Configurable MCR-FL-C-UI-2UI-DCI
1. Description
• 4-way isolation
• Input, power, output 1, output 2
• Signal conversion and amplification
• Adjustable signal combinations
• 17.5 mm (0.689 in.) ME housing
V, I V, I
V, I
POWER
2. Technical Data
OUT OUT
OUT I2 1 7 OUT I1
A D
OUT U2 2 8 OUT U1
D A
GND 2 3 9 GND 1
IN I 4 0 +24V DC
A
IN U 5 ! GND 4
D
GND 3 6 " GND 4
IN
MCR-FL-C-UI-2UI-DCI
with configurable input and output
8
M3
rigid flexible
[mm2] AWG (A a planned)
Connection data 0.2-2.5 0.2-2.5 24-14
Pcs.
Description Type Order No. Pkt.
MCR signal multiplier,
for splitting and electrical Preconfigured MCR-FL-C-UI-2UI-DCI 28 14 85 4 1
isolation of analog signals Not configured MCR-FL-C-UI-2UI-DCI-NC 28 14 86 7 1
Technical Data
Input
Input signal range 0…24 mA/0…12 V, freely selectable in 0.1 (mA/V) steps
Measuring range span 8 mA/4 V, minimum
Maximum input signal 50 mA or 30 V
Input resistance 50 Ω at I (current) input/200 kΩ at U (voltage) input
Output
Output signal per channel See order key/configuration table
Maximum output signal per channel 35 mA or 15 V
Load per channel ≤ 600 Ω at I (current) output/ ≥10 kΩ at U (voltage) output
General Data
Supply voltage 20…30 V DC
Current consumption (without load) < 25 mA
Transmission error < 0.15% of the final value; 0.05% (typical) of the final value
Temperature coefficient < 0.015%/K, 0.0075%/K, typical
Cut-off frequency (3 dB) 30 Hz
Step response (10 - 90%) 12 ms
Test voltage 1.5 kV AC, 50 Hz, 1 minute
Protective circuit Transient protection
Ambient operating temperature range -20°C to +55°C (-4˚F to +131˚F)
Degree of protection IP 20
Connection method Plug-in COMBICON screw-cage terminal block
Mounting position/mounting Any
Electromagnetic compatibility: c Conformance with EMC Directive 89/336/EEC
• Noise emission EN 50 081-2
• Noise immunity EN 50 082-2
c
Conforms to the EMC Directive 89/336/EEC and the
Low Voltage Directive 73/23/EEC
1
P
4V
O ND 1 GND
W 4
G T
E GN
I
O U
R D
I
4
P
DC
O
W
UI-
E
1
R
I-2
DIP switches R-FL
-C
-U
MC
I
O
U
2
IN
G
N
U
D
2
G
N
D
3
I
DC
1 UI-
I-2 4
2 -U 85
-C 14
3 Metal lock for fastening on the DIN rail 3 -
R :
FL28
MrtC.-Nr.
A OU
T
OU
7 OU
8 GN
9
D A
T 0
4 OU
!
5 "
6 A
D
1
I2
2
U2 7
3
2 D
2
4
A
D
OU
T
T
I1
U
1
8
9
5 OU 1 10
6 D
IN GN DC 1
I2 2 4V 1
T +
OU 2
D
4
1 U 12
T GN
OU 4
2 2 D
D GN
GN
3 L S
I VA
IN P RO
4 U AP
IN /
5 3 N
GN
D NE
IO
6 AT
OB
PR
AP
Fig. 06
3. Configuration
C
-D
UI
I-2
-U
L-C
R -F
3.1. Opening the Device (Fig. 07) MC
O U
U
T
I
2
IN
using a screwdriver 1. The housing cover and
G
N
U
D
2
G
N
D
3
electronics can now be pulled out about 3 cm 1
(1.181 in.) 2. 2
3 FL
R-r.:
MrC
t.-
N
A
4
5
6 N
I I2
T
OU 2
1 U
UT
O
2 2
D
GN
3
I
IN P
4 U AP
IN /
3
5 D EN
Fig. 07
3.2. Setting (Fig. 08)
Modifications to the ordered connection method
settings are made via DIP switches S1 through S10.
Configuration S10 7
Via DIP switches OFF 6 Output 1: Setting the
Signal ranges preset by factory ON 5 output signal ranges
4
Input (IN) S1 S2 S3
3 Setting the
0…20 mA OFF OFF OFF input signal range
2
0…10 mA OFF OFF ON
1
4…20 mA OFF ON OFF
2…10 mA OFF ON ON
0…10 V ON OFF OFF
1…5 V ON OFF ON
Fig. 08
0…5 V ON ON OFF
2…10 V ON ON ON
The current and voltage channel can be used in
parallel at each output so that up to four signal outputs
with full load capability are provided.
Please note: Where possible, output 1 should be
used as a current output.
Output: Output 1 Output 2
Current/Voltage (OUT 1) (OUT 2)
Signal
S4 S5 S6 S7 S8 S9
0…20 mA / 0…10 V OFF OFF OFF OFF OFF OFF
0…20 mA / 1…5 V OFF OFF ON OFF OFF ON
0…20 mA / 0…5 V OFF ON OFF OFF ON OFF
0…10 mA / 0…5 V OFF ON ON OFF ON ON
4…20 mA / 0…10 V ON OFF OFF ON OFF OFF
4…20 mA / 1…5 V ON OFF ON ON OFF ON
4…20 mA / 0…5 V ON ON OFF ON ON OFF
4…20 mA / 2…10 V ON ON ON ON ON ON
If the value is above or below the measuring range, a
linear transmission response is triggered.
0…10 V
Control system
5. Order Key IN OUT2 MCR-FL-C-UI-2UI-DCI OUT1 POWER
4 I 1 I2 I1 7 +24V 10
POWER
For custom input settings consult factory 5 U 2 U2 U1 8 GND4 11
Ultrasonic transmitter/sensor
MCR-FL-C-UI-2UI-DCI / 1 / 0.0 / 20.0 / 1 / 1
Defult configuration 1 2 3 4 5 4…20 mA 24V
24V
1 Input Signal
1 = I
2 = U AC supply voltage
Input Signal Range
• Measuring range span 8.0 mA/4.0 V, minimum
• Increment 0.1 mA/0.1 V
2 Start Value
I: Freely selectable between 0.0…24.0 mA Fig. 09
U: Freely selectable between 0.0…12.0 V
3 Final Value
I: Freely selectable between 0.0…24.0 mA
U: Freely selectable between 0.0…12.0 V
4 Output 1 5 Output 2
1 = 0…20 mA 1 = 0…20 mA
2 = 4…20 mA 2 = 4…20 mA
3 = 0…10 mA 3 = 0…10 mA
4 = 0…10 V 4 = 0…10 V
5 = 0…5 V 5 = 0…5 V
6 = 1…5 V 6 = 1…5 V
7 = 2…10 V 7 = 2…10 V
http://www.phoenixcon.com
TNR: 5106352-00
June 1, 2001
PHOENIX CONTACT