life
nectors, incorporating proven flat- designed for use in indoor medium- > low operating cost due to long
chamber arcing technology, can per- voltage switchgear systems. They periods between maintenance
form a wide variety of switching have a making capacity and are suit- procedures
functions in medium-voltage distribu- able for switching: > space-saving design
tion systems. They are the result of > load currents > high switching capability
more than 50 year’s experience in > currents in ring mains > low operating torques
development and manufacture of > transformers, cables and overhead > suitable for use in in harsh climatic
switch disconnectors by AREVA lines. conditions
(formerly Concordia Sprecher). The > ideal as substitute for older switch
simple, low-maintenance and highly L-TRI 5 switch disconnectors are the disconnectors (ECOFIT measures)
economic indoor switch disconnec- reliable and economic solution for or disconnectors
tors in the L-TRI 5 range have a pro- refurbishment and maintenance pro- > switch disconnector-fuse combi-
ven service record, with hundreds of grams, extensions, renewal or upgra- nation to IEC 62271-105 (EN
thousands of units installed and ding of personnel protection. 62271-105) available.
operating on a wide range of
systems. L-TRI 5 switch disconnec-
tors comply with the requirements
of IEC 60694 (EN 60694) and
IEC 60265-1 (EN 60265-1). Addi-
tionally, selected variants are availa-
ble, complying with IEC 62271-105
(EN 62271-105).
4
TYPE DESIGNATION
Example L - T R I 5 / 1 2 / 4 0 0 / 2 1 0 - D - E A - VA
Switch disconnector
to IEC 60265
Rated voltage 12 kV
Standard drive
Rapid ON/OFF
5
PRODUCT RANGE 12/17.5 KV
Breaking
Type Rated Rated Pole centre Fuse carrier Drive current shunt Integrated Mechanical
voltage current spacing release earth switch interlock
- ET - VT
-D
- EA - VA
125 T - ET - VT
400/ -D
165 - EU - VU
- UH
210 - ET - VT
630/ - KS - A (- AA)**
250 - EU - VU
- KS - AA - ET - VT
165
210
12/ 1000/
- ET - VT
-D
- EA - VA
1250/
250
210
- ET - VT
2500/ 250 -D
- EA - VA
L-TRI 5/
- ET - VT
-D
- EA - VA
- ET - VT
400/ -D
- EU - VU
210 - UH
- ET - VT
630/ - KS - A (- AA)**
- EU - VU
- KS - AA - ET - VT
17,5/
- ET - VT
1250/ 250 -D
- EA - VA
- ET - VT
2500/ 270 -D
- EA - VA
6
PRODUCT RANGE 24/36 KV
Breaking
Type Rated Rated Pole centre Fuse carrier Drive current shunt Integrated Mechanical
voltage current spacing release earth switch interlock
- ET - VT
-D
- EA - VA
- ET - VT
165 T
400/ -D - EUI - VUI
250 - EU - VU
- UH
275 - ET - VT
630/ - KS - A (- AA)** - EUI - VUI
300
- EU - VU
- KS - AA - ET - VT
24/
250
- ET - VT
1000/ 275 -D
- EA - VA
300
1250/
- ET - VT
300 -D
- EA - VA
1600/
L-TRI 5/
- ET - VT
-D
- EA - VA
340(T) - ET - VT
-D
- EUI - VUI
630/ 370 - UH
- ET - VT
- KS - A (- AA)**
400 - EUI - VUI
36/
340(T)
- ET - VT
1000/ 370 -D
- EA - VA
400
7
PRODUCT RANGE 12/24 KV
TO IEC 60420
Breaking Integrated
Type Rated Rated Pole centre Fuse carrier Drive current Mechanical
earth switch
voltage current spacing shunt release interlock
125 T
165 - ET - VT
12/ 400/* - UH - KS - A (- AA)**
210 - EU - VU
250
L-TRI 5F/
165 T
- ET - VT
250
24/ 400/* - UH - KS - A (- AA)** - EUI - VUI
275
- EU - VU
300
Legend:
T Phase partitions
KS Stored energy drive; rapid CLOSING – breaking energy stored / rapid OPENING
UH Fuse carrier
A Fuse trip linkage for all-pole tripping
AA Breaking current shunt release
ET Mounted earthing switch on fixed-contact side
EUI Mounted earthing switch on fuse carrier, internal
EU Mounted earthing switch on fuse carrier side, external
VT MMechanical interlock for ET
VUI Mechanical interlock for EUI
VU Mechanical interlock for EU
* Commonly, the rated current of the switch disconnector-fuse combination is lower (see technical data).
** Breaking current shunt release
When motor-driven, no mechanic interlock between disconnector and earth switch is possible!
8
>>
CABLE DISCONNECTOR
Description
L-TRI 5...-D
5
Legend
1 Base frame
2 Epoxy resin insulator
4
3 Switch drive shaft
4 Main current path with
push rod
5 Arcing chamber
L-TRI 5...-D
9
TRANSFORMER
DISCONNECTOR L-TRI 5...- 5 4
UH-KS-A
Legend
6
1 Base frame
2 Epoxy resin insulators
3 Switch drive shaft
4 Main current path 8
As for the D-type disconnector, this For the drive type KS..(rapid CLO- L-TRI 5 switch disconnectors employ
type also consists of the main com- SING, stored energy for OPENING, proven flat arcing chambers working
ponents (1) to (5). Additionally, the rapid OPENING), low-maintenance on the hard gas principle. The arc
elongated base frame carries epoxy springs are used. Charging of the quenching facility is shunted to the
resin insulators with fuse carriers breaking springs occurs automatical- main current path and incorporates
(6) to accommodate HH fuses to ly during the closing action. After the a flat arcing chamber and arcing
DIN 43625 and the fuse tripping rapid closing action, the opening blade for each phase. The optimized
device (8). energy remains stored in the brea- design and the use of an improved
king spring. Opening may occur quenching medium have allowed the
immediately after closing by actuati- dimensions to be reduced and the
on of the switch drive shaft, by trip- service life to be increased
ping of an HH fuse, or by an atta-
ched breaking current shunt release.
The drive angle is 90°.
10
SWITCH DISCONNECTORS
L-TRI 5...-KS-AA
General
Design
TRANSFORMER DISCON-
NECTOR L-TRI 5...-UH-D
General
Design
11
TRANSFORMER
DISCONNECTOR
L-TRI 5F...-UH-KS-A
L-TRI 5F...-UH-KS-A-EU-VU
12
CABLE DISCONNECTOR E a r t h s w i t c h o n f i x e d - c o n t a c t s i d e E T
WITH INTEGRAL EARTH
SWITCH 3 5 1
Legend
2
6
1 Base frame extension
2 Earth shaft
3 Earth blade
4 Rapid closing SPRING
5 Earth contact
6 Mechanical interlock
6
2
5 3 4
E a r t h s w i t c h o n m o v i n g - c o n t a c t s i d e E A
L-TRI 5...-D-ET-VT-EA-VA
Earth switches mounted on switch The earth shaft (2) and the earth bla- Rapid operation of the earth switch
disconnectors improve safety for the des (3) are mounted on the frame drive is achieved with a toggle
operating personnel and operational extension (1) which is connected to spring action. When operating the
reliability. The integrated earth swit- the disconnector base frame. The shaft, the dead point is passed after
ches have a defined high making earth contacts (5) are mounted on approx. 15° and the rapid closing is
capacity and are equipped with a the connecting brackets. The rapid activated. It is possible to add a
rapid closing facility in the form of a closing spring (4) is attached bet- mechanical interlock between the
rocker spring. The connection bet- ween the earth shaft (2) and the dis- shafts of the switch disconnector
ween switch shaft and frame forms a connector base frame. and the integrated earth switch (VT
reliable transition resistance so that Earth switches may be mounted on and VA). This interlock prevents clo-
an additional earthing strap is not the: sing of the open earth switch when
necessary. The integrated earth swit- > fixed-contact side ET the switch disconnector is CLOSED,
ches have a making capacity, and > moving-contact side EA and closing of the open switch dis-
can be mounted on the fixed and/or and also on both sides. connector when the earth switch is
the moving contact side of the closed. The mechanical interlock
switch disconnector. between switch disconnector and
earth switch is available only on
manual drive versions.
13
TRANSFORMER DISCON-
NECTOR WITH INTEGRAL Integrated earth switch type ET
EARTH SWITCH
14
>>
AUXILIARY SWITCH HS3
Accessories
Auxiliary switch (HS3) for switch disconnectors type L-TRI 5 and L-TRI 5F
Switch disconnectors and integrated Rated Rated Pole centre Number of contacts
earth switches can be fitted with voltage current spacing
auxiliary switches type HS 3 as kV A mm 4pole 6pole 10pole
4-pole, 6-pole or 10-pole variants
125 ●
with user-configurable contacts
(normally closed, normally open, 12 400...2500 165 ● ●
change-over). The high switching
210, 250 ● ● ●
capability allows the direct triggering
of releases, locking magnets and 17.5 400...2500 210, 250, 270 ● ● ●
attachments to motor drives (see 165 ●
technical data). 24 400...1600
250, 275, 300 ● ● ●
125 ●
12 400...2500 165 ● ●
210, 250 ● ● ●
165 ●
24 400...1600
250, 275, 300 ● ● ●
4-pole auxiliary switch attachment 36 630...1000 340, 370, 400 ● ● ●
on a type ET earth switch
Technical data
15
STANDARD MOUNTING
Auxiliary switch for Earth
VARIANTS FOR
ET earth switch switch ET
AUXILIARY SWITCHES
L1 Earth
L2 switch EA
Auxiliary switch for L3
switch disconnector Auxiliary switch for
earth switch EA
16
SIGNALLING SWITCH Signalling switch (MSKM), HH fuse released
MSKM (only possible with all-pole fuse release).
Technical data
Switching capability 10 A 6A 4A 2A 6A
BREAKING-CURRENT
SHUNT RELEASE
(OPERATING
CURRENT RELEASE AA)
17
CAPACITOR DIVIDERS
CLAMPING LEVER
The following clamping levers are Divider attachment on the moving-contact side
available for the operation of stan-
dard variants of the switch discon-
nectors and earth switches:
Clamping
lever type
QW 6
18
MANUAL DRIVES
STAD 2
MOTOR DRIVES
PLUG-IN BOARD
12 kV = 4 mm
17.5 kV = 6 mm
24 kV = 8 mm
36 kV = 10 mm
19
>> Selection of mounting position, drive
side and shaft length
MOUNTING POSITION
Standard
wall-mounting
Inverted
wall-mounting
Floor-mounting
20
Selection of the drive side
The selection of the drive side depends on whether manual or motor drive is used and on requierements for a mechani-
cal interlock.
Attached Attached
Manual drive motor drive Manual drive motor drive Mechanical interlock
left right left right left right left right possible
●
●
● ●
● ●
● ● ●
● ● ●
●
●
● ● ●2)
● ● ●2)
1) 1)
● ●
●1) ●1)
1) For a combination of 3 switching devices (1 switch disconnector and 2 integrated earth switches) a maximum of two motor drives can be fitted.
Referred to the device they are located opposite to each other.
2) Activation of the motor by an auxiliary switch on the earth switch is strongly recommended for a motor drive on the load switch disconnector.
The selection of shaft length depends on the rated voltage and the pole centre spacing.
Pole centre spacing (mm) 125 T 165 210 250 210 250 270 165 T 250 275 300 340 T 370 400
340
Shaft length (mm) 566 ● ●
588 ●
666 ● ●
766 ● ● ● ● ●
866 ● ● ● ●
966 ● ● ● ● ● ● ● ●
1066 ● ●
1100 ● ●
1500 ● ● ●
21
>>
STANDARDS
Standards and tests
IEC EN
22
TRANSFORMER TRANSFORMER An inspection is recommended after
DISCONNECTORS TO DISCONNECTORS 1500 switching cycles or after
IEC 62271-105 TO IEC 60265-1 a serious short-circuit fault. In most
TYP L-TRI 5F applications, it will never be neces-
In addition, switch disconnector-fuse sary to replace any parts during the
IEC 62271-105 is a supplementary combinations to IEC 60265-1 operating life of the equipment. In
regulation for "Transformer discon- (EN 60265-1) are available, for event of the maximum number of
nectors" and specifically applies to breaking transformers of higher breaking operations actually being
switch disconnector-fuse combi- power ratings: reached, it is a simple operation to
nations with fuse release (type > 12 kV transformers up to replace the arc quenching device.
L-TRI 5F...-UH-KS-A). The combina- 1250 kVA.
tion of switch disconnector and > 24/36 kV transformers up to
fuse is considered to be one unit 1600 kVA. QUALITY
and has to be tested accordingly.
As the standard also requires the The consistently high quality
breaking of high fault currents with CLIMATIC CONDITIONS standards achieved by of our pro-
unfavourable power factors (cos ϕ) ducts are ensured by our DIN ISO
the arc quenching system has been The design, components and tole- 9001 quality assurance management
modified and improved, but at the rances for the switch disconnectors procedures, in accordance with
same time retaining the proven con- are selected so that the devices can DIN ISO 9001 introduced in 1993.
cept of the flat arcing chamber. The be used without any restriction in
type L-TRI 5F can be easily recogni- indoor conditions in accordance with
zed by the curved arcing blades (see IEC 60694 (EN 60694) over a maxi- ECONOMY
photograph, page 12). mum temperature range of -25°C to
+40°C. When it comes to minimising procu-
The type L-TRI 5F…-UH-KS-A can rement and operating costs, we
be used at operating voltages of recommend you consider the advan-
10/12kV with a transformer power LOW MAINTENANCE tageous economic benefits of the
ratings up to 1000 kVA, and at ope- L-TRI 5 range of products and
rating voltages of 20/24 kV with a In normal operational conditions accessories, in terms of quality,
transformer power ratings up to (so called EVU use) as specified in operational and functional reliability,
1250 kVA. The fuse selection table relevant regulations, L-TRI 5 switch availability and low maintenance
assigns the tested HH fuse links disconnectors are virtually mainten- costs.
from different manufacturers to the ance-free, as the time between two
different transformer ratings, and is maintenance procedures is approxi-
to be considered for engineering. mately 15 years under normal clima-
tic conditions.
23
>>
CHARACTERISTICS
Selection tables
OF SWITCH DISCONNECTORS
(CABLE DISCONNECTORS)
Type
to standard
Rated voltage Ur kV 12
Rated frequency fr Hz 50/60
Rated lightning impulse withstand voltage Up
to earth kV 75
between phases kV 75
across the isolating gap kV 85
Rated withstand alternating voltage Ud
to earth kV 28
between phases kV 28
across the isolating gap kV 32
Rated current lr A 400 630 1000 1000 1250 2500 400
Rated short-time current 1s Ik kA 25 25 40 32 40 50 25
3s kA 18 18 23 23 25 35 18
Rated peak current Ip kA 63 63 63 80 100 125 63
Rated short-circuit making current Ima kA 63 63 63 63 50 50 63
Number of operations at rated short-circuit making current n 2 2 2 2 2 2 2
Rated system breaking current for 20 cycles I1 A 400 630 630 630 630 630 400
System breaking current for 3 cycles A 1000 1000 1250 2500
System breaking current for 200 cycles A 32 32 32 32 35 35 32
Rated ring main breaking current I2a A 400 630 630 630 630 630 400
Rated transformer breaking current I3 A 10 10 10 10 10 10 10
Rated cable and overhead line breaking current I4a, I4b A 50 50 50 50 50 50 50
Rated earth-fault breaking current I6a A 150 150 150 150 150 150 150
Rated cable and overhead line breaking current I6b A 86 86 86 86 86 86 86
under earth-fault conditions
Mechanical operations n 1500 1500 1500 1500 1000 1000 1500
125 mm ❍1) ❍1)
165 mm ● ● ●
210 mm ● ● ● ● ● ●
Pole centre spacing 250 mm ● ● ● ● ● ●
(3-pole switchgear) 270 mm
275 mm
300 mm
340 mm
370 mm
400 mm
Integrated earth switch
Rated short-time current 1s Ik kA 25 25 252) 32 32 32 25
2)
3s kA 14 14 14 23 23 23 14
Rated peak current Ip kA 63 63 63 80 80 80 63
Rated short-circuit making current Ima kA 63 63 63 80 80 80 63
1)
With phase partitions
2)
Higher values on request.
24
L-TRI 5
IEC 60265-1 (EN 60265-1)
17.5 12 36
50/60 50/60 50/60 50/60
38 50 70 70
38 50 70 70
45 60 80 80
630 1250 2500 400 630 1000 1000 1250 1600 630 1000 630 1000
25 40 50 25 25 40 32 40 40 20 20 20 20
18 25 35 18 18 23 23 25 25 14 14 14 14
63 100 125 63 63 63 80 100 100 50 50 50 50
63 45 45 63 63 63 63 37 37 20 20 20 20
2 2 2 2 2 2 2 2 2 2 2 2 2
630 630 630 400 630 630 630 630 630 630 630 630 630
1250 1250 1000 1000 1250 1600 1000 1000
32 35 35 32 32 32 32 35 35 32 32 32 32
630 630 630 400 630 630 630 630 630 630 630 630 630
10 10 10 10 10 10 10 10 10 6,3 6,3 6,3 6,3
50 50 50 50 50 50 50 50 50 25 25 25 25
150 150 150 285 285 150 150 150 150 70 70 70 70
86 86 86 86 86 86 86 86 86 40 40 40 40
1500 1000 1000 1500 1500 1500 1500 1000 1000 1000 1000 1000 1000
❍1) ❍1)
●
● ● ● ● ●
●
● ● ● ●
● ● ● ● ● ●
❍1) ❍1) ● ●
● ●
● ●
25 32 32 25 25 252) 32 32 32 20 20 20 20
2)
14 23 23 14 14 14 23 23 23 14 14 14 14
63 80 80 63 63 63 80 80 80 50 50 50 50
63 80 80 63 63 63 80 80 80 50 50 50 50
25
CHARACTERISTICS VALUES
OF SWITCH DISCONNECTORS
(TRANSFORMER DISCONNECTORS)
Type L-TRI 5
to standard IEC 60265-1 (EN 60265-1)
Rated voltage Ur kV 12 17.5 24
Rated frequency fr Hz 50/60 50/60 50/60
Rated lightning impulse withstand voltage Up
to earth kV 75 95 125
between phases kV 75 95 125
across the isolating gap kV 85 110 145
Rated withstand alternating voltage Ud
to earth kV 28 38 50
between phases kV 28 38 50
across the isolating gap kV 32 45 50
Rated current lr A 400 630 400 630 400 630
Rated short-time current 1s Ik kA 25 25 25 25 25 25
3s kA 18 18 18 18 18 18
Rated peak current Ip kA 63 63 63 63 63 63
Rated short-circuit making current Ima kA 63 63 63 63 63 63
Number of operations with rated short-circuit making current n 2 2 2 2 2 2
Rated short-circuit breaking current kA
System breaking current for 20 cycles A 400 630 400 630 400 630
System breaking current for 200 cycle A 32 32 32 32 32 32
Rated transformer breaking current I3 A 10 10 10 10 10 10
Rated cable and overhead line breaking current I4a, I4b A 50 50 50 50 50 50
4)
Rated current for fuse carrier A 200 200 200 200 200 200
Rated take-over current with striker pin release I4 A
Mechanical operations n 1500 1500 1500 1500 1000 1000
1) 1)
125 mm ❍ ❍
165 mm ● ● ❍1) ❍1)
210 mm ● ● ● ●
Pole centre spacing 250 mm ● ● ● ●
(3-pole switchgear) 275 mm ● ●
300 mm ● ●
340 mm
370 mm
400 mm
Opening times of the switch disconnector To ms
with striker pin operation
Type of the approved fuse striker pin medium medium medium
Fuse length e mm 292 367 442
292 3)
Integrated earth switch
Rated short-time current 1s Ik kA 25 25 25 25 25 25
3s kA 14 14 14 14 14 14
Rated peak current Ip kA 63 63 63 63 63 63
Rated short-circuit making current Ima kA 63 63 63 63 63 63
Number of operations at rated short-circuit making current n 2 2 2 2 2 2
26
Switch disconnector-fuse
combination
L-TRI 5F
IEC 62271-105 (EN 62271-105)
36 12 24
50/60 50/60 50/60
70 70 28 50
70 70 28 50
80 80 32 60
2) 2)
400 630 200 200
25 20 16 16
18 14
63 50 40 40
63 25 40 40
2 2 2 2
25 25
630 630 200 200
32 32 32 32
6,3 6,3 10 10
25 25 50 50
200 200 200 200
1250 800
1000 1500 1500 1500
❍1)
● ❍1)
●
● ●
●
●
❍1) ●
●
●
20 20 16 16
14 14 14 14
63 50 40 40
63 50 40 40
2 2 2 2
27
>> Dimensions and weights
L-TRI 5/12/400...1000/...-D
28
L-TRI 5/12/400...630/...-UH-D
L-TRI 5/12/400...630/...-UH-KS-A
29
L-TRI 5/12/400...630/...-KS-AA
30
L-TRI 5/12/1250/...-D
Weight of Weight of
A B C D L-TRI 5 earth switch
966 630 250 700 57 13
Reference dimension is "C” (pole centre spacing) 966 630 210 600 55 12.5
Define dimension "A” (switch shaft length).
Weights in kg 766 630 210 600 55 12.5
L-TRI 5/12/2500/250-D
31
Dimensions and weights of L-TRI 5, 17.5 kV
L-TRI 5/17.5/400...630/210-UH-D
L-TRI 5/17.5/400...630/210-UH-KS-A
32
L-TRI 5/17.5/400...630/210-KS-AA
L-TRI 5/17.5/400...630/210-D
33
L-TRI 5/17.5/1250/250-D
L-TRI 5/17.5/2500/270-D
34
Dimensions and weights of L-TRI 5, 24 kV
L-TRI 5/24/400...1000/...-D
Weight of Weight of IR
A B C D L-TRI 5 earth switch [A]
1066 775 300 750 32 11.5
966 775 300 750 32 11.5
1066 775 275 750 32 11.5 400/
966 775 275 750 32 11.5 630/
1000
966 655 250 630 29 10.5
866 655 250 630 29 10.5
766 655 250 630 29 10.5
766 485 165T 460 28 8.5 400/
666 485 165T 460 28 8.5 630/
566 485 165T 460 28 8.5
35
L-TRI 5/24/400...630/...-UH-D
L-TRI 5/24/400...630/...-UH-KS-A
36
L-TRI 5/24/400...630/...-KS-AA
37
L-TRI 5/24/1250/300-D
38
Dimensions and weights of L-TRI 5, 36 kV
L-TRI 5/36/630...1000/...-D
400 59 13 170
370 59 13 170
340 T 59 13 170
340 57 13 145
39
L-TRI 5/36/630/...-UH-D
L-TRI 5/36/630/...-UH-KS-A
400 98 13 170
370 98 13 170
340 T 98 13 170
340 96 13 145
40
Dimensions and weights of L-TRI 5F to IEC 60420, 12 kV
L-TRI 5F/12/400...630/...-UH-KS-A
Weight of Weight of
A B C D L-TRI 5 earth switch
966 665 250 640 41 11
866 665 250 640 41 11
766 665 250 640 41 11
966 625 210 600 38 10.5
866 625 210 600 38 10.5
766 625 210 600 38 10.5
730 485 165 460 35 8
666 485 165 460 35 8
566 485 165 460 35 8
588 405 125T 380 32 7
41
Dimensions and weights of L-TRI 5F to IEC 60420, 24 kV
L-TRI 5F/24/400...630/...-UH-KS-A
42
Notes:
43
Notes:
44
Notes:
45
>> Fax – Request for quotation
To From
Contact name:
Phone: +49 (0)351/820-0
Fax: +49 (0)351/820-2426 Department:
Phone:
Fax/E-mail:
L-TRI 5 /......./......./.......-D
L-TRI 5 /......./......./.......-UH-KS-A
L-TRI 5 /......./......./.......-UH-D
L-TRI 5 /......./......./.......-KS-AA
L-TRI 5F /......./......./.......-UH-KS-AA
Optional extras:
4 pole auxiliary switch on switch disconnector
Release signalling switch MSKM for switch disconnector (for UH-KS-A variant only)
46
AREVA Sachsenwerk GmbH · Rathenaustraße 2 · D-93055 Regensburg · Postfach 10 01 55 · D-93001 Regensburg
Telephone +49 (0)9 41/46 20-0 · Telefax +49 (0)9 41/46 20-4 18