Sunteți pe pagina 1din 9

1114 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO.

2, APRIL 2017

Triggered Current Limiters—Their Arc Flash


Mitigation and Damage Limitation Capabilities
Jay Prigmore, Member, IEEE, and John S. Schaffer, Senior Member, IEEE

Abstract—Triggered current limiters (TCL) have traditionally ings [1], [2]. Onsite personnel can be exposed to hazardous
been applied to protect overdutied switchgear in medium volt- levels of system energy when working in the vicinity, should
age substations but increasing trends include the applications of an arc fault occur. Lowering or removing the available incident
damage limitation and Arc Flash mitigation. TCLs are effective at
minimizing damage from short circuits due to their speed, which energy in the system can not only save equipment from damage
results in their peak current limitation capabilities. Their subcycle but also minimize exposure of personnel.
response time (extinction in 1/4–1/2 cycle) can often reduce the I2 t Traditional approaches for limiting fault currents and mini-
available in the system to less than 1% of its potential value com- mizing system damage are highlighted below [3]–[5]:
pared to a fice-cycle breaker. TCLs are capable of reducing the 1) Upgrade system equipment
incident energy enough to reduce the Arc Flash hazard category
and required personal protective equipment for onsite personnel. 2) Addition of a current limiting reactor
A TCL can commonly reduce the Arc Flash hazard category from 3) Open bus ties or disconnect sources
category 4 to category 2 in medium voltage. For low voltage, most 4) Addition of current limiting fuses (CLFs) when <1000V
applications should be reduced to category 0 or 1. This paper aims or in branches of medium voltage systems [6]. Yet their
to address the applications of Arc Flash reduction and damage lim- effectiveness may be limited by melt characteristics or
itation for substation design and generating stations, and highlights
the benefits a TCL can provide. availability of sufficient continuous duty ratings.

Index Terms— Arc flash and arc blast, electrical safety, fault
current limiters, occupational safety, power system faults, power II. TRIGGERED CURRENT LIMITER
system protection, substation design, substation protection. Triggered Current Limiters (TCLs) also referred to as Com-
mutating Current Limiters (CCLs) are devices which consist
of a main continuous current conduction path with a parallel
I. INTRODUCTION mounted current limiting fuse [7]. TCLs have voltage ratings up
to 38 kV with continuous current capabilities up to 5000 A and
S electrical energy demand continues to grow, additional
A sources are often added to existing substations or new
substations are constructed to accommodate this increase in de-
interrupt ratings up to and sometimes exceeding 200 kA rms,
sym. TCLs have successfully interrupted up to 311 kA rms, sym
at 15.7 kV [7].
mand. These additional sources often increase fault currents
The TCL, as shown in Fig. 1, is externally powered and does
to levels which can destroy system equipment even if the sys-
not derive its control power from the bus voltage. As the control
tem is operating within its circuit breaker interrupt ratings. The
logic requires a few cycles to power up, if one closes into a
additional sources may also exceed existing installed equip-
short-circuit condition the TCL may not operate before the first
ment ratings potentially causing catastrophic failure to multiple
peak current is reached and would not provide the protection
pieces of system equipment. This may require lengthier repair
the system requires. By externally powering up the TCL, this
times and expensive repair costs or replacement. In addition,
undesirable situation can be avoided and protection is provided
a short-circuit event may reduce the service life of substation
if one closes into a fault. TCLs are commonly powered from the
equipment due to through-fault damage. Not only can the in-
same station batteries that are used for tripping circuit breakers
terrupt ratings of protective devices be exceeded, but also the
or other equipment.
thermal and mechanical ratings of other equipment in the fault
circuit.
Furthermore, the incident energy available on the system can A. Operation
exceed all available Personal Protective Equipment (PPE) rat- Under normal (non-faulted) operating conditions, a high
percentage of the continuous current (>99%) flows through
Manuscript received February 16, 2016; revised June 2, 2016; accepted July the main conduction path with the remaining portion flowing
30, 2016. Date of publication August 24, 2016; date of current version March through the parallel mounted current limiting fuse. Upon occur-
22, 2017. Paper no. TPWRD-00195-2016.
The authors are with the System Protection Division, G&W Electric Co., rence of a short-circuit current event, the TCL senses the current
Bolingbrook, IL 60440 USA (e-mail: jprigmore@gwelec.com; jschaffer@ and determines whether to operate or not based on its preset
gwelec.com). “trigger level.” The main conduction path consists of a copper
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. bus bar with thin sections that are pyrotechincally cut and folded
Digital Object Identifier 10.1109/TPWRD.2016.2602098 back upon themselves, creating physical gaps and associated arc
This work is licensed under a Creative Commons Attribution 3.0 License. For more information, see http://creativecommons.org/licenses/by/3.0/
PRIGMORE AND SCHAFFER: TRIGGERED CURRENT LIMITERS 1115

Fig. 2. Let-through I2 t comparison.

Fig. 1. Typical components of a triggered current limiter

Fig. 2 compares the let-through I2 t of a 5 cycle breaker, a 5


voltages. This forces commutation of main conductor currents cycle breaker plus reactor combination where the reactor lim-
to the shunt current limiting fuse(s). Electrically, the cutting op- its the current to half, a traditional 200 A continuous medium
eration mimics a separation of contacts, but at extremely high voltage current limiting fuse and the TCL with its 40 kA rms,
speed. To pyrotechnics are used to achieve this high speed nec- sym interrupt rating for a medium voltage application. The let-
essary for the TCL to function in a current limiting mode. The through I2 t for a 5-cycle breaker for a 40 kA rms, sym fault
current limiting fuse melts and ultimately interrupts the fault current is 133 million A2 sec at 60 Hz. When a reactor is in-
current within 1/4 to 1/2 of a cycle (before the first peak current serted to provide a 50% reduction, the let-through I2 t is reduced
occurs) shortly before the “voltage zero” of the system [8]. The to one quarter of its original value or 33 million A2 sec. A 200 A
TCL uses two basic principles in determining when to operate. continuous current limiting fuse would reduce the let-through
The first principle is instantaneous overcurrent (threshold). The I2 t to approximately 1 million A2 sec. The TCL for this scenario
second principle is an extremely brief time-delay where the cur- can reduce the let-through energy to 0.6 million A2 sec which
rent flowing must exceed the threshold value for the specific is less than 1% of the let-through I2 t as compared to a 5 cycle
minimum time before a “short-circuit” is determined to have breaker.
occurred and the TCL operates [9]. The built in time delay is a A quick comparison is shown by the red horizontal bar rep-
filtering means to avoid operating on non-fault system transients. resenting the relative let-through I2 t just below each sub-plot
It is not desirable to utilize rate-of-current-rise (di/dt) sensing in Fig. 2. The TCL provides the excellent damage limitation
as it can have a higher probability of unwanted nuisance trips. as a traditional current limiting fuse but at elevated continu-
Short-circuits, system transients and capacitor bank discharges ous current ranges. Regarding damage limitation and Arc Flash
all have a high di/dt characteristic and it is not always possi- mitigation, it can be seen in Fig. 3 that the worst-case exposure
ble to reliably determine, in the sub-cycle timeframe required when using a TCL is based on the trigger level and its associated
for the TCL to operate, which system event is occurring. For rms, symmetrical fault level, below which the breaker or similar
timeframes greater than 1 cycle the differences between short- device is expected to clear and the TCL will not trigger. Divide
circuits, transients and capacitor bank discharges can be readily the TCL instantaneous trigger level by 1.414 to determine the
observed. By not using di/dt sensing, nuisance trips can be more associated rms, symmetrical fault. This rms, symmetrical value
readily avoided. can be applied by the user in their Arc Flash analysis programs
as a maximum exposure.
It should also be noted that the three (3) trigger levels, in
B. Energy/Damage Limitation Comparison Fig. 3, represent only the maximum values for a certain oper-
A more recent trend relates to Damage Limitation of failed ating range of a TCL and that lesser values for each range will
devices and surrounding equipment. In this case, equipment may similarly reduce the exposure. The low end of each trigger level
be properly rated for its fault duty, but the catastrophic effects of range for each interrupt rating will be the maximum trigger level
a fault are greatly limited by a TCL, as opposed to the more tra- for that interrupt rating divided by 3.5. Other ranges are avail-
ditional techniques using relays, breakers and current limiting able and custom trigger levels can be set. For faults reaching
reactors. It is well known that traditional current limiting fuses, the trigger level due to asymmetry of a lesser rms, symmetrical
in lower continuous current ratings, can be very effective in dam- fault, this will result in a triggering at a lower value, to effec-
age limitation. Commutating limiters, such as the TCL, can pro- tively mitigate those asymmetrical faults as well. In other words,
vide this effectiveness for the higher continuous current ranges the TCL will also protect against asymmetrical faults. For fault
than traditional CLFs, especially in the medium voltage range energy, similarly consider the fault currents, below which the
where CLFs with high continuous current ratings do not exist. TCL does not operate as worst-case.
1116 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 2, APRIL 2017

Fig. 3 Comparison of let-through I2 t for different protection devices based on available rms, sym current for a low voltage system.

Fig. 3 shows the let through I2 t of a 3 cycle breaker, a 3 cycle an individual may be exposed, but also by mitigating the effects
breaker and reactor combination where the reactor limits the of direct exposure to an arcing fault. Energy limitation is critical
available short-circuit current to 50% of its available value, a in Arc Flash Mitigation. It should be noted that the personnel
4000 A continuous high speed current limiting fuse and the TCL and equipment are not just coping with the energy release of an
with multiple interrupt ratings and trigger levels. The high speed Arc Flash and Arc Blast event through PPE or the routing of
current limiting fuse performs adequately while operating in its energy release to other locations. Instead, the TCL effectively
current limiting region at limiting let-through I2 t but performs reduces the arc fault energy by reducing the current in both time
poorly due to its long time to melt when below its current and magnitude. A large percentage of TCL applications are fo-
limiting region. This can be seen in Fig. 3 at 70 kA rms, sym cused on Energy Limitation for the purpose of Arc Flash and
where the graph appears to be discontinuous. Below 70 kA rms, Arc Blast mitigation.
sym, the traditional current limiting fuse quickly exceeds the The 5 main factors that determine an Arc Flash injury severity
maximum scale in Fig. 3. are given below.
The breaker and the breaker plus reactor combination both 1) Proximity
exceed the maximum scale for Fig. 3 but they reach it at differ- 2) Temperature
ent available fault currents. The TCL is reliant on its individual 3) Sound, Light, Pressure Wave
trigger level setting to determine the worst-case let-through I2 t. 4) Personal Protective Equipment (PPE)
Fig. 3 demonstrates why the trigger level selection is very im- 5) Duration of Arcing Fault.
portant in limiting the let-through I2t. The TCL will follow the The majority of Arc Flash mitigation technologies are focused
breaker curve until its trigger level is reached which acts as a on limiting the duration of the arcing fault by interrupting the
step function for any available fault currents greater than the arcing fault as quickly as possible. The TCL minimizes the
trigger level. duration of the arcing fault more than conventional technologies
once the TCL’s trigger level is exceeded. It has a far more
III. TCL APPLICATIONS pronounced effect in that it limits the magnitude of the fault,
where the energy is related to the square of the current magnitude
A. Arc Flash and Arc Blast (integrated over time).
An outgrowth of the damage limitation application and recog- A typical Arc Flash application is depicted in Fig. 4. The
nized for many years is the use of TCLs in personnel protection. TCL is installed directly on the secondary of the main trans-
This occurs not only by limiting equipment destruction to which former. Alternatively, the TCL can be installed on the incomer
PRIGMORE AND SCHAFFER: TRIGGERED CURRENT LIMITERS 1117

TABLE I
INPUT DATA FOR ARC FLASH ANALYSIS

Medium Voltage Low Voltage

Equipment Class Switchgear Switchgear


Grounding Grounded Grounded
Available Short-Circuit Current 38.85 kA 85.18 kA
Current Through Protective Device 29.88 kA (FLA/0.07) 72.16 kA (FLA/0.05)
System Voltage 13.8 kV 480 V
Gap Between Conductors 6 in (152 mm) 1 in (25.4 mm)
Working Distance[10], [11] 36 in (914 mm) 24 in (610 mm)
Arc Duration Device Specific Device Specific

Calculate the total full-load amperes (FLA) for motors and then
for transformers that makes up the maximum simultaneously
energized KVA. For motors multiply the FLA by 15; and for
transformers multiply the FLA by 30 for very conservative re-
sults.
Step 3 – Based on the inrushes, select a standard trigger level
from the manufacturer that is just greater than the maximum
Fig. 4. Typical arc flash application. TCLs are installed on the major source expected inrush value, which also provides for a device with
to cut-off a significant portion of system energy. sufficient interrupt capability. If a standard trigger level is not
desirable, a custom trigger level may be set. If the expected
inrush exceeds the maximum trigger level for the selected inter-
for a Motor Control Center (MCC). The TCL will protect all rupt rating, then select the next highest interrupt rating that has
equipment downstream of its location. If installed on the MCC, a trigger level above the expected maximum inrush.
it will protect the MCC and limit associated damage. The Arc Step 4 – The worst-case condition occurs when the fault cur-
Flash application is similar to the Damage Limitation applica- rent is just below the TCL’s trigger level. Below this level the
tion but differs in the overall protection objective and ultimately, circuit-breaker or similar device is expected to clear over a
the trigger level. longer period of time and the TCL will not trigger. To determine
For Arc Flash mitigation the criteria may be a targeted Per- the associated rms, symmetrical fault current, divide the TCL’s
sonal Protective Equipment (PPE) level. It is common to reduce instantaneous trigger level by 1.414 or 2. This rms, symmetri-
exposure down a few levels from that encountered without the cal value can be applied by the end user in their Arc Flash anal-
TCL, and in some cases to hazard level “0” for low voltage ap- ysis programs as a worst-case fault current let-through. Please
plications. For these cases, the trigger level is critical, since the note, a lesser magnitude rms, sym fault current offset by asym-
maximum exposure is typically at a current level just beneath metry could still operate the TCL.
that of the TCL trigger or instantaneous pick-up level. This can 2) Application Examples: All example calculations assume
be readily noted on Fig. 3, where the dashed vertical lines are an infinite bus and ideal conductors when calculating short-
indicative of the rms, symmetrical current level beneath which circuit current and arcing fault current. The incident energy
the TCL will not operate, thus permitting the breaker or similar calculations and hazard level results were performed using the
device to clear the fault. software package in Arc Flash Analysis by ARCAD Inc. The
1) Trigger Level Selection: Follow the steps below when values used in the calculations are given below in Table I. Only
selecting the appropriate TCL ratings and trigger level for an the duration of interruption was modified to correspond to the
Arc Flash or personnel protection application: appropriate protective devices.
Step 1 – Determine the maximum amount of fault current Medium Voltage:
flowing through the TCL that will need to be interrupted in both For a medium voltage application example of Fig. 4, the
directions. This may or may not be the total amount of fault equipment ratings are given below.
current on the system. Select the next highest interrupt rating 1) Main Transformer Rating
from the TCL interrupt ratings and corresponding standard in- – 50 MVA
stantaneous trigger levels. For example, if the system has 60 kA – 60 Hz
rms, sym available but only 40 kA rms, sym will flow through – VSECONDARY = 13.8 kVL−L
the TCL (to be interrupted by the TCL), the proper interrupt – Z% = 7%
rating would be an associated interrupt rating above this 40 kA – FLA = 2,091 A
rms, sym value. – Fault Current (ISC ) = 29.88 kA rms, sym
Step 2 – Calculate the maximum worst-case inrush of down- 2) Motor Ratings
stream motors or transformers by determining the maximum – Total Lumped MVA = 40 MVA
total KVA simultaneously energized. This can either be the – FLA = 1.67 kA
highest KVA of a single motor/transformer or it can be a sum – Backfeed ISC = 5 ∗ FLA = 8.37 kA
of individual motors/transformers within this KVA grouping. – Largest Individual Motor = 10 MVA
1118 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 2, APRIL 2017

TABLE II TABLE III


MEDIUM VOLTAGE ARC FLASH COMPARISON LOW VOLTAGE ARC FLASH COMPARISON

Breaker TCL Operation up to TCL Below Breaker + TCL Operation up to TCL Below
+ Relay Max Fault Current Trigger Level Relay Max Fault Current Trigger Level

Arc Duration 83 ms∗ 10 ms 83 ms Arc Duration 50 ms∗ 10 ms 50 ms


Incident Energy 28 6.4 6.5 Incident Energy 4.8 0.9 1.0
(cal/cm2 ) (cal/cm2 )
Hazard Level 4 2 2 Hazard Level 2 0 0
Arc Flash Boundary 174 in 83 in (739 mm) 84 in (1384 mm) Arc Flash Boundary 61 in (1554 mm) 19 in (487 mm) 21 in (523 mm)
(4418 mm) Initial Blast Pressure 258 lbs/ft2 53 lbs/ft2 59 lbs/ft2
Initial Blast Pressure 171 lbs/ft2 40 lbs/ft2 (Mainly due to 40 lbs/ft2 (lbs/ft2 )
(lbs/ft2 ) Motor Backfeed) TNT Mass Equivalent 0.46 lbs 0.07 lbs (31 grams) 0.08 lbs
TNT Mass Equivalent 1.99 lbs 0.25 lbs (115 grams) 0.26 lbs (211 grams) (35 grams)
(903 grams) (120 grams)

The arc duration for the breaker scenario may increase significantly on lower magnitude

The arc duration for the breaker scenario may increase significantly on lower magnitude faults.
faults.

An important note, the main breaker may trip and interrupt


the source contribution but it does not interrupt the backfeeds
– Largest Motor FLA = 600 A rms, sym which can prolong the arc duration and increase accumulative
– Highest Inrush = 6.3 kA inst. (peak) damage and the hazard level.
3) Maximum Downstream Transformer Rating The TCL operation yields an approximate let-through I2 t of
– 3.5 MVA 140,000 A2 sec. Adding this let-through I2 t to the I2 t value of the
– Primary FLA = 146.4 A residual 8.97 kA rms, sym yields a combined I2 t of 7.2 million
– Backfeed limited to 0.6 kA A2 sec. The combined I2 t value equates to 9.05 kA rms, sym for
– Highest inrush = 4.4 kA inst. at 13.8 kV 5 cycles. This 9.05 kA rms, sym value is used as the worst case
Based on the system voltage and continuous current ratings, fault current when the TCL does operate and is an input to the
the proper ratings for the TCL would be a 15.5 kV, 3000 con- software.
tinuous class device without any de-rating factors due to the When the fault current is below the trigger level, the TCL
environment or elevation. The maximum amount of fault cur- does not operate. The worst-case fault current would be the
rent required to be interrupted is 29.88 kA rms, sym. An in- combination of the rms, sym trigger level and the residual fault
terrupt rating greater than 30 kA rms, sym is required for this current from motors and downstream transformers. If the fault is
application (Step 1). only at a percentage of the maximum prospective fault current
The maximum inrush for the downstream transformer is due to arc impedance, the backfeeds will also be reduced to
4.4 kA inst. and the largest motor inrush is 6.3 kA inst. The that same percentage. In this application, the backfeeds will be
site operating philosophy is to energize each piece of down- reduced to 23.66% of their prospective value. The worst-case
stream equipment individually. Therefore the maximum inrush fault current is 9.19 kA rms, sym (7.07 rms, sym trigger level
current is 6.3 kA instantaneous and not a combination of both plus the percentage reduced motor backfeed current of 2.12 rms,
the largest motor and downstream transformer (Step 2). sym). Limiting the source current to the 7.07 rms, sym trigger
The next highest standard trigger level is 8 kA instanta- level in any software package typically models the worst-case
neous, although 10 kA inst. can be selected for extra margin. In condition through the TCL. An alternative approach would be
this example, the 10 kA instantaneous trigger level is selected to implement a custom TCC with a straight line at the 7.07
(Step 3). The 10 kA inst. trigger level equates to a 7.07 kA rms, sym trigger level. For Arc Flash purposes, the TCL would
rms, sym current (Step 4). The 7.07 kA rms, sym value can be essentially be a switch that operates above the 7.07 kA rms, sym
used to limit the maximum fault current output by the source as limit and would not operate below as the TCL would already be
applied in an Arc Flash software package. Since a 10 kA trig- cleared at 0.01 sec, before traditional TCCs even start. A lower
ger level is chosen, the 40 kA rms, sym interrupt rating of the asymmetrical current could still operate the TCL but exposure
TCL is the correct rating as the selected trigger level is within would be less.
the standard trigger level range for this particular the interrupt As shown in Table III, the TCL reduces the Arc Flash and
rating based on the manufacturer’s data sheet. A higher rated Arc Blast exposure considerably. In this example, it reduces
TCL can be chosen but the peak cut-off and energy let-through the hazard level from 4 to a worst-case level 2. Note that an
will also increase. Arc Flash relay operation is applicable only to a lineup of gear
The results of the Arc Flash analysis are shown below in Ta- and that the TCL is effective both inside and outside of the
ble II. It is assumed the medium voltage circuit breaker requires lineup – a zone effect with further coverage. In medium voltage
5 cycles to operate (83 ms). The Arc Flash relay operates in 1-4 applications, installing a TCL in the system can typically reduce
ms and is included in the 83 ms total operation time to clear the the hazard level from a level 4 to a level 2.
arc fault. In this medium voltage example, Lee’s method was Low Voltage: Modifying the ratings for the previous exam-
used as it is more conservative than the IEEE 1584 method for ple to accommodate low voltage applications (<1000 V), the
medium voltage [3]. equipment ratings are given below. This is a standalone example
PRIGMORE AND SCHAFFER: TRIGGERED CURRENT LIMITERS 1119

and does not reference any data in the previous medium voltage The TCL forces a current zero to occur during its interruption
example. process. This is in contrast to a breaker in which the breaker
1) Main Transformer Rating waits for a current zero to interrupt the arc fault and allows the
– 3,000 kVA full sine wave and its associated peaks to be reached. For this
– 60 Hz application, when the TCL operates, it would have an approxi-
– VSECONDARY = 480 VL−L mate let-through I2 t of 525,000 A2 sec. The residual current I2 t
– Z% = 5% plus the TCL let-through I2 t is approximately 9 million A2 sec
– FLA = 3.608 kA which equates to a 3 cycle (50 ms) arcing current of 13.4 kA
– Fault Current (ISC ) = 72.16 kA rms, sym rms, sym. The 13.4 kA for 3 cycles is used as the input into
2) Motor Ratings the Arc Flash program. The results are shown in Table III for
– Total Lumped KVA = 2,000 kVA when the TCL operates as a breaker would have to clear the
– Lumped FLA = 2.405 kA residual arcing current after the TCL operates. When the fault
– ISC = 5 ∗ FLA = 12.02 kA rms, sym currents are below the trigger level and the TCL does not op-
– Largest Individual Motor = 500 kVA erate, the worst-case symmetrical current is 15.02 kA rms, sym
– Largest Motor FLA = 600 A rms, sym (12.72 rms, sym trigger level plus the percentage reduced
– Highest Inrush Current = 9 kA inst. (17.64%) backfeed contribution of 2.3 kA rms, sym). Note at
3) Downstream Transformer Rating lower magnitude fault currents, the over current relay pickup
– 200 kVA time may incur a significant delay which in turn will add greatly
– FLA = 240 A to the exposure value.
– Worst-case inrush = 7.2 kA inst. The worst-case Arc Flash exposure is not when the TCL op-
– 1 kA rms, sym backfeed erates as shown in Table III but instead just below the TCL’s
The system voltage and continuous current determine the trigger level as a circuit breaker must interrupt the arc fault.
nominal operating ratings of the TCL. A 750 V, 4000 A con- In this example, the trigger level is selected as 18 kA instanta-
tinuous current TCL should be used if there are no additional neous (12.72 kA rms, sym). Re-running the software using the
de-rating factors such as elevation or maximum ambient tem- 12.72 kA rms, sym trigger level as the current through the device
perature. The total fault current available is the sum of main instead of the available 72.16 kA rms, sym yields elevated expo-
transformer contribution and the total contribution from all sure levels assuming a 50 ms breaker plus relay operation time,
downstream sources or 85.18 kA rms, sym. Since the TCL which may be extended at lower current magnitudes. The inci-
is installed on the secondary of the main transformer, it is re- dent energy exposure increases from 0.9 cal/cm2 to 1.0 cal/cm2
quired to interrupt the contribution from the main transformer with an increased Arc Flash boundary limit of 21 in (523 mm).
for a downstream arc fault. Based on the short-circuit flowing The hazard level remains at level 0. The initial blast pressure
through the device, an interrupt rating greater than 73 kA rms, has increased to 59 lbs/ft2 due to the larger arcing current and
sym must be used (Step 1). the TNT mass equivalent has also increased slightly to 0.08 lbs
The maximum worst-case inrush current of both the down- (35 grams).
stream motors and the downstream transformer is shown above. Overall, the PPE requirements of site personnel have been
However, one must be cautious to use the largest sum of mo- reduced from hazard level 2 with optimal assumptions before
tors or the largest motor energized at one time to get the most the TCL was applied to hazard level 0 after the TCL is applied.
accurate worst-case inrush current. In this example, the motor Typically a TCL can reduce low voltage applications to a hazard
inrush is 9 kA instantaneous and the downstream transformer level of 0 or 1.
inrush is 7.2 kA instantaneous. The maximum inrush current
is 9 kA (Step 2). Looking at the standard trigger level ranges
for the TCL based on its voltage rating, continuous current rat- B. Damage Limitation
ing and an acceptable interrupt rating, the next highest standard A typical design for damage limitation applications is shown
trigger level range is 12 kA instantaneous (Step 3). However, in Fig. 5. One TCL is installed on each individual feeder. Even
the site personnel desire extra margin and agreed upon an 18 kA if equipment is rated properly to withstand the available fault
inst. trigger level. The 18 kA instantaneous selected trigger level duty, the let-through energy of a fault may still result in costly
equates to 12.72 kA rms, sym (Step 4). This 12.72 kA rms, sym damage. Traditional equipment such as relays, circuit breakers
equivalent trigger level can be used in an Arc Flash analysis and current-limiting reactors are far less effective at mitigating
program to determine the worst-case incident energy exposure. damage. At lower continuous currents, current-limiting fuses
A 4000 A continuous current circuit breaker is assumed to prevent this damage. For higher continuous currents where tra-
have an operating time of 50 ms including relay time. The ditional CLFs do not exist (medium voltage) or are less effective
Arc Flash relay which is typically light and pressure sensor (low voltage, high continuous current), a TCL provides effec-
based is assumed to operate in 1-4 ms. The light and pressure tive current-limiting performance of a much lower rated fuse,
sensor allows the Arc Flash relay to pick-up lower magnitude through its electronically controlled operation.
faults much quicker than an over current relay at that same low Selection of trigger levels (pick-up) for minimizing damage
magnitude. The circuit breaker operating times are viewed as is more subjective. Normal, non-fault current levels that must
optimal times. flow through the TCL should be considered. This may be the
1120 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 2, APRIL 2017

the operating time of the breaker in seconds (usually between


.05 and .083s), depending on the combined relay plus breaker
speed. Please note a lesser magnitude rms, sym fault current off-
set by asymmetry could still operate the TCL but for worst-case
purposes, the rms, sym current should be used.
2) Damage Limitation Example: The main objective for the
damage limitation application is to limit the available I2 t down-
stream of the TCL to protect underrated equipment. Another
source of restriction may be a local municipality or utility re-
quirement to not exceed a certain amount of short-circuit current
or I2 t on specific circuits. These protected circuits maybe a crit-
ical circuit feeding into downtown metro networks, or it may
contain aging equipment that has been de-rated over the years
and requires improved protection against the available current.
It is commonly applied to keep manhole covers from being
launched by electrical explosions in underground systems.
1) 13.8 kV System Voltage
2) 1200 A Continuous Current Rated Bus
3) 25 kA rms, sym available fault current
4) 10 kA rms, sym desired maximum limit
Fig. 5. Typical damage limitation application. TCLs are installed on each 5) 10 kA instantaneous worst-case inrush
individual feeder. Based on the system voltage and continuous current require-
ments, the most appropriate TCL rating is the 15.5 kV, 1200
instantaneous peak of a motor or transformer inrush, or instan- A continuous current class (Step 1). Any environmental ratings
taneous peak fault level of equipment reflected to the opposite have been ignored but altitude and temperature may affect the
side of the transformer where the TCL resides. Let-through I2 t overall ratings due to their de-rating affects in dielectric strength
value, peak current let-through value or similar criteria may and continuous current capability of the TCL, in agreement with
also be targeted. Unlike traditional overdutied equipment appli- industry practice.
cations, in cases where there is not a distinct peak let-through The total current flowing through the TCL is 25 kA rms,
(cutoff) current value required for the TCL, a minimum trigger sym. A properly rated TCL should have an interrupt rating
level which avoids response to typical expected inrushes should greater than 25 kA rms, sym (Step 2). The maximum inrush
be considered. current through the TCL is 10 kA instantaneous so any trigger
1) Trigger Level Selection: level above 10 kA instantaneous would suffice. The goal is to
Step 1 – Same as in the Arc Flash Mitigation Application. select a trigger level that avoids tripping on inrush current but
Step 2 – Same as in the Arc Flash Mitigation Application. still meeting the I2 t requirements. One must also balance the
Step 3 – Based on the inrushes, select a standard trigger level increased probability of operating with a lower trigger level if
from the manufacturer’s trigger level selection table that is just multiple trigger levels would meet the requirements (Step 3).
greater than the maximum expected inrush value. For medium For example, the desired maximum fault current available
voltage sectors of a utility distribution system, the trigger level is on the system is 10 kA rms, sym. The 10 kA rms, sym tar-
commonly selected to prevent triggering on inrush to a network get value has a crest of 10∗ 2 or 14.14 kA instantaneous.
transformer and also on the peak asymmetrical instantaneous One can choose a 12 kA trigger level from manufacturer sup-
current value on the low voltage side as reflected to the medium plied tables to stay below the 14.14 kA instantaneous value
voltage side of the system [12]. If a standard trigger level is or a less conservative 14 kA instantaneous trigger level. A
not desirable, a custom trigger level may be set. If the expected 10 kA fully symmetrical fault current has an equivalent 5 cy-
inrush exceeds the maximum trigger level for the selected inter- cle let-through I2 t of 8,333,333 A2 sec. Therefore the require-
rupt rating, then select the next higher interrupt rating that has a ment to trip the TCL must be below this value. By selecting
trigger level above the expected maximum inrush. Maintaining the 14 kA instantaneous trigger level (9.89 kA rms, sym), the
the lowest trigger level will maximize the protection. worst-case let-through I2 t when below the TCL trigger level is
Step 4 – The worst-case condition occurs when the fault cur- 8,166,667A2 sec. If some additional margin is desired to be built
rent is just below the TCL’s trigger level. Below this level the in the system, a 12 kA instantaneous (8.48 kA rms, sym) trig-
circuit-breaker or similar device is expected to clear and the ger level may be selected. The 12 kA trigger level lowers the
TCL will not trigger. To determine the associated rms, symmet- 5 cycle let-through to approximately 6,382,000 A2 sec. Either
rical fault current, divide the TCL’s instantaneous trigger level the 12 kA instantaneous or 14 kA instantaneous trigger level
by 1.414 or 2. This rms, symmetrical value can be applied by would be acceptable for this example (Step 4). The increased
the user, with an appropriate breaker opening time, to calculate trigger level has a higher let-through I2 t but statistically has a
the let-through I2 t. This is commonly used as a measure of dam- smaller probability of operating while the 12 kA trigger level
age assessment, similar to let-through energy. This is calculated has a lower let-through I2 t but a slightly increased probability of
using the square of the rms, sym current value above, times operating. The trade-off must be decided for each application.
PRIGMORE AND SCHAFFER: TRIGGERED CURRENT LIMITERS 1121

IV. DESIGN CONSIDERATIONS WHEN USING When applying power electronic FCLs, one must consider
ALTERNATIVE TECHNOLOGIES the constant voltage drop across the semiconductor themselves,
Traditionally, both Damage Limitation and Arc Flash Mitiga- their associated losses, the ability of the power electronic devices
to switch the fault current over to the parallel resistance or
tion applications have been addressed by using more traditional
inductance, its transient withstand capability, rate of current rise
protection technologies such as current limiting fuses, expul-
sion fuses, circuit breakers, current limiting reactors and three- (di/dt) and rate of voltage rise (dv/dt). The end user must also
have an operational plan if the FCL should fail as a short.
phase earthing switches. One must carefully consider the below
design considerations if selecting one of the more traditional
technologies.
V. CONCLUSION
Traditionally a circuit breaker has much slower clearing times
which allow for far greater energy let-through. Some recent low In conclusion, TCLs can provide effective damage limita-
voltage, low continuous current (250 A) circuit breakers can op- tion and Arc Flash mitigation for substations. Their sub-cycle
erate sub-cycle but the main breakers, where the higher current response and energy absorption capabilities make them an at-
TCLs would be installed, would be much slower. A relay or some tractive solution to utility and industrial power systems for the
other external mechanism is required to send the trip signal to purpose of Arc Flash and Arc Blast mitigation in addition to
the circuit breaker which may further delay circuit interruption damage limitation. PPE only addresses the Arc Flash (heat) and
per the relay coordination curve. A traditional current limiting does not substantially protect personnel against the Arc Blast
fuse has reduced current-limiting capabilities at the low magni- (concussion). A TCL effectively mitigates both the Arc Flash
tude currents and often provides no status feedback. It also must and the Arc Blast, thereby providing improved protection for
be able to handle motor starts, lightning surges and heavy tran- site personnel as compared to the slower operating devices such
sients without damaging any of the internal meltable elements as circuit breakers and relays.
otherwise a change in performance may occur and replacement The TCL can protect equipment by selecting the trigger level
may be necessary. This is not a concern with TCLs. based on the desired let-through I2 t to accommodate regulatory
A current limiting reactor is physically large and may not mandates and limit damage to downstream equipment. A TCL
be able to fit physically in retrofit applications or locations can avoid splitting buses to lower fault currents while keeping
with little real estate. The reactor adds continuous conductor reliability unchanged. These are predictable devices over their
resistive losses during normal operation, imposes a regulating wide range of trigger levels and available fault currents within
voltage drop and blocks VARs transfer out of generators. The their ratings.
three phase earthing switch eliminates the arc by inducing a
3-phase “bolted fault” on the system (typically upstream) which
can add extra stress to the entire source side electrical system REFERENCES
and may incur progressive through-fault damage and potentially [1] National Fire Protection Association, “NFPA 70E Standard for Electrical
reduce the life expectancy of system components. Safety in the Workplace,” 2015.
Alternative fault current limiting (FCL) technologies such as [2] National Fire Protection Association, “National Electrical Code(R)
(NEC(R)), 2014 Edition,” 2014.
saturable core FCLs, superconducting FCLs and power elec- [3] A. C. Parsons, W. B. Leuschner, and K. X. Jiang, “Simplified arc-flash
tronic FCLs typically only “limit” the short-circuit current and hazard analysis using energy boundary curves,” IEEE Trans. Ind. Appl.,
do not fully “interrupt” the current as these devices rely on a vol. 44, no. 6. pp. 1879–1885, Nov./Dec. 2008.
[4] C. Rapids, “Arc-flash application guide arc-flash energy calculations for
breaker to clear the current, some number of cycles later. Their circuit breakers and fuses,” Energy, vol. 2, pp. 1–16, 2006.
I2 t limitation characteristics are more commonly less effective [5] J. R. Prigmore, J. A. Mendoza, and G. G. Karady, “A neodymium hy-
as compared to the TCL due to their waiting for the breaker brid fault current limiter,” Int. Trans. Elect. Energy Syst., vol. 25, no. 7,
pp. 1366–1380, 2015.
to clear the limited, but yet remaining currents. These devices [6] R. L. Doughty, T. E. Neal, T. L. Macalady, V. Saporita, and K. Borgwald,
also cannot lower the incident energy as effectively as a TCL. “The use of low-voltage current-limiting fuses to reduce arc-flash energy,”
Their operational philosophy is to introduce an inductance or IEEE Trans. Ind. Appl., vol. 36, no. 6, pp. 1741–1749, Nov./Dec. 2000.
[7] J. S. Schaffer, “Triggered current limiters for closing bus ties, bypassing
resistance in the circuit upon a short-circuit condition that is nor- reactors and improving power quality,” in Proc. 44th Annu. Rural Electr.
mally bypassed. For saturable core FCLs, one must consider the Power Conf. Pap., 2000, pp. 1–6.
voltage drop across the windings, the on-state losses due to the [8] J. S. Schaffer and T. Hazel, “Ensuring switchgear integrity in High-Power
installations,” IEEE Trans. Ind. Appl., vol. 51, no. 3. pp. 2641–2650,
resistance in those windings, fault current backfeed into the DC May/Jun. 2015.
biasing system, physical space, time to return from a limiting [9] G&W Publication, Guide to the methodology of trigger level selection for
state to a nominal state and a cooling system if superconductors the G&W CLiP., Bolingbrook, IL, USA, G&W Publ., 2010, pp. 1–8.
[10] Guide for Performing Arc-Flash hazard Calculations, IEEE 1584-2002,
are used. 2002.
Some design considerations when applying superconduct- [11] K. J. Lippert and C. W. Kimblin, “Understanding arc flash hazards,” in
ing FCLs, one must recognize the time to return from a non- Proc. IEEE IAS Pulp Paper Ind. Conf., 2004, no. 2, pp. 120–129.
[12] B. Deal, “Improving urban safety by installation of current limiting fuses
superconducting limiting to a superconducting state as well as on network feeders,” in Proc. Southeast Elect. Exchange Conf. Paper Ind.
the losses and power system operation effects associated during Excellence Award, Atlanta, GA, USA, 2009.
this time, the service and maintenance of a cooling system and [13] J. R. Prigmore, “A neodymium based hybrid fault current limiter,” Ph.D.
dissertation, School Elect., Comput. Energy Eng., Arizona State Univ.,
the operational steps if the cooling system fails. Tempe, AZ, USA, 2013.
1122 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 2, APRIL 2017

Jay Prigmore (M’07) received the B.Sc. degree in John S. Schaffer (SM’90) received the BSEE and
electrical engineering from Lamar University, Beau- BSME degrees from Marquette University, Milwau-
mont, TX, USA, and the M.S. and Ph.D. degrees in kee, WI, USA, in 1974 and 1976, respectively, and
electrical engineering from Arizona State University, the MBA degree from Lewis University, Romeoville,
Tempe, AZ, USA. IL, USA, in 1988.
Currently, he is with G&W Electric Co. in the He has been with G&W Electric Co. since 1982
System Protection Division. and he has been the General Manager of its Sys-
Dr. Prigmore is a Member of the Power and Energy tem Protection Division since 1992. Prior to join-
Society, the Power Electronics Society, Industrial Ap- ing G&W, and he was affiliated with Allis-Chalmers
plications Society, and the Magnetics Society. He is Corp. for 7 years, in the engineering of high volt-
a Member of Sigma Xi, Eta Kappa Nu, and Tau Beta age circuit breakers, motors, and DC traction sys-
Pi. He is the Chair for the IEEE IAS Executive Subcommittee for Early Career tems. He has authored and coauthored numerous technical papers on fusing
Professionals. He is a registered professional engineer in the State of Illinois. and switchgear topics for IEEE, the American Power Conference, CIGRE, and
CIRED. He is a holder of four U.S. patents and their foreign counterparts.
Mr. Schaffer is a member (now primarily inactive) of the IEEE High Voltage
Fuse Subcommittee, and a number of its working groups, in the IEEE promul-
gation of associated fuse standards. He has also been a member of the NEMA
High Voltage Fuse Technical committee. He has been a registered professional
engineer in the State of Wisconsin for more than 30 years.

S-ar putea să vă placă și