As per discussion, Please find attached herewith P&ID for HMI screen Development & Logic details for PLC
modification,
1. Low Level (LS-01) T-01A Feed tank, Recirculation Pump & ozone system will Stop.
2. High Level (LS-01) T-01A Feed tank, Recirculation Pump & ozone system will Start.
3. Low Level (LS-02) T-01B Feed tank, UF feed Pump, HIUV-01 & NaOCL Dosing pump will
Stop.
4. High Level (LS-02) T-01B Feed tank, UF feed Pump, HIUV-01 & NaOCL Dosing pump will
Start.
5. ORP-01 High Above Set Point & continuously high for settable time , Ozone gen will Stop.
6. ORP-01 fall below Set Point & continuously low for settable time , Ozone gen Start.
Please proceed for HMI screens Development & logic modification as per today’s discussion.
Also provide quote for Proceed PO.