Documente Academic
Documente Profesional
Documente Cultură
© 1991
THE CHARTERED INSTITUTION OF
BUILDING SERVICES ENGINEERS
LONDON
ISBN 0 900953 47 0
This document is based upon the best knowledge available at the time of publication. However no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of these
recommendations con be accepted by the Chartered Institution of Building Services Engineers, the authors or others involved in its publication. In adopting these recommendations for use each adopter by so doing agrees
to accept full responsibility for any personal injury, death, loss, damage or delay arising out of or in connection with their use by or on behalf of such adopter irrespective of the cause or reason therefore and agrees to
defend, indemnify and hold harmless the Chartered Institution of Building Services Engineers, the authors and others involved in their publication from and against any and all liability arising out of or in connection with such
use as aforesaid and irrespective of any negligence on the port of those indemnified.
Draft Addendum to CIBSE Lighting Guide 5: The visual environment in lecture, teaching and conference
rooms
CIBSE Lighting Guide 5: The visual environment in lecture, teaching and conference rooms was published in
1991. However, the European standard for lighting of indoor workplaces, EN 12464-1, published as a British
Standard in January 2003, contains a schedule of illuminance and other recommendations related to lecture,
teaching and conference rooms. This schedule also appears in the Code for Lighting 2002.
The purpose of this Addendum is to clarify the relationship between these documents.
The lighting principles in LG5 are still valid. However, for projects covered by the Public Procurement
Directive, which includes PFI projects, European Standards must be followed if they exist. Therefore for such
projects the schedule in EN 12464-1 (and the Code for Lighting 2002) should be followed. Note that most
sections have a footnote permitting variation of the illuminance to suit circumstances. Other requirements of the
European Standard should also be followed. For aspects of lighting not covered by the European Standard the
guidance in LG5 should be followed.
For projects not covered by the Public Procurement Directive, compliance with European Standards is optional
and should normally be covered by the conditions of the contract.
Lighting Guide 5 has relevant recommendations on pages 3, 4, 6, 22, 23, 30 and 33. The relevant information in
BS EN 12464-1 is as follows:
JLD/14/11/2003
Foreword
Task group
A W S Tarrant Chairman
R I Bell
F Bentham
J A Lynes
A Mitchell
Publications Secretary
K J Butcher
Co-ordinating Editor
V P Rolfe
Contributors
R Anderson
L Bedocs
K Jones
I MacLean
D Poole
iii
Contents
1 Introduction
1.1 The classification of teaching and conference spaces 1
3 Teaching rooms 20
3.1 Lighting and visual needs 20
3.2 Rooms intended for formal instruction 21
3.3 Rooms intended for interactive learning 22
3.4 Rooms used for practical work 23
5 Committee rooms 28
6 Multi-purpose rooms 30
6.1 Lighting needs 30
6.2 General lighting 30
6.3 Suitable light sources 31
6.4 Suspension points and wiring 31
6.5 Controls 31
8 Emergency lighting 34
8.1 Escape route signs 35
8.2 Escape route illumination 35
8.3 Hazard areas 36
8.4 Operating conditions 36
8.5 Choice of systems 36
8.6 Classification of systems 37
8.7 Planning schemes 38
8.8 Planning sequence 38
8.9 Inspection and servicing 38
9 Maintenance 40
9.1 Lighting maintenance 40
9.2 Cleanliness and tidiness 40
References 51
Glossary 52
Index 55
1 Introduction
However, lighting problems do not only occur in the design of new buildings;
equally important questions are those of re-lighting or redecorating existing
rooms, and this Guide has been written with this in mind. Questions of safety
must be considered, and so a section on emergency lighting has been included.
Consideration has also been given to the lighting of spaces immediately
adjoining teaching rooms; and sections have been included on the vital
questions of the management and maintenance of such rooms as far as the
visual problems are involved.
Each chapter has a list of points that the lighting designer should check
before finalising any design. The check lists are to be used in this way:-
First, read the questions on the checklist, and compare your answers with
the checklist answers. (Y = Yes, N = No, ? = You need to consider this
item).
Second, if your answers agree with the checklist, then carry on; if they
disagree, then check the chapter for advice; if the answer given is ‘?’ then
you will need to understand what the effect of your answer will be. Make
sure that you understand the reasons behind the answers, and check the
chapter for more information.
1.1 The classification of For the purposes of this Guide, teaching and conference spaces are classified
teaching and in the way indicated below, and this terminology is used throughout.
conference spaces
1.1.1 lecture theatres Rooms used for the delivery of formal lectures with raked floors and/or
balconies or galleries and with fixed seating.
1
CIBSE LIGHTING GUIDE
1.1.2 lecture rooms Rooms used mainly for the delivery of formal lectures, with basically flat
floors and fixed seating. This category includes rooms with a raised step or
podium for the lecturer, and rooms with one or two raised steps towards the
rear of the seating.
1.1.3 Teaching rooms Rooms used mainly for class teaching purposes, with flat floors and no fixed
furniture except possibly chalkboards and projection screens. Such rooms
will usually have a seating capacity of less than 60.
1.1.4 Rooms used for Rooms used regularly for class teaching purposes, without large permanent
practical work pieces of apparatus set up. Such rooms will usually have a seating capacity
of less than 60. This category will include many teaching laboratories.
1.1.5 large conference Rooms used mainly for conferences and meetings at which people may
rooms address the audience from almost any point in the room. Such rooms will
usually have a capacity of more than 60.
1.1.6 Committee rooms Rooms used for meetings capable of seating up to roughly 30 persons.
1.1.7 Multi-purpose rooms Rooms used for a wide variety of purposes, such as school halls, assembly
rooms, function rooms, church halls.
1.1.8 Adjoining spaces Foyers, ante-rooms, lobbies and corridors immediately adjoining those spaces
listed above.
The choice between a lecture room (basically flat) and a lecture theatre
(raked) will be determined by the audience size. If it is less than 60 there is
little point in providing a raked room. If it is more than 80, raked seating is
essential, unless the lecturer is raised on a stage or podium.
2.1 Basic lighting and The lighting in a lecture space must reveal the lecturer to the audience and
visual needs the audience to the lecturer and also provide for the other visual tasks
involved. These include observing demonstrations, reading what is written
on the chalkboard, and the taking of notes. Note-taking has to continue when
slides, films or video presentations are used.
2.2.1 lighting the audience For the audience area the basic choice is between incandescent and fluor-
area escent lighting. Incandescent light is readily controllable in intensity and
direction, and is often preferred on aesthetic grounds. However it is inefficient
in terms of energy usage, doubly so in the case of lecture theatres, since the
heat which it introduces to the building has to be removed (at great expense)
by the air conditioning system. Fluorescent lamps of modern types, with
good colour rendering, are very much more energy-efficient and in those
theatres which are heavily used e.g. in schools and colleges, energy economics
will usually dictate their use. Other types of discharge lamp (e.g. high pressure
sodium) are not suitable, since if they inadvertently get switched off it may
be several minutes before they can be relit.
LECTURE, TEACHING AND CONFERENCE ROOMS
shows that when the ceiling is not a flat horizontal surface it may be possible
to make use of its shape to conceal the luminaires from the direct sight line
of the audience, provided that they do not become bad glare sources for the
lecturer. The glare index at any point of the audience area should not exceed
16.
Lamps used should be of colour rendering group 1B, i.e. their CIE general
colour rendering index (Ra) should be greater than 80. The common 'white'
3
CIBSE LIGHTING GUIDE
and 'warm white’ fluorescent tubes do not meet this requirement. An efficient
solution is offered by triphosphor fluorescent lamps.
2.2.2 Lighting the In small lecture theatres and any theatres that have an unbroken horizontal
demonstration area ceiling it is a good plan to carry the general lighting forward to serve the
whole area, and to add additional lighting as described below. This technique
does not emphasise any division between the demonstration and audience
areas. In very large lecture theatres, e.g. Figure 2.3, and especially those
where the ceiling height is reduced at the front it is advisable to use quite
separate lighting systems for the demonstration and audience areas. Since
the demonstration area lighting needs to be carefully directionally controlled,
only incandescent lighting is suitable.
higher, but not more than double those of the audience area. The rec-
ommended values are 500 lux for the demonstration area and 300 lux for
the audience area.
Lighting provided specifically for the lecturer to read notes when the theatre
is darkened for the purpose of slide projection needs careful attention. The
problems are that either light direct from the source, or light reflected from
the notes and desk, may fall on the screen and spoil the appearance of the
projection; it takes very little stray light of this kind to ruin the effect of a
good colour slide. The best solution is to incorporate carefully shielded low
4
LECTURE, TEACHING AND CONFERENCE ROOMS
power light sources in the lectern itself, whether it be of the pulpit variety,
shown in Figure 2.4, or of the movable table-top kind. The illuminance of
the notes should be kept as low as possible, 5 lux is quite enough. Linear
incandescent lamps can readily be used for this job, and their brightness can
be simply controlled with a dimmer mounted within the lectern itself.
Adjustable table lamps are not suitable for lighting the lecturer’s notes. The
beam angles are so wide that a great deal of light goes where it is not wanted,
and adds to the stray light. It is also very easy for such lamps to be positioned
wrongly, so that light shines directly onto the screen or onto the audience.
2.2.3 Sightlines The first requirements of a lecture space are that the audience shall see the
lecturer easily and that the lecturer shall see the audience easily.
Lecture theatres should not be raked too steeply, as shown in Figure 2.5, this
makes the audience feel uncomfortable and can present problems with slide
projection. The seating layout is important in raked theatres; if straight rows
are used the seats at the ends of the front rows offer a very oblique view.
Figure 2.5 Problems of a steeply raked theatre; if the screen is placed at A it will be very
uncomfortable for those in the front rows; if at B severe distortion may occur when slides/films are
projected.
5
CIBSE LIGHTING GUIDE
There can be little social contact between different members of the audience,
and this is disadvantageous from two points of view: (a) it discourages
audience participation and (b) it does not facilitate or encourage discussion
and questions after a lecture.
For these reasons, the curved rows in Figure 2.6 are to be preferred using a
fan shaped plan. This arrangement has the disadvantage that if the room is
only two-thirds filled all the audience may be in the back half. Figure 2.7
shows a good design compromise with at least half the length of the side
walls parallel so as to limit the length of rows at the back. If a projection
Figure 2.6 Fan shaped lecture theatre. room or booth is provided it must not jut out into the back rows, as this
creates an unhappy sense of division in the area. It is most important in any
lecture theatre that there is an adequate space in the demonstration area. In
practical terms, this means that there should be at least 3 m (10 feet) between
the front wall and the feet of people sitting in the front row. This not
only allows an adequate area for demonstration purposes and improves the
sightlines, but it gives the theatre a spacious quality as in Figure 2.3. If the
front wall is too close to the seats the theatre will look cramped, and have a
claustrophobic atmosphere.
6
LECTURE, TEACHING AND CONFERENCE ROOMS
2.3.2 Sightlines and glare Lecture rooms are usually rectangular in plan and experience shows that the
best seating plan is that with the lecturing area at one end of the room with
rows of seating parallel to the short dimension as shown in Figure 2.9.
Figures 2.10, 2.11, and 2.12 show typical layouts of lecture rooms. In the
case of a lecture room which is basically flat the sight lines may be greatly
Figure 2.11 The sightlines may be improved by raising the lecturer on a step.
Figure 2.12 Sightlines can be further improved by raising the rear seats on one or two steps.
Figure 2.13 Back row glare in a lecture room; luminaires at A and B are very close to the students
sightlines, and will cause intolerable glare.
improved by raising the latter half of the audience on one or two steps and
raising the lecturer on a step. Lecture rooms in general have a much lower
ceiling than lecture theatres, and in the absence of raked seating the sightlines
become critical. The lighting equipment should be arranged so that the
luminaires do not cause serious glare to the occupants of the rear row of
seats, as shown in Figure 2.13, or to lecturer as shown in Figure 2.14. When
7
CIBSE LIGHTING GUIDE
The glare index at any seat should be less than 16. It should also be
remembered that avoiding glare for the audience may create glare for the
lecturer; in particular, the lecturer must not be subjected to disability glare.
Figure 2.15 Glare shields placed behind luminaires to overcome the problem of back row glare.
2.4 Chalkboards and Figure 2.16 shows a chalkboard made difficult to read by veiling glare. This
their lighting is usually caused by the internal light sources or windows. It is therefore
essential that all chalkboards should have a matt surface; the term chalkboard
includes both the traditional blackboard used with chalk, or whiteboards used
with marker pens,
8
LECTURE, TEACHING AND CONFERENCE ROOMS
Figure 2.17 Ceiling mounted fluorescent luminaire suitable for chalkboard lighting.
9
CIBSE LIGHTING GUIDE
2.5 Provision of daylight Almost all lecture presentations require controlled lighting at some stage.
For that reason, lecture theatres and rooms are often built with no access to
daylight. Equally, people do not like to feel shut in, especially when lectures
are given during daylight hours, and there are many who have a preference
for working under natural light. In rooms the size of lecture theatres the
provision of natural light in sufficient quantities for working purposes requires
very large areas of glazing. That is not only expensive from the point of view
of heat loss, but it is difficult to achieve a good blackout, and unless the
windows are north facing there may be severe problems with solar heat gain
in summer.
The only way in which an adequate blackout can be achieved in such rooms
is by the use of the completely opaque blinds, running in grooves at the sides
to provide a complete light trap. An example of this type of blind is shown
in Figure 2.19. Curtains or venetian blinds are not adequate. Blinds should
be of light colour on the inside so as not to present a large black area when
down, and in view of the area of window involved and the need for frequent
opening and closing they should be motor operated. Blinds should also be of
a light colour on the outside, to prevent excessive solar heat gain.
Figure 2.19 Blind with deep grooves suitable for lecture room use.
10
LECTURE, TEACHING AND CONFERENCE ROOMS
It is often felt that windows in lecture theatres and rooms have to be provided
to give the occupants some view of the outside world and to overcome feelings
of claustrophobia, i.e. to provide some visual escape rather than to provide
lighting. Figure 2.20 shows that very much smaller areas of window can be
used, and the problems associated with them much reduced. However, the
need for a perfect blackout remains and again groove enclosed blinds are
needed, though they may be hand-operated.
Figure 2.20 Windows of limited area in a lecture room, provided to offer ‘visual escape’ to the
occupants rather than to admit daylight.
Windows should not be provided in either the front wall or back wall of a
lecture theatre or lecture room. The former would produce intolerable glare
to the audience and the latter would cause serious veiling reflections on the
chalkboard.
From the point of view of lighting, it is much better for lecture theatres and
rooms to be windowless. Since the occupants rarely have to remain in them
for more than an hour without a break, problems of claustrophobia do not
arise, although they may well do so in small teaching rooms. Some newer
institutions make extensive use of windowless lecture rooms with entire
success. Windowless lecture theatres and rooms require forced ventilation
which may in turn lead to noise problems, but it should be pointed out that
large theatres with extensive glazing have an equal requirement for forced
ventilation.
Light traps (e.g. two sets of doors or other effective means for excluding
daylight) should be provided in all lecture theatres and rooms to prevent
daylight getting in when the theatre is darkened for the presentation of colour
slides. This is particularly so in the case of entrances at the rear of the theatre,
which when opened suddenly by a latecomer may allow full daylight to fall
on the projection screen. These light traps should also function as sound
traps.
2.7 D e c o r a t i o n a n d It is the decoration and furnishings within a lecture theatre or room which,
furnishings in combination with the lighting determine its appearance and contribute to
that indefinable quality that we usually call atmosphere or character.
12
Figure 2.22 Suitable colours for decoration and furnishings. The colours recommended are specified by their British Standard Colour Numbers (given
below each sample) according to BS 4800 (1984). Owing to the difficulties of colour reproduction, these samples may not accurately match the BS
colours. Designers and specifiers should quote the BS numbers and not attempt to match these samples visually.
LECTURE, TEACHING AND CONFERENCE ROOMS
depend on the style of lighting. The colour should always be light but if
luminaires are recessed and no light is reflected off the ceiling it will look
grey by comparison. Walls should be of a different colour from the ceiling
in order to define the boundaries of the interior space and avoid a feeling of
claustrophobia.
The co-ordination of the colour and texture of finishes with the lighting is
all-important. The colour rendering properties of the lighting will greatly
affect the choice of colours and in some cases daylight will have to be
considered also. When replacement lamps are fitted they should always be
the same as the originals, unless a positive decision is made to re-lamp the
whole theatre with lamps of a more modern type. Dark colours in decoration
and furnishings should be avoided and matt or semi-matt surfaces are
desirable as high gloss areas will cause specular reflection and be distracting.
Cold blues, dark greys and dull yellows must be avoided, and also colours
which are very clear and strong in blue and yellow; they are particularly
distorted by some forms of fluorescent lighting.
2.8 Switches, dimmers In any lecture space the lighting controls need to be as simple and comprehen-
and controls sible as possible – lecturers are more concerned with their subject matter
than light switches. In the main, the only lighting settings needed in a lecture
theatre are:
Abrupt changes in the lighting are disturbing to the audience, and for that
reason dimmers which enable gradual changes to be made are preferable to
plain switches, Manually operated dimmers are not satisfactory as it is difficult
to get a smooth transaction from one lighting state to another.
A good system is that in which the only controls are three push buttons,
corresponding to the states (a), (b), (c) above. On pushing the appropriate
buttons the dimmers move accordingly. In such installations the time taken
to go from full-on (a) to full-off (c) should not be too long; about four seconds
is sufficient. The very slow dimming speeds used in the professional cinema
and theatre (usually about twenty seconds from full-on to full-off) are
inappropriate in lecture theatres; it is frustrating to audience and lecturer
alike to have to keep waiting while the lights go down before a slide can be
shown. A further advantage of the pre-set push button dimming system is
that several sets of out-station controls may be used and this may save the
lecturer a great deal of walking about; an out-station control should also be
provided for the lecture attendant e.g. in the projection room.
13
CIBSE LIGHTING GUIDE
Figure 2.23 The small incandescent lamps in this theatre are used alone as ‘pilots’ when slides are
shown.
All lecture theatres should be arranged for one person operation as circum-
stances inevitably arise where a lecturer has to speak without the services of
an attendant.
14
LECTURE, TEACHING AND CONFERENCE ROOMS
2.9 Audio-visual aids It is vital that the various pieces of audio-visual equipment do not obstruct
considerations the audience’s view of the lecturer, the projection screen, and the chalkboard,
Overhead projectors and television monitors are particularly apt to do this.
One solution is to mount the two last mentioned items on wheeled trollies,
so that they can easily be moved out of the way (or out of the room) when
not wanted. A common problem is that a single screen will not be suitable
for both slide and overhead projector (OHP) use. To avoid the keystone effect
shown in Figure 2.25, the screen needs to be angled in different directions.
15
CIBSE LIGHTING GUIDE
Figure 2.26 shows movable screens but these are both costly and bulky, and
can cause unwanted shadows on the chalkboard as shown in Figure 2.27.
The simplest solution is to use two separate screens. Many lecturers like to
use both systems at the same time, and count upon being able to do so.
Figure 2.26 Movable screens in a large lecture theatre: that on the left is set for an overhead
projector, whilst that on the right is set for slide projection from the projection room.
2.10 Access and In both lecture theatres and rooms the question of access is important. Ideally
movement the normal means of access for members of the audience should be through
doors at the back, with a separate entrance for the lecturer at the front. Rear
16
LECTURE, TEACHING AND CONFERENCE ROOMS
All lecture theatres and lecture rooms sooner or later become used for
purposes other than that to which they were originally dedicated. Conse-
quently all items in the demonstration area should be movable and removable.
Lecterns are obtainable which are readily movable, even those embodying
controls for the lighting and projectors. Figure 2.28 shows a removable
lectern. Massive permanent benches are to be avoided; they form an effective
barrier between lecturer and audience, and demonstrations may equally well
be mounted on a set of tables which can be carried out when not wanted.
Experience shows that when demonstrations are mounted, services other
than electricity are rarely, if ever, called for and there is little point in
installing a fixed bench simply to provide terminal points for water, gas, and
other outlets. If such services are needed, they are much better installed in
wall cupboards where they can be kept both locked and out of sight until
they are wanted.
Figure 2.28 Lectern embodying controls for lighting and projection which is movable and remov-
able
In some cases, local authority bye-laws require that all exits to a lecture
theatre/room be marked with permanently illuminated exit signs. Light from
such signs falling on a projection screen can ruin the effect of colour slides
or demonstrations. They should therefore be aligned so as to be visible to
the audience, but not to throw light on the projection screen.
2.11 Use for theatrical Possibly because they resemble legitimate theatres in shape and possibly
presentations because they often constitute the largest auditorium in a particular institution,
lecture theatres are sometimes chosen as the venue for theatrical present-
ations. Such presentations can be greatly helped by the provision of further
special facilities, which are set out in Appendix 3. However some of these
are expensive, and consideration will have to be given to the extent to which
17
CIBSE LIGHTING GUIDE
a particular lecture theatre may be used in this way. The general experience
is that the larger the lecture theatre, the more likely it is to be used for
theatrical purposes.
1) Compare your answers with the checklist answers. (Y = Yes, N = No, ? = You need to consider
this item)
2) If your answers agree with the checklist, then carry on; if they disagree, then check the section
for advice; if the answer given is '?' then you will need to understand what the effect of your answer
will be. Make sure that you understand the reasons behind the answers, and check the section for
more information.
Can the audience see the lecturer easily? Y Is the position and angling of luminaires in the
Can the lecturer see the audience easily? Y demonstration area correct (about 45° to the
vertical)? Y
Will it be a lecture room or a lecture theatre? ?
Are luminaires arranged to produce general
Is the audience lighting incandescent or fluor- illumination over the demonstration area rather
escent? ? than angled at definite points? Y
Is the audience lighting readily controllable? Y The lecturer must be able to read notes when
Are the luminaires positioned not to create glare the theatre is darkened for the purpose of slide
problems either for the audience or the speaker? projection. Is this provided by the room lighting,
Y by dedicated lighting, or by carefully shielded
If the ceiling is not a flat horizontal surface, can low-power light sources provided in the lectern
its shape be used to conceal the luminaires from itself (preferred)? ?
the direct sightline of the audience without In this situation, does light (direct from the
causing glare for the lecturer? Y source, or reflected from notes or desk) fall
Are totally recessed luminaires of the down- on the screen and spoil the appearance of the
lighter type used? N projection? N
Is the modelling of human features good enough In this situation, is the luminance of the notes
for the lecturer to see clearly the reactions of low and can it be controlled easily? Y
the audience? Y In a lecture room does the general lighting
Do any surface-mounted luminaires produce a produce an illuminance above 200 lux at desk
distracting halo on the ceiling? N level in the audience area? Y
Do luminaires mounted close to the walls In a lecture room, is the lighting in the audience
produce a scalloped effect on the wall or any area reasonably uniform? Y
other patterns which can be distracting? N In a lecture room, if fixed seats are installed
Where there is note taking, does the lighting right up to the walls is the illuminance at desk
create multiple shadows of the pen/pencil point level at the wall not less than 70% of the average
on the paper? N illuminance? Y n.b. if there is an aisle next to
the wall this does not apply.
Are luminaires of the semi-recessed type to
prevent the ceiling appearing too dark? Y Can a general illuminance of 15-30 lux (on the
desks) be set so that the audience may take notes
Are fluorescent luminaires mounted with their
whilst slides or overhead projector trans-
long axis parallel to the rows of seats to prevent
parencies are shown? Y
note-taking shadows? Y
Are chalkboards lighted by suitably designed
Is the average illuminance on the working plane
ceiling mounted luminaires, carefully shielded
(normally 0.85 m above the floor) above 200 lux
so that they do not cause glare to the audience?
and adjustable? Y
Y
Do the lamps have adequate colour rendering
Is the room windowless? Y
properties (CIE Class lB)? Y
If windows are provided, has adequate blackout
Is the lighting system designed so that it can be
been achieved by the use of completely opaque
properly maintained? Y
blinds, running in grooves at the sides to provide
Have arrangements been made to ensure that a complete light trap? Y
maintenance is carried out? Y
Are the blinds of light colour on the inside and
In small lecture theatres does the general motor or handle operated? Y
lighting extend forward to serve the whole area?
Are small windows provided to give the occu-
Y
pants some view of the outside world and to
In large lecture theatres is there a separate overcome feelings of claustrophobia? Y
lighting system for the demonstration area? Y Is the ventilation adequate? Y
Is the demonstration area lighting incandescent Is noise from the ventilation system a problem?
with directional control? Y Y
Are demonstration area luminaires recessed or Are light traps provided to prevent the ingress
otherwise concealed from the view of the audi- of daylight when the theatre is darkened for
ence? Y projection (particularly in the case of entrances
18
LECTURE, TEACHING AND CONFERENCE ROOMS
1) Compare your answers with the checklist answers. (Y = Yes, N = No, ? = You need to consider
this item)
2) If your answers agree with the checklist, then carry on; if they disagree, then check the section
for advice; if the answer given is '?' then you will need to understand what the effect of your answer
will be. Make sure that you understand the reasons behind the answers, and check the section for
more information.
at the rear of the theatre which can illuminate Are the lighting controls as simple and compre-
the screen)? Y hensible as possible? Y
Do the light traps also function as sound traps? Have the following 3 conditions been provided
Y and can they be achieved easily? Y
Will doors close quickly and silently? Y
[Lecture room only] Could sight lines be
(a) full normal lighting
improved by raising the latter half of the audi-
ence on one or two steps and/or raising the (b) audience area lighting reduced to a low
level and demonstration area lighting off;
lecturer on a step? Y
for the purpose of slide projection but
[Lecture room only] Is the lecturing area at one allowing enough light for the audience to
end of the room with rows of seating parallel to take notes
the short dimension? Y (c) all lighting off; for the projection of tone
[Lecture theatre only] Is the rake too steep, slides, colour slides, and for the purposes
making the audience feel uncomfortable or of visual demonstrations
causing problems with slide projection? N
[Lecture theatre only] Is the seating plan fan-
shaped with curved rows and limited row lengths Have abrupt changes between lighting condit-
at the rear? Y ions been avoided? Y
If a projection room or booth is provided, does Are dimmers with automatic fade controls used,
it jut out into the back rows? N preferably with three push buttons, corre-
sponding to the three control conditions (a), (b)
Is there anything which competes with the lec-
and (c) above? Y
turer for attention? N
Are the transition times (fade up and down)
Do the lecturer’s desk, chalkboard and screen
acceptable (about four seconds)? Y
obstruct the view of each other? N
Has a suitable number of out-station controls
If an overhead projector is used, does it obstruct
been used to provide flexibility and ease of
either the audience’s view of the lecturer or the
use, and has one been provided for the lecture
lecturer’s view of the audience; does it obstruct
attendant e.g. in the projection room? Y
the projection path and cause shadows? N
If dimmers are not used because of cost, does
If an overhead projector is used, is it mounted
the lecture room seat less than 120, and is the
on a trolley so that they can be wheeled out of control system flexible and easy to use. Y
the way when not required? N
If dimmable fluorescent lighting is required, is
Is the audience’s view free of visual clutter? Y
it correctly designed, installed and maintained
Is the atmosphere too strong nor too bland? N to ensure satisfactory dimming from full bright-
Have darker colours been used on the side walls ness to a level of about 15% of full brightness.
to aid concentration on the focal point? Y Y
Is the ceiling finish light and off-white? Y Can the type of lamps selected be dimmed with
Are the luminaires recessed? ? the circuit proposed? Y
Are the ceilings and walls painted in the same Does the fluorescent lighting use high fre-
colour all-over? N quency control gear (20 - 40 kHz) to minimise
acoustic noise and provide simple, reliable dim-
Have the colour rendering properties of the ming? Y
lighting and daylight been allowed for in the
choice of surface colours? N If fluorescent lighting is switched rather than
dimmed, will it start cleanly without noise or
If replacement lamps are fitted, are they the flickering? Y
same as the originals or has a positive decision
been made to re-lamp the whole theatre? Y If full dimming of the fluorescent lighting is not
provided, then are fluorescent and incandescent
lighting mixed with the latter on dimmer control
Has full advantage been taken of modern lamp for slide projection? Y
types? Y
Is the dimming equipment and associated wiring
Have dark colours in decoration and furnishings designed to keep radio frequency emission to
been avoided? Y the minimum and is other electronic apparatus
Have matt or semi-matt surfaces been used carefully screened to prevent interference being
throughout? Y picked up? Y
Have colour contrasts of a modest nature been Is the lecture theatre arranged so that it can be
used? Y used for one person operation? Y
Has adequate consideration been given to the Are switches or controls positioned so that they
type of carpet (or other flooring) used and the become inaccessible when the projection screen
patterns of wear that will exist? Y is in use? N
19
CIBSE LIGHTING GUIDE
3 Teaching rooms
3 . 1 Lighting and visual The activities which take place in teaching rooms fall into three categories,
needs which require different styles of lighting, and these are discussed separately
in this chapter. One category covers the traditional type of teaching where
students sitting at prescribed places are addressed by a teacher speaking from
another prescribed place - a process described by Joad as “.... the transfer
of information from the notebook of the teacher to the notes of the student
without passing through the minds of either.” This style of teaching is
referred to here as formal instruction.
The second category includes that style of teaching which takes the form of
a group discussion, where teachers and students may sit anywhere, a process
sometimes irreverently termed the brainstorming session or circle dance.
This style of teaching is referred to here as interactive learning.
The third category is that which covers the teaching of practical work such
as metalwork, craft design and technology.
In the case of rooms intended for formal instruction the lighting needs are
similar to those of lecture rooms, except that the students must be able to
read from text books at their desks. The students may have to work at the
same point in the room for several hours at a stretch.
20
LECTURE, TEACHING AND CONFERENCE ROOMS
Rooms used for practical work - laboratories, workshops, art rooms, craft
rooms and the like, involve visual needs and tasks which are the same as
those found in industry; this is particularly so if the room contains much
fixed equipment e.g. a workshop with lathes and other machine tools.
The reader should consult the Code for Interior Lighting(1) for advice on
laboratories, workshops and sewing rooms. However many rooms used for
practical work have to serve a wide variety of purposes and the visual needs
of these are discussed in Section 3.4.
3.2 Rooms intended for In a room planned specifically for ‘chalk and talk’ the role of the windows
formal instruction is as much to provide visual contact with the outside world as to provide
working daylight with a specific daylight factor. Table 3.1 shows the Depart-
ment of Education and Science requirements for windows in the UK.
Table 3.1 Department of Education and Science guidelines(3)
21
CIBSE LIGHTING GUIDE
3.2.1 Electric lighting The electric lighting has three principal roles; to light the desks, the teacher,
and the chalkboard.
3.2.1.1 Desks For secondary schools, colleges and buildings used extensively after dark the
DES Guidelines(3) recommend a general illuminance of at least 300 lux. This
is best achieved by tubular fluorescent luminaires chosen to limit the glare
index to 16. The contrast rendering factor (CRF), which should be 0.8, should
be maximised by positioning of the luminaires. The classical precept ‘light
over the left shoulder’ meets both these requirements, at least for right-
handed students.
3.2.1.2 Teaching space Lighting for the teacher’s space should always be switched separately from
the rest of the room. It may be worth considering a different type of luminaire
for this area. The teacher’s face should be sympathetically revealed. A vector/
scalar ratio between 1.5 and 1.8 would be suitable. The vector direction
should be such as to facilitate lip-reading. The background luminance should
preferably be slightly lower than the luminance of the teacher’s face. This
may be difficult in the case of teachers with dark skin tones, but in that case
a light background would be particularly inappropriate. Light switches should
be handy to the teacher and not local to each luminaire.
3.2.1.3 Chalkboard Chalkboards need not be black, but should have a Munsell value not exceeding
4 (or reflectance not exceeding 0.12): DES Building Bulletin No. 9(2) illustrates
a range of suitable surface colours. Shiny finishes are unsuitable for chalk-
boards, as shown in Figure 2.16. The position of a chalkboard luminaire is
more important than its optical design. Figure 2.18 illustrates the principles
involved. The luminaire should be as far from the chalkboard as possible
whilst remaining above the dashed line. A luminaire close to the board cannot
illuminate the foot of the board satisfactorily, see also Section 2.4.
3.2.2 Decoration The wall behind the teacher should be as simple and uncluttered as possible
and preferably be of a low chroma colour, so that the teacher may be easily
seen. If there is a very light wall behind the teacher, the result can be
dazzling, and so be tiring to the students. This does not mean that all surfaces
should be sombre or dark; on the contrary a desirable freshness of atmosphere
can be achieved by using a variety of colours. As a general rule it is comfortable
to have the window walls a light colour, though not white. A light off-white
can be used for the ceiling, rather than dead white, particularly if the room
has a cornice to divide the ceiling from the walls. If wallpaper is used, it
should either be plain or have only a very restrained pattern.
22
CIBSE LIGHTING GUIDE
The DES heat wave temperatures can be checked using the admittance
procedure(4). See also the BRE Environmental Design Manual(5). The DES
Guidelines(3) recommend that the resultant temperature should not exceed
27°C during the school year. This can normally be achieved with cross-
ventilation and a simple curtain drawn across sunlit windows. If cross-
ventilation is impossible the curtains may need a reflective lining facing
outwards; the admittance calculation will show if more radical design modifi-
cations are needed in a given instance, to reduce the resultant temperature.
3.3.2 Electric lighting The electric lighting in an informal teaching room should be gentle and
unassertive. The DES Guidelines(3) require a minimum illuminance of 150
lux at any point on the working plane.
3.3.3 Decoration By its nature, interactive learning needs a relaxed, informal, and quiet
environment. All furniture should be movable; wall-to-wall carpeting and
preferably, curtains should be provided.
3.4 Rooms used for Reference has been made in Section 3.1 above to the visual needs in rooms
practical work used for practical work. In recent years there have been great changes in the
way traditional subjects have been taught. Teaching spaces are increasingly
becoming more flexible in use with functions ranging from industrial to
office environments. The computer is no longer confined to special rooms,
but computer terminals or personal computers may be used almost anywhere.
If computers with visual display units are to be frequently used then Lighting
Guide LG3: Areas for visual display terminals(6) should be consulted. It is
particularly important to avoid specular reflections of light sources in VDU
screens.
23
CIBSE LIGHTING GUIDE
the lamps should be of colour rendering group 1B. Visual tasks such as
sewing will require temporary local lighting.
In all cases the teacher occupies no fixed position, but spends time at the
benches, machines and tables as needed. The main requirement is that good
supervision is necessary. In most rooms there will be a teaching wall from
where more formal instruction will be carried out with the students sitting
or standing by their machines, benches or tables. Detailed instruction, formal
or informal will be carried out in another room, classroom, seminar room or
small group room, and the design of these spaces should follow the advice
in the previous chapter.
24
LECTURE, TEACHING AND CONFERENCE ROOMS
4.1 Basic lighting and The basic visual needs in a large conference room are that all members of
visual needs the audience can see the chairman and central officers clearly, and that all
persons present should be able to see each other reasonably well in order
that a proper dialogue may take place. Many presentations in conference
rooms, e.g. the reading of scientific papers, are tantamount to formal lectures,
and the lighting needs are similar to those of lecture theatres. However
conference rooms are also often used as cinemas or theatres and the lighting
must be capable of meeting those purposes also.
25
CIBSE LIGHTING GUIDE
It must also be flexible and controllable from a single point, must be absolutely
silent and produce no thermal discomfort. Careful co-ordination of the
lighting design with the interior decoration and with the heating and
ventilating system is essential. Absolute blackout facilities will be needed,
and if the room is to be used for lecture demonstrations adequate power
supplies should be available.
Large conference rooms have a good deal in common with large lecture
theatres, and much of the information in Sections 2, 7, 9, and 10 applies to
them. Conference rooms usually have a clearly defined area where the major
part of the action takes place, corresponding to the demonstration area of a
lecture theatre, and a clearly defined audience area. But the activities in a
conference room differ from those in a lecture theatre in these ways:
(a) The audience may be present for long periods, often on several suc-
cessive days.
(b) The proceedings although of a formal nature involve interaction
between members of the audience and they must be able to see each
other clearly.
(c) Conference participants must be able to move easily between the
demonstration area and the audience area.
(d) Simultaneous interpretation facilities may be required.
Item (a) above requires that participants should be able to move in and out
of the room whilst proceedings are in progress with the minimum of
disturbance, and the seating should be arranged accordingly, with a greater
ratio of gangway space to seating space than is the case in lecture theatres.
It is important that participants can both get in and out without disturbing
the projector beam if one is in use.
In the UK it has always been the custom that those who contribute to a
discussion should do so from their seats, but in many countries of the world
this is not so. A person wishing to speak must seek the chairman’s approval
and then get up from his seat and go to a central podium to speak.
The points made in Section 2.2 relating to the layout of the seating apply
equally here. Cloakrooms, toilets, refreshment facilities and spaces where
participants may relax should be provided immediately adjacent to large
conference rooms.
4.2 Lighting systems The lighting requirements of the demonstration area of a large conference
and controls room will be similar to those of a lecture theatre, but all lamps should be
controlled by dimmer. Large conference rooms are likely to be used for
theatrical performances; consequently provision should be made for easily
rigging additional lighting equipment. The particular requirement is that
appropriate wiring is provided in the shape of numerous circuits terminating
in socket outlets at the points where additional spotlights are likely to be
wanted. These circuits may be controlled from a stage lighting control system
operated from the projection room; in a very large conference room the
lighting is likely to be so complex that a system of this kind, under permanent
control of an attendant is advisable in any case. If it is known that a large
conference room will be used for theatrical presentations further special
facilities may be advisable. These are described in Appendix 3.
The lighting of the audience area, and the appearance of the whole are
crucial in a conference room. The audience must not only be able to
see each other clearly, but should not appear grotesque. For that reason
downlighters are not recommended; they produce shadows under the eyes
26
LECTURE, TEACHING AND CONFERENCE ROOMS
which are not acceptable, this is shown in Figure 4.1. If the ceiling is plain
white, then recessed or cornice lighting may be used, provided that there is
sufficient direct lighting in the demonstration area to provide a modest degree
of ‘sparkle’. If this is not the case, it is worthwhile introducing a few small
incandescent luminaires for this purpose. The furnishing and decoration
should not be too dark, as light reflected from the floor and furniture will
significantly improve the modelling of participants’ faces. The points made
about visual clutter in Section 2 and 10 apply equally to conference rooms.
4 . 3 Simultaneous Strict specifications are laid down for the lighting of interpretation booths.
interpretation See IS0 Standard 2603(7). Care must be taken that light from them does not
booths spill onto the projection screen.
27
CIBSE LIGHTING GUIDE
5 Committee rooms
5.1 Visual and lighting The basic functions of the lighting, be it daylight or artificial are:
needs • to enable the committee members to see each other clearly and without
glare.
• to enable members to read their papers and make notes.
• to enable committee members to see wall mounted displays.
5.2 Daylight Committee rooms should always have some natural lighting; windowless
rooms are unacceptable for committee purposes. The essential problem of
natural lighting in a side-lit committee room lies in the fact that occupants
on different sides of a table are likely to be exposed to different forms of
inconvenience. Those facing a window may suffer glare, and see their
colleagues opposite with features in shadow silhouetted against a bright sky.
Those with their backs to a window may cast a shadow on their own papers.
One possible approach is to ensure that the chairman faces the window and
can control both the curtains and the electric lighting. This arrangement
28
LECTURE, TEACHING AND CONFERENCE ROOMS
ensures that the chairman’s face is clearly revealed, that there is no visual
discomfort, and that the faces of other participants can be seen comfortably.
If this can be achieved, it is unlikely that others will have difficulty in seeing
one or another.
Pinboards and flipcharts should not be seen next to a window: disability glare
will make them harder to read even when discomfort glare is quite acceptable.
They should also not be placed where they may reflect a shiny image of the
window. The prescription above, with the chairman facing the window, takes
care of these problems too.
5.3 Electric lighting The geometry of lighting should correspond to the geometry of the conference
table, defining it as the focus of activity within the room. This does not
necessarily mean that the table should be the brightest surface; downlights
are particularly unsuitable as they cast harsh shadows, generate shiny reflec-
tions in a polished table-top and tend to leave walls and ceilings in relative
darkness. The illuminance on the table should be about 300 lux, and the
glare index at any point of the room should be below 16.
The light distribution should produce a vector/scalar ratio within the limits
recommended in the Code for Interior Lighting(1).
Supplementary display lighting will be required for wall-mounted charts etc.
This is governed by the same geometrical constraints as chalkboard lighting,
see Section 2.4. The display lighting should preferably be dimmer-controlled.
Careful design of a committee room will remove the need for easels and
portable projection screens, and for ad-hoc arrangements of slide projectors,
overhead projectors and blackout facilities.
5.4 Surface finishes The background luminance should ideally be slightly lower than the lumin-
ance of the occupants’ faces.
Dark walls are more suitable for formal boardrooms. Very light coloured
walls can give a clinical feel. A few small pictures or ornaments can do much
to improve a committee room, but large and complicated features which may
distract the attention should be avoided. The floor carpet should not be very
dark.
Table 5.1 Checklist — Committee rooms
29
CIBSE LIGHTING GUIDE
6 Multi-purpose rooms
6.1 Visual and lighting The lighting designer should be involved with the architect and interior
needs designer from the start of the planning process. In attempting to design a
suitable installation for a multi-purpose room the first requirement is for the
designer, in consultation with the client, to draw up a list of the purposes
envisaged for the room and an order of priorities of use. The prime lighting
needs in terms of illuminances and the controls needed for each separate
activity can thus be tabulated and if any common pattern exists it will be
evident; in that case the lighting can be designed accordingly. However, in
many cases no common pattern will emerge and the designer will have to
produce a compromise design.
There are a few basic points, discussed below, which should be considered
at the start of the design process. These are excluding daylight, stage lighting,
and accommodating large chandeliers.
6.1.1 Excluding daylight Daylight should preferably be excluded. Multi-purpose rooms require lighting
that is flexible and controllable to a high degree and daylight is not so. If
windows, rooflights or skylights are to be provided they should be fitted with
light tight blackout blinds of the type described for lecture theatres in Section
2.5. This is particularly so in the case of skylights.
6.1.2 Stage lighting If the room has a definable stage area, then the lighting for it should be
regarded as stage lighting and designed accordingly.
6.1.3 Chandeliers If large chandeliers are to be used, they should be thought of as decorative
features rather than the main source of illumination. They can very easily
obstruct both sightlines and the beams of spotlights and their use is not
recommended. If they are used they should be dimmer controlled along with
the rest of the installation.
6.2 General lighting The function of the general lighting in a multi-purpose room is to provide
an overall uniform illuminance of acceptable colour rendering which is free
from glare, and which may be dimmed. The design survey mentioned above
will indicate the illuminance needed at working plane height e.g. 0.85 m
above the floor. If no such survey can be made the designer should aim for
a value of about 150 lux. If it is known that the room will be used regularly
for examinations then the provision should be for 300 lux. The colour
rendering should be of group 1B(1).
With the variety of activities that may take place, sightlines may be anywhere,
and it is important to avoid glare. This point is very well met if the general
lighting is indirect. If a direct system has to be used the luminaires should
preferably be recessed. If surface mounted fittings are used they should have
opaque or diffusing side surfaces, and in no circumstances should bare lamps
be visible. Suspended luminaires should not be used to provide general
lighting. Care should be taken in avoiding glare not to overdo it; recessed
downlighters in particular give no glare at all but produce both a modelling
effect on faces which is quite the reverse of what is wanted for a social
occasion and a gloomy atmosphere. The illuminance produced by the general
lighting should have a uniformity ratio of a least 0.5 at working plane height,
and if the ceiling is low this may be difficult to achieve with downlighters.
30
LECTURE, TEACHING AND CONFERENCE ROOMS
6.3 Suitable light The main lighting may be either incandescent or fluorescent; in a few cases
sources high pressure sodium may be used. Incandescent lighting is extremely flexible
and controllable, though is inefficient in terms of energy usage. Although its
colour rendering is not of the best it is often thought of as the appropriate
lighting for social functions. Energy efficiency is not of prime importance
unless certain purposes require the use of the room for extended periods, but
the heat which it generates may have to be removed (at some expense) by
the air-conditioning system.
Fluorescent lighting may readily be dimmed but by the nature of the source
is less flexible. The term fluorescent lighting includes compact source
fluorescent lamps which can be used in relatively small luminaires. Fluor-
escent lamps can be used to advantage in an indirect lighting system,
especially where the tubes can be concealed in cornices, coves, or in the
structure of a ribbed ceiling.
High pressure sodium lighting has a very long warm up time and is thus of
restricted value in multi-purpose rooms. However, for some functions, e.g.
exhibitions, it may be useful, especially if used to provide indirect lighting.
If used for direct lighting the mounting height should be at least 3.5 m.
6.4 Suspension points It may be necessary to mount temporary spotlights for many functions and
and wiring appropriate suspension points should be provided; a space frame ceiling is
ideal for this purpose. If the room has a definable stage area then provision
should be made for mounting front-of-house spotlights in the shape of wall
brackets or spot bars mounted below the ceiling and in smaller rooms that
may suffice for all spotlight mounting. Since wall lighting is often needed
for exhibition and display purposes a ceiling track round the entire room
1.2 m in from the wall is a wise provision if ceiling height is less than 4 m.
Where provision is made for spotlight mounting for stage purposes, appro-
priate wiring runs back to the control point/switchboard must be provided
with separate circuits for each outlet point. Outlet points of this kind are
normally out of reach from floor level and should be provided with sockets
to BS 546 (9) (15A round pin type).
The wiring should also provide a plentiful number of normal 13A outlet
sockets at wainscot level all round the room. These are necessary for exhibition
purposes. Flush fitting floor traps should also be provided where projectors
are likely to be used, and these should contain not only power outlets but
wiring and sockets of appropriate type for projector remote control systems.
6.5 Controls Multi-purpose rooms will generally be regarded as places of public resort and
thus be subject to local bye-laws. These often require that the lighting controls
be placed in a separate room not accessible to the public, which is awkward
if the room is used for, say, a lecture involving slides and demonstrations.
All of the lighting controls should be grouped together so that one individual
can have charge of all of them; the controls are best placed in an adjacent
room with a window into the multi-purpose room. If the room is used as a
cinema the lighting controls can well be placed in the projection room,
provided that a full-depth window is installed and not just projector loopholes.
7.1 Lighting objectives The functions of the lighting in spaces adjoining teaching and conference
spaces are:
• To provide for the entrance and exit of the users, bearing in mind that
many people may need to get in and out in a short time.
• To put users, as they approach, in an appropriate frame of mind for the
activity in which they are about to take part.
• In some cases, especially ante-rooms, to provide a social atmosphere
(such spaces are often used as tea and coffee spaces).
• In some cases, to indicate to visitors the route they should take to reach
their destination, e.g. the lecture theatre in a museum. In other cases,
e.g. a suite of teaching rooms in a college, this may not be appropriate.
32
LECTURE, TEACHING AND CONFERENCE ROOMS
7.2 Circulation If the lighting is to provide guidance for the visitor from entrance to
destination, that may be done in two ways. Firstly the geometry of the
luminaires can imply a direction. Secondly by the phototropic effect; people
are attracted to bright lights. A lighting designer can exploit this tendency
by leading visitors towards brightly-lit areas.
Lighting in corridors must provide for safe movement, and should provide
an illuminance of at least 100 lux at floor level, with a glare index of below
19. There must be appropriate lighting for hazards to be visible. A particular
hazard in corridors with shiny floors is that of water on the floor which may
have got there by spillage, roof leakage, or from melted snow carried in on
shoes.
The rule for staircase illumination is to light the treads and not the risers.
Figure 7.1 shows luminaires at B and C reduce the contrast between treads
and risers. In addition they can cause accidents by distracting attention. The
luminaire at A is well placed, illuminating each tread by putting the risers
Figure 7.1 Staircase lighting. Position A is
into shadow. On a long staircase it might be supplemented by a wall-mounted
recommended; B and C are to be avoided; and luminaire at D at a height which permits easy access for re-lamping. In the
D can be used for wall-mounted luminaires on latter respect too position B should be avoided; steps or ladders are hazardous
very long staircases. over a staircase.
7.3 Waiting areas and Waiting areas and lobbies immediately adjoining teaching or conference
lobbies spaces should be kept tidy and free of visual clutter (see Section 10.1). As
they may well be used as social or tea and coffee areas, the illuminance
should be about 200 lux and lamps of colour rendering index group 1B
should be used. Unless the height is greater than 4 m above the floor,
downlighters should not be used.
Because activities of this kind may well go on at the same time as lectures
or conference proceedings, there should be two sets of doors at the entrance
to the teaching or conference space, to act as both light and sound traps.
There must be a rear entrance for latecomers to lecture theatres/rooms and
it should be clearly signposted from the main entrance — preferably with a
sign illuminated when lectures are in progress. The main doorway should
be able to accommodate a large trolley.
33
CIBSE LIGHTING GUIDE
8 Emergency lighting
In all of the premises covered by this Guide, large numbers of people will
gather together. It is therefore necessary to provide emergency lighting,
which is defined as lighting that will enable people to see their way out of a
building in the event of the normal lighting failing. It must be stressed that
it is not the function of emergency lighting to enable normal activities to
continue within a building if the main power supply should fail; such lighting
is referred to as standby lighting and is not normally provided in educational
and conference premises.
34
LECTURE, TEACHING AND CONFERENCE ROOMS
Although BS 5266 (12) provides detailed requirements as yet these are not
accepted uniformly throughout the UK. Before the finalisation of specifi-
cation is completed it is essential to consult the local enforcing authority.
In general, teaching rooms and laboratories are used by persons who will be
reasonably familiar with the layout and safety provisions for an orderly
evacuation in the event of emergency. However, in laboratories some pro-
cesses may need terminating before evacuation and in conference rooms the
majority of persons present are likely to be unfamiliar with the layouts. It is
therefore necessary to provide strategically placed signs permanently indi-
cating the ways out of the areas and that adequate illuminance is provided
in special locations where a visual task must be performed prior to evacuation.
8.1 Escape route signs Much anxiety and confusion can be alleviated by strategically placed signs
permanently indicating the ways out of the premises. It is very important
that exits and emergency exits are quite clearly sign posted and are visible at
all times with normal emergency lighting systems. The signs should use the
preferred terms EXIT or EMERGENCY EXIT. On no account should signs be used
indicating NO EXIT. Where direct sight of an exit is not possible and doubts
may exist as to its position, then direction signs with an appropriate arrow
or words should be added. The sign must direct someone who is unfamiliar
with the building to the nearest exit.
The signs must comply with the requirements of BS 5499 (14) Parts 1, 2 or 3
and in one building should be uniform in colour, format and style. Examples
of two types of exit sign are given in Figure 8.1.
8.2 Escape route There are three types of areas to be considered for the purpose of escape
illumination lighting requirement; clearly defined routes, large open areas and areas with
fixed seating.
8.2.1 Clearly defined route Normally corridors or gangways. The horizontal illuminance at floor on the
centre line of a clearly defined route width up to 2 m wide should be lit to
a minimum of 0.1 lux. Wider routes should be treated as several 2 m bands.
8.2.2 Large open areas Examples are dining halls, laboratories, and multipurpose rooms. These
places will not have defined routes and the layout of furnishings may change
from time to time.
8.2.3 Fixed seating areas Examples are auditoriums, lecture theatres and rooms. These places will
have fixed seating layout on horizontal or sloping planes but divided by
gangways which are designed as clear escape route and should be treated so.
For any part of the area having fixed seating layout the average horizontal
illuminance measured on a plane 1 m above floor/pitch line, should be not
less than 0.1 lux with a uniformity of 0.025.
35
CIBSE LIGHTING GUIDE
8.3 Hazard areas In laboratories and certain control rooms or workshops the activity may
involve hazardous tasks not dependent on electricity supply or which present
a hazard if left in operation. These need to be made safe before evacuating
the area. In these situations the immediate area containing the task should
be illuminated to a minimum illuminance of 2 lux or such higher level,
normally 1% of the main lighting levels that the visual task demands it. This
illuminance may be of shorter duration than that used for escape lighting.
Often a strategically placed escape luminaire will suffice.
8.4 Operating The emergency lighting must reach the required illuminance within 15
conditions seconds after failure of the supply to the normal lighting and should maintain
these levels for a period of not less than 1 hour. Certain local authorities may
demand a faster response of 5 seconds. The emergency lighting luminaires
should be chosen with care and be installed in locations where they will not
cause disability glare (dazzle).
8.5 Choice of systems Basically two systems can be considered for use; central power or self
contained. Block diagrams for the two systems are shown in Figures 8.2 and
8.3. The advantages and disadvantages of the systems are shown in Table
8.1.
Figure 8.2 Block diagram for central power Figure 8.3 Block diagram for self contained
system. system.
8.5.1 Central power system In a central power system the energy is provided by batteries or generators
and is distributed through sub-circuits to feed a number of luminaires.
Typically with a central battery system the battery room or cubicle will
contain the charger, batteries, controls and indicators, and the automatic
change over switches. With central systems care should be taken on the
location of the fault detection equipment for the supply of the normal lighting
so that sub zone detection becomes effective. Also the wiring between power
source and luminaires must be routed and protected by special means to
ensure operation integrity for the full working duration even under fire
conditions. Central systems tend to be cheaper to purchase and maintain but
36
LECTURE, TEACHING AND CONFERENCE ROOMS
Table 8.1 Advantages and disadvantages of central and self contained power sources
8.5.2 Self contained system In a self contained system the emergency luminaires are self powered and
operate the luminaire independently in an emergency. Each luminaire is
fully equipped with battery, charger, charge indicator and change over device.
The batteries are continuously charged via the normal unswitched lighting.
Contained luminaires tend to be expensive with limited operating tempera-
ture but are easy to install and extend and require relatively little maintenance.
8.6 Classification of Systems are classified according to categories and modes of operation:
systems
8.6.1 Categories The emergency lighting system can be designed to supply the required load
for any desired time or duration. However, for application in the premises
covered by this guide a duration of one hour is adequate. The duration is
usually designated by X/1, X/2, X/3 for 1 hour, 2 hour and 3 hour rated units
respectively.
8.6.2 Mode of operation The mode of operation is a description of the lamp working status in a
luminaire. Broadly speaking there are two modes of operation, maintained
and non-maintained. Maintained systems are identified by marking of M
whilst the non-maintained are marked NM. For the premises discussed in this
guide the use of systems having designations of M/1 or NM/1 are recommended.
8.6.2.1 Maintained In this system the lamp is on all the time the premises are occupied. The
lamps may be powered by normal supply directly or indirectly and under
emergency conditions automatically switched to the emergency power. At
all times the output of the luminaire must meet the emergency lighting
requirements.
8.6.2.2 Non-maintained In this system the emergency lamp is off when mains power is available to
charge the batteries. When the supply fails the lamp is energised from the
emergency power source. A variant of this system called sustained is often used
where maintained lighting is required, particularly for internally illuminated
signs. The sustained system uses two lamps. One operates off the mains and
the other when required from the emergency power.
37
CIBSE LIGHTING GUIDE
8.7 Planning schemes The lighting calculations involved in emergency lighting are straightforward.
The detailed methods are described in Technical Memoranda TM12: Emerg-
ency lighting (13). It is important to base all calculations on real photometric
data for the specific lamp and luminaire with the output at worst (minimum)
condition. These conditions can be a combination of end of maintenance
cycle, end of lamp life, end of discharge at end of battery life, lowest ambient
temperature, and longest supply wire to name just a few. It is important that
the designer discusses these parameters with the likely supplier and installer
of the equipment.
8.8 Planning sequence There is no defined sequence to be followed but these few points indicate
one approach. It is most important that consultation with relevant bodies
over the specific plans are carried out early in the design process.
8.9 Inspection and Regular inspection and servicing of emergency lighting schemes is essential.
servicing BS 5266 (12) provides the framework for certification of completion if instal-
lation and certification for periodic testing and servicing. The onus for these
activities falls on the owner/user of premises.
38
LECTURE, TEACHING AND CONFERENCE ROOMS
1) Compare your answers with the checklist answers. (Y = Yes, N = No, ? = You need to consider
this item)
2) If your answers agree with the checklist, then carry on; if they disagree, then check the section
for advice; if the answer given is ‘?’ then you will need to understand what the effect of your answer
will be. Make sure that you understand the reasons behind the answers, and check the section for
more information.
Are the legal obligations to provide emergency Where there is a clearly defined route which is
lighting understood for the type and location of more than 2 m wide it must be divided into
the premises? Y 2 m strips. For each strip, does the horizontal
Will escape lighting be provided in all areas illuminance on the floor exceed 0.1 lux at all
where there is insufficient natural lighting at all points in the central area (central band) which
times that persons are on the premises? Y forms 50% of the width of the strip? Y
Does the escape lighting comply with the In large open areas — dining halls, conference
requirements of BS 5266(12), Code of Practice for rooms, laboratories, multipurpose rooms —
the Emergency Lighting of Premises (which lays which do not have defined routes and the layout
down minimum standards for the indication and of furnishings may change from time to time,
illumination of escape routes in the event of is the average horizontal illuminance over the
failure of normal supply)? Y whole area on an unobstructed floor greater
than 1 lux with a uniformity of 0.025 or better?
In essence, does the escape lighting reveal a safe
Y
passageway, fire alarm call points, fire fighting
equipment, escape signs and any permanent In areas with fixed seating — auditoriums, lec-
hazards along the escape route? Y ture halls - which have seating horizontal or
sloping planes divided by gangways which are
Does the design of emergency lighting instal-
designed as clear escape routes, are the following
lation conform to the advice given in TM 12(13)?
conditions met? Y In the part of the area with
Y
fixed seating, does the average horizontal illu-
Has the local enforcing authority been consulted minance (measured on a plane 1 m above floor/
about the escape lighting? Y pitch line) exceed 0.1 lux with a uniformity of
In laboratories will safety considerations dictate better than 0.025? Y In the gangways and other
that some processes need to be terminated before parts of the route does the horizontal illumin-
evacuation can be completed? ? If this is so then ance on the floor on the centre line exceed
standby lighting will be needed. 0.2 lux at all points and does the horizontal
illuminance on the the floor exceed 0.1 lux at
Are exits and emergency exits clearly sign-
all points in the central area (central band)
posted and are these signs visible at all times? Y
which forms 50% of the width of the escape
Where direct sight of an exit is not possible and route? Y
doubts may exist as to its position, have direction
In the case of laboratories and certain control
signs with an appropriate arrow or words been
rooms or workshops, the activity may involve
used to eliminate doubt about the route? Y
hazardous tasks which must be made safe before
Would someone who is unfamiliar with the evacuating the area. In these situations is the
building be directed to the nearest exit? Y immediate area containing the task illuminated
Do the signs comply with the requirements of to the level that the visual task demands? Y Is
BS 5499(14) Parts 1,2 and 3 and are they uniform the minimum illuminance 2 lux or higher? Y
in colour, format and style? Y Will the emergency lighting reach the required
Are the signs mounted over exit doorways or illuminance within 15 seconds after failure of
along escape routes at a height of 2 m to 2.5 m the supply to the normal lighting? Y Certain
above floor? Y local authorities may demand a faster response
Where there is a clearly defined route — corri- of 5 seconds.
dors and gangways — does the horizontal illu- Will the lighting conditions be maintained for
minance on the floor on the centre line of the a period of not less than 1 hour and in certain
route exceed 0.2 lux at all points? Y cases 3 hours? Y
Where there is a clearly defined route — corri- Will the luminaires and their location cause
dors and gangways — which is 2 m wide or less, disability glare (dazzle)? Y
does the horizontal illuminance on the floor Have installation instructions, commissioning
exceed 0.1 lux at all points in the central area procedures and operation and service instruc-
(central band) which forms 50% of the width of tions been prepared? Y
the escape route? Y
Will appropriate tests and inspections be carried
Where there is a clearly defined route which is out to verify that adequate emergency lighting
more than 2 m wide it must be divided into is available at all material times? Y (Inspection/
2 m strips. For each strip, does the horizontal tests: daily, monthly, six-monthly and three-
illuminance on floor on the centre line of the yearly).
strip exceed 0.2 lux at all points? ?
39
CIBSE LIGHTING GUIDE
9 Maintenance
9.1 Lighting In both lecture and conference spaces it is essential for the lighting equipment
maintenance to be properly maintained. Lamps which have failed, or which are flickering
not only fail in their function, but convey the impression to audience and
lecturer alike that nobody cares. It is important that lamps which have failed
be replaced promptly, and with lamps of precisely the same type. There is a
natural reluctance on the part of maintenance departments to maintain stocks
of special lamps, and thus there is a tendency to simply put in any lamp that
will fit the holders. It is necessary therefore to see that adequate stocks of
the correct lamps are held.
Other items such as blackout blinds, projection screens and lighting controls
suffer damage relatively frequently, often as a result of misuse by lecturers
unfamiliar with the particular theatre. Any damage of this kind should be
made good promptly. It can largely be avoided by mounting clear instructions
on an engraved plate adjacent to the item concerned and using equipment
of sufficiently robust construction to withstand the onslaughts of a frustrated
lecturer.
9.2 Cleanliness and Lecturers and audience alike expect lecture rooms and theatres to be clean.
tidiness Fixed seating presents particular difficulties to cleaning staff, especially in
steeply raked theatres — it is difficult to both see and to reach under the
seats. In very large lecture theatres or conference rooms it may be worthwhile
to provide special overhead lighting for the purposes of the cleaners, but if
this is done it should be arranged so that it cannot be switched on during
the normal use of the theatre, as it will usually ruin the effects of the normal
lighting.
Because many lecture theatres are heavily used they are often cleaned at
night. Troubles then arise if they are used for special evening functions. On
such occasions arrangements should be made for at least rubbish to be
removed beforehand.
40
LECTURE, TEACHING AND CONFERENCE ROOMS
For the purposes of managing lecture theatres there are three categories.
In practice, all lecture theatres are on occasions used for purposes other than
their intended ones, sometimes on a hire basis.
10.1 Visual clutter Mention has already been made in Section 2.7 of the need to keep lecture
rooms free of visual clutter, which means keeping them free of unwanted
paraphernalia which serves only to distract the attention of the audience
from the speaker. This is illustrated in Figure 10.1. It is an essential part of
the managing of a lecture theatre or conference room to see that unwanted
paraphernalia is kept out.
Lecture theatres of category (a) are particularly prone to this trouble; wall
charts, glass cased specimens, glazed portraits of the great men of the subject
serve to distract rather than inspire. Such items should only be permanently
displayed if there is a real need to refer to them frequently, e.g. the periodic
table in a chemistry lecture theatre.
41
CIBSE LIGHTING GUIDE
Figure 1 0 . 2 A lecture room used by all departments of a university. Note the absence of visual
clutter.
10.2 Lecture attendants The term ‘lecture attendant’ refers to those individuals who actually assist in
the running of lectures, often called projectionists. The job of such lecture
attendants is to see that the lecturer’s wishes are fulfilled exactly as the
lecturer wants them, e.g. that slides appear at precisely the right moment,
that the projection is immaculate, that the lights are raised or lowered at the
right time and at the right speed. To do this, it is necessary for the attendant
to give undivided attention to assisting the lecturer and to avoid distraction.
This is particularly so when the projection room has a large window between
it and the lecture theatre/room. Whilst this may be a convenient arrangement
in allowing projectors to be operated from several positions, it raises visual
problems. First, if the lights are left on in the projection room whilst a lecture
is in progress, spill light will fall on the projection screen and ruin the quality
of any colour slides that may be shown. Second, the projectionist is extremely
visible to the lecturer, and may cause distraction to him.
42
LECTURE, TEACHING AND CONFERENCE ROOMS
In rooms of this type the internal lights must be kept off whilst lectures are
in progress, and only the designated projectionist should be there. A carefully
shielded desk light should be provided to enable the projectionist to read the
script or cue sheets. Figure 10.3 illustrates the typical lighting in a projection
room.
Figure 10.3 The projection room of a large university lecture theatre. Note the carefully shielded
desk lights and that the room is strictly reserved for projection purposes.
Care should be taken to see that bright light from nearby lights in the
audience area does not fall on the projection window. The scattered light
which this causes can in some circumstances make it difficult for the
projectionist to see the screen.
43
CIBSE LIGHTING GUIDE
10.3 Communication In the majority of lectures in which slides are shown, an automatic projector
between lecturer under the direct control of the lecturer is used. Figures 10.4 and 10.5 show
and projectionist the complementary controls of the lecturer and projection room staff. The
or projector controls available to the lecturer should be clearly marked in words, suf-
ficiently distinct to be visible in near-darkness. The controls available to the
lecturer should also include an on/off switch as it often happens that there
are long periods when slides are not required. Some automatic projectors
have an arrangement in which the light is physically obscured if a gap is left
in the train of slides, or an opaque slide inserted, but the fan noise will
continue to distract and annoy the audience; it is much better to be able to
actually switch the projector off from the lecturer’s position.
Lighting controls are similar; it is best if they can be operated directly by the
lecturer, but again the controls must be clearly marked. If this system is used
it is important that all the lights should be under the lecturer’s control. It is
commonly found that some of the lights in a lecture theatre/room are
switchable from a rear entrance door. This arrangement is not advisable, but
if it has to be adopted the switching should be such that the lecturer (or
lecture attendant) has complete control whilst lectures are in progress.
However advisable direct control of the projection and lighting may be, there
are occasions when they have to be in the hands of an attendant — for
example when a large array of demonstrations is presented. When it has to
be so, it is best to use direct verbal communication, unless dozens of slides
are to be presented.
Where large numbers of slides are used the arrangement of a push button
on the lecturer’s desk which produces a distinctive visual signal in the
projection room may be used to indicate the next slide but a second signal
indicating ‘slide off should also be available.
44
LECTURE, TEACHING AND CONFERENCE ROOMS
For this purpose, telephones between lecturer and attendant are useless.
In very large lecture theatres they may have some value when lecture
demonstrations are being set up, but they are of no value when a lecture is
actually in progress. Telephones connected to either the internal or national
networks should not be installed in lecture theatres/rooms.
1 0 . 4 Projection rooms The traditional projection room adjacent to a lecture room is nowadays used
and booths more often as a control room than a projection room, as shown in Figure
10.3. A separate projection room is strictly only required if full scale 35 mm
cinema films are to be projected, but experience shows that such a room is
essential in any lecture theatre seating more than 150. Besides housing the
projection equipment and its operator, it may also be needed to house sound
amplifying equipment, lighting controls, video recording and projection
equipment, and possibly controls for the air conditioning system. A projection
booth i.e. some sort of shack erected within a lecture theatre is not rec-
ommended because of difficulty of access once an audience is seated in the
theatre. Considerations of safety (often as local authority bye-laws) preclude
the use of booths of this type for 35 mm film projection.
10.5 Equipment rooms The multiplicity of audio visual aid techniques now in use require that much
equipment needs to be kept where it is both secure and readily available
when it is wanted. Projection rooms should not also be expected to act as
equipment stores. Separate lockable equipment rooms should be provided.
In large lecture theatres there should ideally be a large equipment room
adjacent to and on the same floor as the demonstration area, which can be
used to house items such as television monitors and overhead projectors when
not in use, and a small equipment room adjacent to the projection room.
10.6 Preparation The value of a preparation room immediately connecting with a lecture
rooms theatre or lecture room is dubious, especially when the communication is
via a door in the front wall of the lecture theatre/room. Such a door
serves only to distract the audience, and unless elaborate demonstrations are
mounted frequently, preparation rooms of this kind are unnecessary; such
rooms often become junk rooms.
10.7 Problems of
visiting lecturers
10.7.1 Lectures involving The problem here facing the visiting lecturer is familiarity with the lighting
audio visual aids but controls, and seeing that the audio visual aids chosen will actually work
not demonstrations satisfactorily in the apparatus provided. The visitor should arrive in plenty
of time before the lecture to try things out and a lecture attendant must be
there.
Reference has already been made to the necessity for lighting and projector
controls to be clearly marked. They should be few in number and should be
grouped separately from other controls. A control panel resembling the flight
deck of a large aircraft does nothing to ease the lecturer’s task.
45
CIBSE LIGHTING GUIDE
10.7.2 lectures involving Adequate access to the theatre/room from cars or vans is required. Demon-
demonstrations stration equipment intended to be seen by large numbers of people must
itself be large, and may well obstruct the view of some members of the
audience of either the projection screen or the lecturer. This is particularly
the case in lecture rooms and conference rooms as distinct from raked lecture
theatres. To avoid this problem the presentation area should be devoid of
any fixed furniture; the use of loose tables or benches of varying heights
usually enables this problem to be overcome.
The difficulties caused by problems of this kind can be greatly reduced if the
visiting lecturer makes the requirements known to the host well beforehand.
A printed list of requirements is useful here.
46
LECTURE, TEACHING AND CONFERENCE ROOMS
Slide projectors and overhead projectors have the power to Artwork should be prepared on a sheet framed to the shape
rescue or wreck a lecture. They must be carefully positioned of the slide aperture (normally width = 1.5 x height). On a
and maintained. Remote controls should be properly drawing 150 mm wide, outlines, axes and graduations should
labelled. be 0.75 mm thick. Trend lines on a graph should be 1.5
mm thick.
Lamp failure must be provided for. Some projectors have
arrangements whereby a replacement lamp can be brought Conventional architectural and engineering drawings make
into use at the push of a single lever. If these cannot be very bad slides. Non-essentials such as centre-lines and
used, it is better to provide a spare projector than a spare construction lines must be rigorously suppressed. Captions
l a m p - it is not easy to replace a red-hot lamp in the should be related to components by a line, not an arrow. A
middle of a lecture. separate key should be only a last resort. Captions should
be horizontal where possible. Vertical captions should read
Table A1.1 shows the most common lenses for front projec- upwards.
tion, and corresponding relations of picture width to projec-
tion distance for 35 mm slides in landscape format. For Sanserif type faces are sometimes preferred for lettering, as
practical purposes the magnification is given sufficiently these are usually obtainable with a wide range of weights and
accurately by the expression: sizes within one family. Heavily condensed or attenuated
versions of these faces should be avoided. Capitals should
xf = yd be used only as initial letters. A typewritten caption looks
where: messy when enlarged. Rub-down lettering is ideal. Sten-
X = Screened dimension (m) tilled lettering is suitable if carefully spaced: spacing
between individual characters should be slightly greater
f = Focal length of lens (mm) than in printed letter spacing.
y = Dimension on slide (mm)
d = Screen distance (m)
If the master is on A4 paper, titles should be approximately
20 point, captions approximately 14 point. Point sizes refer
Table A1.1 Slide projection distances (m) for various focal lengths and to the space occupied by successive lines of close-spaced
picture widths lettering. There are 72 points to one inch, or about 2.8 to
a millimetre. An 18-point type face implies a quarter-inch
distance between the bottom of one horizontal line and the
bottom of the next. This distance includes some white space
between the lines; the height of a capital letter might be
about three quarters of its point size, depending on its
typographic character.
47
CIBSE LIGHTING GUIDE
48
LECTURE, TEACHING AND CONFERENCE ROOMS
A2.1 Dimming systems Great care has to be exercised when specifying a dimmer
size as the load has to be calculated using circuit watts, not
just tube watts. To avoid confusion, always specify the
The usual method of dimming lamps nowadays is to use quantity of tubes connected to a dimmer together with their
solid state devices such as thyristors or triacs. These are, in rating and length. The dimmer size should be calculated in
essence, very fast operating electronic switches. Both have amps, based upon the specified uncorrected current of the
a main current path which becomes conducting on the ballast used. In practice, it is sufficient to use the tube
application of a pulse signal to the control gate. The advan- manufacturer’s design current for rating purposes. Power
tage of the triac over the thyristor is that it will pass current factor correction (PFC) makes no difference to the dimmer
in both directions. The thyristor passes current in one size required. PFC capacitors are connected across the fixed
direction only and two devices must be connected in inverse level output of the dimmer and therefore have no effect on
parallel if they are to operate over the full AC cycle. the current flowing through the thyristors.
All dimmers must be fully protected by quick acting fuses for A2.2.2 low voltage tungsten
overload protection. Sub-circuit protection can be provided
with either quick acting fuses or circuit breakers (MCBs) to Due to the inductive nature of the transformers necessary
choice. to operate low volt tungsten lamps, only dimmers specifically
designed for inductive loads may be used; these will usually
Since the power dissipated in thyristors and the control be described as being universal or suitable for inductive
circuit is very small, the dimmer efficiency can be as high loads. The term ‘hard-firing’ is also used to describe the
as 98%. The output waveform is heavily distorted producing operation of such units; this refers to the mode of operation
mains harmonics and appropriate filter networks must be of the back-to-back thyristors so that the need for load
incorporated to minimise radio interference and meet the resistors is eliminated. Care must be taken when operating
requirements of BS 800(17). both mains and low voltage halogen lamps dimmed for
extended periods as the operation point may be below the
It should be noted that any dimming system, incandescent threshold of the halogen cycle, leading to short life and
and fluorescent alike, is apt to produce radio-frequency premature lamp blackening. The lamps can be cleared by
interference which may upset other electronic apparatus in running them for a period at full power until all of the
the vicinity, and particularly sound amplifying systems. deposited tungsten is re-evaporated. Note that, in no circum-
Dimming equipment and the wiring associated with this stances, may lamps operating on electronic transformers be
should be designed to keep radio-frequency emission to the connected to dimmers.
minimum and other electronic apparatus should be carefully
screened to prevent interference being picked up. A2.2.3 Fluorescent lamps
49
CIBSE LIGHTING GUIDE
The introduction of high frequency electronic ballasts for A2.2.4.2 Automatic control
the operation of fluorescent lamps has led to the develop-
ment of controllable ballasts where the output can be varied This control method provides a number of light levels which
between 25% and full-up. This control is obtained without are preset by the user. Momentary action of the appropriate
the use of external thyristor dimmers, all dimming being preset button on the control plate causes the dimmer to
achieved electronically within the ballast, using external change (up or down as required) form its existing light level
control signals within 0-10 V DC or of a pulse width to the new preset level. Control can be from either a single
modulation coded signal, again on a low voltage supply. plate or any number of remote plates wired in parallel.
A2.2.5 Luminaires
A2.2.4 Controls
All fluorescent luminaires must be fitted with the appro-
Dimming systems are usually available with a range of priate dimming control gear — in no circumstances may
control options. unmodified luminaires be used.
50
LECTURE, TEACHING AND CONFERENCE ROOMS
Lecture theatres and conference rooms are sometimes used • Over-stage rigging for hanging scenery and top
as venues for theatrical presentations. The paragraphs below masking. This can be basic exposed rolled steel joists
describe the additional provisions that should be made if (RSJs) and scaffold pipes, with manual or motorised
the room is to be easily adaptable for these purposes. It is winches, or fully counterweighted flying systems
stressed that these are additional, and it is necessary that requiring two to three times the visible stage height.
the requirements of Sections 2, 4, 9 and 10 are first met.
When such rooms are used for theatrical purposes, they will • Work-lights at both sides, rear and over main stage for
almost certainly be subject to local authority bye-laws: for setting and changing scenery with local switching and
more information on emergency lighting see Section 8. master switch at stage manager position, Fluorescent
battens with protective trough reflectors and wire guards
Publications on the subject and general advice are available are usually used for work-lights. Instant operation is
from the Association of British Theatre Technicians, and essential. Dim, shielded lights are also required for used
detailed advice and planning from members of the Society of during performance but these can be rigged as required
Theatre Consultants, both contactable at 4 Great Pulteney if full theatrical standards are not specified.
Street, London W1R 3DF. • Provision for theatrical lighting installation using pro-
fessional spotlights rigged on standard 48 mm OD scaf-
The additional provisions needed in the audience area are: fold tube and connected using industry standard 15A
BS 546(9) plugs and sockets. Essential locations are
• The lighting must be dimmable smoothly and without above the stage parallel to the front curtain immediately
flicker to 1% of its maximum level.
behind the curtain line, 1 m in front of rear wall and
• Exit signs as required by local safety code. Luminance between at 1 m to 1.5 m intervals. Each socket should
and spill light should be restricted to avoid glare and be wired individually to a 10A theatre dimmer remote
interference with stage lighting effects. control from the lighting control room.
• Light and sound traps on all entrance doors (or at least Control of the lighting and sound systems may be effected
those used by latecomers and for access to toilets). from the projection room or separate lighting and sound
Lighting within a light trap should be primarily from control rooms. The lighting in those rooms should be similar
the dimmed houselight system, but a low power light to that for a projection room and the rooms should be
from the external system may also be needed, and sound-proofed. A good view of the stage is essential in
possibly a maintained emergency light. each case. Loudspeaker reproduction of platform sound is
• Provision for theatrical lighting installation using pro- essential, and if a headset communication system is used
fessional spotlights rigged on standard 48 mm OD scaf- appropriate wiring should be provided.
fold tube and connected using industry standard 15A
BS 546(9) plugs and sockets. Essential locations are All systems should be arranged so that they can be operated
above the seating parallel to the front curtain at approxi- by a single person if necessary. The control rooms should
mately 45° elevation from 1.8 m above the front of the be of sufficient size; as many as forty dimmer circuits
stage, Steeper and shallower positions will also be useful may be involved. The sound control room should have
as will positions on the side walls at 45° in plan to centre connections to tie-lines for microphones and loudspeakers
stage. Safe access for adjustment and re-lamping must both on stage and in the audience area, and also be con-
be anticipated, Each socket should be wired individually nected to the headset communication system, the dressing
to a 10A theatre dimmer with remote control from the room sound system and the audience deaf-aid system if one
lighting control room. is installed.
51
CIBSE LIGHTING GUIDE
8 Lighting Guide LG4: Sports (London: Chartered Institution of Building of high correlated colour temperature as having a cool
Services Engineers)(1990) appearance.
9 BS 546 Specification. Two-pole and earthing-pin plugs, socket-outlets and
socket-outlet adaptors (London: British Standards Institution)(1950)
10 The Fire Precautions Act (London: HMSO)(1971) colour rendering
11 The Health and Safety at Work etc. Act (London: HMSO)(1974)
12 BS 5266: Part I: 1975 Code of Practice for the emergency lighting of A general expression for the colour appearance of objects
premises used for entertainment (London: British Standards Insti- when illuminated by light from a given source compared,
tution)(1975) consciously or unconsciously, with their appearance under
13 Technical Memoranda TM12: Emergency lighting (London: Chartered
light from some reference source. ‘Good colour rendering’
Institution of Building Services Engineers)(1986)
14 BS 5499: Fire safety signs (London: British Standards Institution)(1984)
implies similarity of appearance to that under an acceptable
15 BS 4727: Part 4: 1971/2 Glossary of terms particular to lighting and light source, such as daylight. The colour rendering proper-
colour (London: British Standards Institution)(1972) ties of the lamp relate to this effect under specified condit-
16 CIE 17.4: International Lighting Vocabulary : 4th Edition (Vienna: ions.
Commission Internationale de l’Eclairage)(1987)
17 BS 800: Specification for limits and methods of measurement of radio
committee rooms
interference characteristics of household electrical appliances, portable tools
and similar electrical apparatus (London: British Standards Insti-
tution)(1988) Rooms used for meetings capable of seating up to roughly
30 persons.
contrast
Glossary of terms used
A term which, when used subjectively, describes the differ-
ence in appearance of two parts of a visual field seen
The definitions and explanations given in this glossary are simultaneously or successively. The difference may be
intended to help readers to understand the Guide. They are brightness or colour or both. Objectively, the term expresses
based on British Standard 4727: Part 4: Glossary of terms numerically the luminance difference by various formulae.
particular to lighting and colour (15), and on the fourth edition
of the International Lighting Vocabulary (16) issued jointly contrast rendering factor
by the Commission Internationale de l’Eclairage and the
International Electrotechnical Commission. These docu- The ratio of the contrast of a task under a given lighting
ments should be consulted if more precise definitions are installation to its contrast under reference lighting con-
needed. The terms are arranged in alphabetical order. ditions.
adaptation
correlated colour temperature
The process which takes place as the eye adjusts to the The temperature of a full radiator that emits radiation
brightness or the colour of the visual field. The term is also having a chromaticity (colour quantity defined by an
used, usually qualified, to denote the final state of the accepted system) nearest to that of the light source being
process. For example, ‘dark adaptation’ denotes the state of considered. The unit is the kelvin, K. As an example, the
the eye when it has become adapted to very low brightness. colour of a full radiator at 3500 K is the nearest match to
that of a white fluorescent lamp, which is therefore said to
adjoining spaces have a correlated colour temperature of 3500 K.
Equipment used with discharge lamps for stabilising the direct lighting
discharge.
Lighting in which the greater part of the flux reaches a
booth surface directly, i.e. without reflection from other surfaces.
52
LECTURE, TEACHING AND CONFERENCE ROOMS
The part of emergency lighting which is provided to ensure Lighting in which the greater part of the flux reaches a
that the escape route is illuminated at all material times. surface only after reflection at other surfaces and particu-
larly at the roof or ceiling.
flicker
intensity
Impression of regular fluctuations of brightness or colour.
Flicker is associated especially with the light from discharge See luminous intensity.
lamps and occurs when the frequency of variation lies
between a few hertz and the ‘fusion frequency’ of the images. keystone effect
The latter is the frequency above which the variations are
too rapid to be registered by the eye. The distortion of an image caused by projection onto a
surface not at right angles to the projector beam. It com-
monly occurs when a slide or overhead projector is tilted
general lighting upwards to throw an image on a vertical screen, causing
the top of the image to become more highly magnified than
Lighting designed to illuminate the whole of an area without the bottom.
provision for special local requirements.
lamps
glare
• Discharge lamp: a lamp in which the light is produced
The discomfort or impairment of vision experienced when either directly or by the excitation of phosphors by
part of the visual field (e.g. sky or lamps) are excessively an electrical discharge through a metal vapour (e.g.
bright in relation to the general surroundings. There are mercury, sodium), gas (e.g. xenon), or a mixture of
several forms of glare. several gases and vapours.
• Disability glare: glare which impairs the ability to see • Incandescent lamp: a lamp in which light is produced
detail without necessarily causing visual discomfort. by a filament heated to incandescence by the passage
• Discomfort glare: glare which causes visual discomfort of an electric current through it. The filament is
without necessarily impairing the ability to see detail. enclosed in a glass bulb which is either evacuated or,
more usually, filled with an inert gas at low pressure.
• Direct glare: glare caused when excessively bright parts A tungsten filament is used in most incandescent lamps
of the visual field are seen directly. e.g. lamps which which are consequently known as tungsten lamps.
are inadequately shielded.
• Reflected glare: a term used to describe various visual large conference rooms
effects, including reduction of contrast, discomfort and
distraction, produced by the reflection of light sources
Rooms used mainly for conferences and meetings at which
or other bright areas in glossy or smooth surfaces; gloss
people may address the audience from almost any point in
paint and water surfaces are examples of such surfaces.
the room. Such rooms will usually have a seating capacity
of more than 60.
See lamps. Rooms used mainly for the delivery of formal lectures, with
basically flat floors and fixed seating. This category includes
rooms with a raised step or podium for the lecturer, and
illuminance
rooms with one or two raised steps towards the rear of the
seating.
The luminous flux incident on unit area of a surface. The
unit is the lux which is one lumen per square metre.
lecture theatres
illumination
Rooms used for the delivery of formal lectures with raked
floors and/or balconies or galleries and with fixed seating.
The process of lighting an object or surface.
local lighting
illumination vector
Lighting designed to illuminate a particular small area.
A term used to describe the directional characteristics of
light at a point. Its magnitude is the difference in illumin-
ance on opposite sides of a flat surface, which is so orientated localised lighting
that this difference is a maximum. Its direction is normal
to this surface; the positive direction of the vector is from Lighting designed to illuminate a general area, such as a
the higher illuminance to the lower illuminance (lux). sports hall, and at the same time provide higher illuminance
53
CIBSE LIGHTING GUIDE
over a particular part of the area, e.g. the tables in table Where l is the length of the room, w is the width of the
tennis. room and h the height of the luminaires above the floor or
other relevant horizontal plane. Consistent units should be
used for the dimensions.
luminance
A term which expresses the intensity of the light emitted rooms for practical work
in a given direction by unit area of a luminous or reflecting
surface. It is the physical equivalent of what subjectively is Rooms used regularly for class teaching purposes, without
called brightness. The unit most commonly used is the large permanent pieces of apparatus set up. Such rooms
candela per square metre (cd/m2). will usually have a seating capacity of less than 60. This
category will include many teaching laboratories.
luminaire
teaching rooms
reflector
Rooms used mainly for class teaching purposes, with flat
A device for controlling the flux from a lamp by reflection floors and no fixed furniture except possibly chalkboards
at suitably shaped surfaces. These may be either specular and projection screens. Such rooms will usually have a
(e.g. mirrored glass or polished aluminium) or diffuse (e.g. seating capacity of less than 60.
vitreous enamel). In the former, the light is reflected in
accordance with the laws of optical reflection. In the latter
the light is diffused, largely without reference to any par-
uniformity ratio
ticular direction.
In this Guide, the ratio of the minimum illuminance over
response time a given area to the average illuminance.
54
LECTURE, TEACHING AND CONFERENCE ROOMS
55