TECHNICAL DATA SHEET

Instructions:
1 Kindly do not alter the contents of the cell which contain formulas
2 Click the appropriate TABS to select/go to the respective sheets.
3 Cells/Columns colour coding
Data Contain standard / Formulas / Results
Data to be Entered Manually
Select from Drop down
Resp. Dept. Prepared by

Doc No: PTC-BBT-D-015, Rev. 0 Date Approved by


Generator Synchronising Panel - Technical Data
Title: 23.06.2017
Sheet

GENERATOR SYNCHRONISING PANEL - TECHNICAL DATA SHEET

Sl. No Description Unit Requirement Data Vendor Confirmation

1.0 GENERAL
1.1 Panel Type Self Standing Panel Yes / No
1.2 Degree of Protection IP-54
1.3 Type of Installation Indoor
1.4 Minimum Ambient Temperature °C 5
1.5 Maximum Ambient Temperature °C 40
1.6 Panel Height mm Vendor to specify
1.7 Panel Width mm Vendor to specify
1.8 Panel Depth mm
Vendor to specify
1.9 Panel Weight kg Vendor to specify
1.10 Auxiliary AC Voltage V 230V, 1Ph
1.11 Auxiliary DC Voltage V DC 220
1.12 Redundant DC Power Supply V DC Required
1.13 Cable Entry Bottom Entry
1.14 Paint Shade RAL 7035
1.15 Panel Labeling As per Manufacturer Standard
1.16 Mimic Requirement Required
2.0 INTERNAL WIRING
2.1 Wire Insulation - FRLS
2.2 Control Wiring Sq.mm 2.5
2.3 Current Transformer Wiring Sq.mm 4
2.4 Voltage Transformer Wiring Sq.mm 2.5
2.5 Wire Colour As per Standard
2.6 Wire Marking Ferruled at both ends.
3.0 COMPONENTS AND
ACCESSORIES
3.1 Panel Illumination with Door Switch - Required
Panel Heating with Thermostat
Required
3.2 Control -
3.3 Ventilation - Exhaust Filters
3.4 AC Power Socket Required
3.5 Spare Terminals 20%
3.6 Terminal for CT With Shorting facility
3.7 Test Terminal Block Required
4.0 SYNCHRONISATION
COMPONENTS
4.1 Synchronisation Configuration Automatic and Manual Channel
4.2 No.of Breakers One (1) for each panel

Auto Synchroniser Model No. & Make Vendor to specify


4.3
Manual Synchroniser Model no. &
Vendor to specify
4.4 Make
4.5 Control of Synchronising Local / Remote
4.6 Dead Bus Closing Option Required
Voltage Adaption and Compensation
Required
4.7 VT's
4.8 Double Voltmeter Required

Page 2 of 3
Sl. No Description Unit Requirement Data Vendor Confirmation

4.9 Double Frequency Meter Required


4.10 Synchroscope Required
4.11 Meter Dimension 96mm x 96mm
4.12 Communication Interface Profibus DP / Ethernet