Publication No. TPD1742E3, September 2014.
Copyright © 2013 Perkins Engines Company Limited, all rights Perkins Engines Company Limited
reserved. No part of this document may be reproduced in any form Peterborough, PE1 5FQ, United Kingdom
or by any means, without prior written permission of Perkins Engines Tel: +44 (0)1733 583000
Company Limited. The information in this document is substantially Fax: +44 (0)1733 582240
correct at the time of printing and may be altered subsequently. www.perkins.com
General installation
1103D-33 G2
Type of operation and application
Designation Units Prime power Standby power Prime power Standby power
1500 rpm 1500 rpm 1800 rpm 1800 rpm
Gross engine power kWb 29.7 33.0 34.2 38.0
Fan Power kWm 0.7 1.1
Gross BMEP kPa 1023 1128 1020 1124
Mean piston speed m/s (ft/s) 6.35 (20.8) 7.62 (25.0)
ElectropaK nett engine power kWm 29.0 32.3 33.1 36.9
Engine coolant flow 35 kPa system restriction litres/min 125.0 151.0
Combustion air flow (at STP) m³/min 2.13 2.16 2.60 2.63
Exhaust gas flow (max.) m³/min 5.25 5.49 6.10 6.52
Exhaust gas outlet temperature
°C 515.0 570.0 530.0 580.0
(max. at standby)
Cooling fan air flow (200 kPa external
m³/min 45.6 69.6
restriction)
Overall thermal efficiency (nett) % 36.4 36.3 36.1 35.9
kWe 25 28 29 32
Typical Genset electrical output (0.8pf 25ºC)
kVA 32 35 36 40
Friction power and pumping loss kW 7.7 10.3
Assumed alternator efficiency % 89%
Specific Fuel Consumption litres/min 0.13 0.15 0.20 0.21
Energy balance
Designation Units Prime power Standby power Prime power Standby power
1500rpm 1500rpm 1800rpm 1800rpm
Power in fuel (Fuel heat of combustion) kWt 81.6 91.0 94.8 105.8
Power output (gross) kWb 29.7 33.0 34.2 38.0
Power to cooling fan kWm 0.7 1.1
Power output (nett) kWm 29.0 32.3 33.1 36.9
Power to coolant and lubricating oil kWt 21.3 23.9 23.2 26.7
Power to exhaust kWt 26.1 29.1 32.2 35.3
Power to radiation kWt 4.5 5.0 5.2 5.8
Note: The airflows shown in this table will provide acceptable cooling for an open power unit operating in ambient temperatures of up to 53 °C (127 °F)
or 46 °C (114.8 °F) if a canopy is fitted. If the power unit is to be enclosed totally, a cooling test should be done to check that the engine cooling is
acceptable. If there is insufficient cooling, contact Perkins Technical Service Department.
2 of 9
Publication No. TPD1742E3, September 2014.
Copyright © 2013 Perkins Engines Company Limited, all rights Perkins Engines Company Limited
reserved. No part of this document may be reproduced in any form Peterborough, PE1 5FQ, United Kingdom
or by any means, without prior written permission of Perkins Engines Tel: +44 (0)1733 583000
Company Limited. The information in this document is substantially Fax: +44 (0)1733 582240
correct at the time of printing and may be altered subsequently. www.perkins.com