Installation Instructions for the New Caterpillar Digital Voltage Regulator (CDVR) In Field
Retrofit Applications{4467}
Media Number -REHS4494-02 Publication Date -03/08/2012 Date Updated -06/08/2012
i04967749
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 2 of 12
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 3 of 12
Introduction
Illustration 1 g01425620
The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.
These instructions are provided in order to assist in replacing an existing DVR or VR6 with a new Caterpillar
Digital Voltage Regulator (CDVR). Refer to the Specifications, Systems Operation, Testing and Adjusting,
RENR7941-08, "Cat® Digital Voltage Regulator " for complete information.
Parts kit 329-4513 Conversion Kit is required to complete this retrofit for both the DVR and the VR6 voltage
regulators. The VR6 also requires some additional parts as called out in Table 4.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 4 of 12
Work safely. Most accidents that involve product operation, maintenance, and repair are caused by failure to
observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially
hazardous situations before an accident occurs.
A person must be alert to potential hazards. This person should also have the necessary training, skills, and
tools in order to perform these functions properly.
Safety precautions and warnings are provided in this instruction and on the product. If these hazard warnings
are not heeded, bodily injury or death could occur to you or to other persons. Caterpillar cannot anticipate
every possible circumstance that might involve a potential hazard. Therefore, the warnings in this publication
and the warnings that are on the product are not all inclusive.
If a tool, a procedure, a work method, or operating technique that is not recommended by Caterpillar is used.
Ensure that the tool, procedure, work method, or operating technique is safe to use. Ensure that the product
will not be damaged or made unsafe by the operation, lubrication, maintenance, or the repair procedures that
are used.
Table 1
P6Pin Functions
Pin Function
P6-1 Power Input (single phase)
P6-2 Power Input (single phase)
P6-3 Power Input
P6-4 F-
P6-5 F+
P6-6 Chassis Ground
Table 2
P9 Pin Functions
Pin Function
P9-1 CAN bus - High
P9-2 CAN bus - Low
P9-3 CAN bus - Drain (Shield)
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 5 of 12
Table 3
P12 Pin Functions
Pin Function
P12-1 B-phase generator current sensing ("CT1")
P12-2 B-phase generator current sensing ("CT2")
P12-3 ±10 DCV Input (B), -
P12-4 Alarm Output Driver (24V, 100mA)
P12-5 Fault Shutdown Driver (24 VDC, 100 mA)
P12-6 ±10 DCV Input (A), +
P12-7 18 to 30 V Control Power Input (B-)
P12-8 18 to 30 V Control Power Input (B+)
P12-9 Driver Supply (50) (24 VDC, 100 mA)
P12-10 Generator Voltage Sensing - C (T3), lead 20 for SR4 and SR4B generators) (1)
P12-11 Generator Voltage Sensing - B (T2), lead 24 for SR4 and SR4B generators) (1)
P12-12 Generator Voltage Sensing - A (T1), lead 22 for SR4 and SR4B generators) (1)
(1)
Refer to the generator set wiring diagrams.
Table 4
Additional Parts Required for VR6
Part Number Description Qty
244-0452 Wire End 3
153-2707 Electrical Cable (J1939 communication) 2500 mm (98.42 inch)
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 6 of 12
The CDVR has three multipin plug connectors. The connectors have the following markings: "P6", "P9" and
"P12". Connector "P6" mates with a corresponding connector with six pins on the harness. Connector "P9"
mates with a corresponding connector with nine pins on the harness. Connector "P12" mates with a
corresponding connector with 12 pins on the harness. Refer to the Tables 1, 2 or 3. Each table corresponds to
the connector number in order to identify the function of each pin in the connector.
Illustration 2 g03157977
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 7 of 12
Illustration 3 g03157978
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 8 of 12
Illustration 4 g01456243
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Voltag... Page 9 of 12
Illustration 5 g01015474
The CDVR does not require a burden resistor. When changing from a DVR, remove the resistor in parallel
with the CT for sensing droop. The CT connections are polarized. One of the terminals has a dot. Confirm
that the CT connection with the dot is connected to P12-1 on the CDVR. Refer to the Illustrations 2, 3, and 4.
Note: Whereas the DVR and CDVR require 24V DC power, the VR6 does not. When converting from the
VR6, two extra wires will be needed to jumper from the existing battery power terminations to the included
terminal block. Refer to the Table 4 for the recommended DC wiring.
Note: If the CDVR harness wires (1A and 2A) are long enough for the installation, the recommended battery
jumper wires will not be necessary.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Volt... Page 10 of 12
Illustration 6 g01455440
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Volt... Page 11 of 12
Illustration 7 g01455439
Different labels and additional terminals are provided in the parts kit. These parts are required for the terminal
blocks. These terminal blocks may be located inside the generator terminal box or located in a remote
location. Some labels may need to be changed on the terminal blocks or added to the terminal blocks. These
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 03/04/2018
By NPR - REHS4494 - Installation Instructions for the New Caterpillar Digital Volt... Page 12 of 12
labels include the following: "VAR/PF", "Enable", "Fault Reset" and "Excitation Disable". Refer to the
Illustrations 4 and 5. Install the new terminals and labels that are required for your specific application. Refer
to the Illustrations 6 or 7.
A new momentary switch is provided in the parts kit. The part number for the switch is 110-7884 Toggle
Switch . This switch is used to adjust the voltage on the CDVR output. The common wire to the switch will
replace the following connections: pin 50 to "Excitation Disable", "Fault Reset" and pin 52a enable for VAR
and PF. This switch also replaces the rheostat that was used on the DVR and VR6. Refer to the Illustration 5.
CAN datalink communication wires (P9-1, 2 and 3) are not included in the 243-4271 Wiring Harness . If
datalink communication for the CDVR is desired, it will be necessary to install the additional 153-2707
Electrical Cable . Three 244-0452 Wire Ends will also be needed. These parts are included in Table 4,
"Additional Parts Required for the VR6".
Note: When installing the CDVR on the J1939 datalink, please be aware of the terminating resistor location
and adjust as necessary.
Note: When converting from a VR6 to a CDVR, an additional wire will be needed for the common wire
connection from the included terminal block to the momentary switch. Refer to Table 4 for the recommended
wire part number and amount needed.
In the case of the DVR, the drivers for the alarm output and the shutdown circuit will remain connected
between 24V DC, pin 50 and the output contacts.
The logic for the control circuit has changed in the CDVR. The DVR supplies a signal unless a fault is
present. The CDVR signals only when the fault has occurred. Refer to the Illustration 4.
Operator Interface
In order to configure the parameters of the CDVR, a PC with the CDVR PC Software is required. Software
can be downloaded from the Service Information System (SIS).
Refer to the Specifications, Systems Operation, Testing and Adjusting, RENR7941-08, "Cat® Digital Voltage
Regulator ", for more thorough information on the CDVR software.
The CDVR requires a connection to a PC for configuring the settings for the generator. The PC is also used to
monitor the parameters for the generator and the faults from the generator.
A nine pin RS232 cable is required to communicate with the CDVR from a PC or a laptop computer.
The following CDVR settings will need to be configured in the CDVR: rated voltage, current, frequency, PT
Ratio, CT ratio, setpoints for VAR and PF, mode for load compensation, voltage adjustment band, setpoints
for soft start, setpoints for under frequency, protective relay functions and settings for PID. More parameters
may need to be configured for your specific application.
Note: If CAN datalink communication wires are installed, Caterpillar Electronic Technician can also be used
to adjust voltage regulator settings. Refer to the Specifications, Systems Operation, Testing and Adjusting,
RENR7941-08, "Cat® Digital Voltage Regulator ", for more information.