Sunteți pe pagina 1din 4

HC900 Controller

Rack Installation

4 I/O Slot Rack 900R04 - (current revision number)


8 I/O Slot Rack 900R08 - (current revision number)
12 I/O Slot Rack 900R12- (current revision number)
8 Slot Rack - Redundant Power 900R08R - (current revision number)
12 Slot Rack – Redundant Power 900R12R - (current revision number)
Redundant CPU Rack 900RR0 - (current revision number)
Document Number Form: 51-52-33-150
Effective Date: 03/2005
Supersedes: None

Summary Enclosed is a Rack for your HC900 Controller.

Racks are available in 4-slot, 8-slot, and (900R04)


12-Slot versions.
Racks are interchangeable between the
Controller rack and an I/O expansion rack
(C50 CPU only) - Figure 1.
8 and 12 slot I/O racks (900R08 and
900R12) can be modified with additional (900R08R)
slots for optional Reserve Power Supply (900R08)
and Power Status Module.

C50: I/O rack has a Scanner 1 module


C70R: I/O rack has a Scanner 2 Module.
(900R12R)
(900R12)

Redundant CPU Rack (900RR0)


Redundant CPU Rack:
Holds two redundant C70R CPUs, two
Power Supplies, and one Redundancy
Switch Module (RSM).
The C70R Redundant CPU Rack does not Power C70R RSM C70R Power
Supply CPU CPU Supply
support any I/O Modules and cannot be
used with C30 or C50 CPU’s

Figure 1 Rack Configurations

3/05 Controller Rack Installation Kit # 51-52-33-150 1


Rack Orientation and Mounting
Racks must be mounted as indicated in illustrations throughout this instruction, so as to provide for
vertical airflow through the racks. That is, racks must never be mounted vertically, and must never be
mounted with the backplane horizontal (for example, flat on a horizontal panel or tabletop).
Environmental specifications apply only to the normal mounting configuration.

Rack dimensions, including overall dimensions and patterns for drilling holes for mounting, are given
in Figure 2, Figure 3 and Figure 4. Vertical spacing of racks, which is required for rack ventilation and
for routing wires, is shown in Figure 5.

Figure 2 Rack Dimensions (4, 8, 12 Slot)

Total Depth
6.0 (Rack +
152.4 components)
Rear
mounting Redundant Power Supply 12-Slot
plate Chassis and Power Status Module I/O Rack 8-Slot
height height (I/O Racks only) I/O Rack
6.90 5.4
175 137

4.4 16.5
113 419
22.5
571
Key: 20.9
530.9
inches 26.9
mm 684

Reference Center
12-slot for Drilled Holes
racks only 8-slot at Top of Rack
racks only All racks
0.263
7
Redundant Power Supply
and Power Status Module
6.90 (I/O Racks only) 6.375
175 162

4.34 3.02 3.02


110.2 6.04 76 6.23 76 6.04
153 158 153

Figure 3 Rack Dimensions with Redundant Power Supplies (8 and 12 slot)

2 Controller Rack Installation Kit # 51-52-33-150 3/05


Reference Center
for Drilled Holes
at Top of Rack
Total Depth
6.0 (Rack +
152.4
0.263 components)
Rear 7
mounting
plate Chassis Controller Rack
height 6.375 height (CPUs, RSM,
6.90 162 5.4 Power Supplies)
175 137

10.3
Key:
261.6
inches 6.23
mm 158

Figure 4 Redundant CPU Rack Dimensions

Figure 5 Vertical Spacing of Racks (all models)

3/05 Controller Rack Installation Kit # 51-52-33-150 3


Procedure
Use the following procedure to install the specific rack supplied.

Table 1 Redundant Controller CPU Module installation or replacement


Step Action
1 Using the dimensions in Figure 2, 3,
and 4 as a guide, mark the locations for
rack mounting in the enclosure for the top
holes in the rack.

CAUTION:

When drilling holes, prevent metal


flakes from falling into the rack, or onto
any surface within the electrical cabinet.

2 Aluminum grounding bars for I/O module


wiring are optional. They can be mounted at
top, at bottom, or at top and bottom of the
rack, as indicated at right.

If grounding bars are included, attach them


with two M3 screws (supplied with grounding
bars in plastic bag).

Note: The plastic bag also includes four M4


screws for attaching the grounding wire lugs,
which are attached later.

Attach the M4 screws loosely to the


grounding bars for safe keeping.
3 Hang the rack in the enclosure on the top
screws.

Start all screws in the bottom of the rack and


then tighten all screws.

Note: You may find it easier to postpone this


step until after all components have been
installed in the rack.

4 Repeat for each rack in your system.

4 Controller Rack Installation Kit # 51-52-33-150 3/05