Programming of DRIVE-QLiQ-Modules with SINAMICS –

CU320-2 and Firmware Version 4.X

To test the 1PH8-motors with star-delta-mode and the 1FK7-Redesign motors with the
SINAMICS converter it is necessary to install a CU320-2.

With the new CU320-2 and firmware versions 4.X there is a change of the current
programming process of DRIVE-CLiQ Modules. Different scenarios are described in the
following.

1. Reprogramming of a programmed DQ-Module


Before reprogramming of an already programmed DQ-Module, it has to be deleted at first.

1.1 Delete DQ-Module

1.1.1 The first step is to load an existing STARTER-Project. Then change into online-mode
and in the topology view. The DQ-Module of the motor is connected at port 2 of the
motor module in this case and has component #6:

1.

Date: 2012-03-28 EWN ServiceCenter


1.1.2 The next step is to get a component number bigger than 200 in the topology tree. This
2. happens very easy if the motor (DQ-module) will be connected to a free port. In this
3. example it was connected to port 1 of the motor module.

4.

5. In this case the component #205 was created.

6.

1.1.3 Then the access level has to be changed to “Expert (3)”. Therefore open the expert list
(parameter list) of the CU and then click on the key symbol in the tool bar.

7.
8. The following window will be shown:

Date: 2012-03-28 EWN ServiceCenter


9. Now change to “Expert (3)” with the drop-down menu.

1.1.4 Execute the following steps in the parameter list of the CU

-> p4690: Enter the new component number. In this case 205 and then press the
10. ENTER key.

-> p4691: Select the entry [30] „Delete SMI data“ with the drop-down menu. After then press
11. the ENTER key.

-> p4691: The parameter changes to [35] „Confirmation of SMI data delete required“ now

-> p4691: With drop-down select [30] „Delete SMI data“ again. After then press then ENTER
12. key again.

-> p4691: Now the following confirmation is shown up [36] „SMI data deleted and POWER
13. ON required for component“

-> POWER OFF / ON

-> The DQ-Module is deleted now.

1.2 Programming of the deleted DQ-Module see chapter 2.

Date: 2012-03-28 EWN ServiceCenter


2. Programming a new / deleted DQ-Module
For programming a new or deleted DQ-Module it has to be connected to a free port so that a
component number bigger then 200 will be created. How to achieve this is described in item
1.1.1 and 1.1.2.

Was the module deleted with item 1 it can be left at once here at this port and the
corresponding component number can be used. In this case #205.

With this component #205 it has to be created a new folder on the CF-Card of the Sinamics.
This folder is named:
USER\SINAMICS\DATA\SMI_DATA_MAN\C205

Both BIN files (at DQi only 1 BIN flie) which were downloaded from the internet site before
have to be stored in this folder. If older bin files are available in this folder they have to be
deleted at first.

Execute the following steps in the parameter list of the CU now.


14.
-> p4690: Enter the new component number. In this case 205 and then press the ENTER
15. key.

-> p4691: Now select the entry [2] „Download SMI data“ with the drop-down menu. After
16. then press the ENTER key.

-> p4691: The parameter changes to [9] „SMI data downloaded and POWER ON required
17. for component“

-> POWER OFF / ON

-> The DQ-Module is programmed now.

At next the DRIVE-CLiQ module has to be connected to the original port 2 and the motor can
run.

Date: 2012-03-28 EWN ServiceCenter