ETAP

Project: Page: 1
12.6.0H
Location: Date: 21-11-2017
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: MODUL5 Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 150.000 100.000 0.0 0.354 0.227 0 0 Bus2 0.354 0.227 1.6 84.1

Bus2 20.000 99.951 0.0 0 0 0 0 Bus3 0.354 0.227 12.1 84.2

Bus1 -0.354 -0.227 12.1 84.2

Bus3 20.000 99.752 -0.1 0 0 0 0 Bus2 -0.353 -0.226 12.1 84.2

Bus4 0.353 0.226 12.1 84.2

Bus4 20.000 99.554 -0.1 0 0 0 0 Bus3 -0.352 -0.225 12.1 84.2

Bus5 0.176 0.113 6.1 84.2

Bus8 0.176 0.113 6.1 84.3

Bus5 20.000 99.434 -0.2 0 0 0 0 Bus4 -0.176 -0.113 6.1 84.2

Bus6 0.176 0.113 6.1 84.2

Bus6 20.000 99.355 -0.2 0 0 0 0 Bus5 -0.176 -0.112 6.1 84.3

Bus7 0.113 0.072 3.9 84.2

Bus9 0.063 0.040 2.2 84.3

Bus7 20.000 99.265 -0.2 0 0 0 0 Bus6 -0.113 -0.072 3.9 84.2

Bus10 0.113 0.072 3.9 84.2

Bus8 0.400 96.485 -0.9 0 0 0.172 0.107 Bus4 -0.172 -0.107 303.3 85.0

Bus9 0.400 96.616 -0.9 0 0 0.062 0.038 Bus6 -0.062 -0.038 108.3 85.0

Bus10 0.400 96.183 -1.0 0 0 0.110 0.068 Bus7 -0.110 -0.068 195.0 85.0

* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA