AeroDuct program presentation

Ductwork sizing

Jean Yves MESSE - THERMEXCEL

50, rue d'Erevan (Bât. 35 le Capricorne)

92130 ISSY LES MOULINEAUX – FRANCE


ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

AeroDuct program
Characteristics and functions of the program

This calculation program on Excel makes it possible to dimension and carry out the calculation
of the pressure losses on the ductworks and air distribution systems.

AeroDuct can be distributed with calculation in English system (e.g., ounces, pounds, inches,
and feet) and common units in the metric system (e.g., grams, kilograms, meters, and
centimeters). .

It applies in all types of duct and holds account particularly on the operating conditions and
specific Characteristics on the ductworks, such as:

• The temperature of the air conveyed


• The level of altitude or is located the installation
• The nature of the various types of materials used (steel ductwork, copper, PVC, built
walls, etc)
• The geometrical shapes of ductworks (circular, quadrangular, oblong)
• The various types of pressure loss coefficients
• Le contrôle des vitesses silencieuses de passage d'air.
• The control of air speeds.

Complementary modules of calculations are incorporated in the program, such as:

• K-factor editor of the local pressure loss


• Equivalent K-factor calculator.
• Calculator for evaluation of the motorized power of the ventilator, according to the
calculated load.

The calculation program is equipped with a customized command bar giving access to the
various procedures, boxes of calculation and macro commands.

The working files are created separately making it possible to reduce the data storage.

Display of the table of calculation of pressure loss

The working file can be made up of various computation sheets. You can from the same file, to
insert a new computation sheet or to duplicate the computation sheet in progress for the study of
a similar ductwork and to make the complementary modifications thereafter.

If you forget some elements from the ductwork, you can add lines of calculation anywhere,
without deteriorating the phases of calculations.

You can also choose the unit of pressure of your choice in the study:

• Pa (Pascal)
• Pounds per square foot (lbf/sq ft) = 47.88026 Pa
• Torr / mm Hg (133.3226 Pa)

Page : 2 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

• Inches w.g (248.6 Pa)


• kPa ( = 1000 Pa)
• Psi (Pound per square inch (lbf/sq. in) = 6894.757 Pa)

AeroDuct can be distributed with calculation in Metric system or English unit.

For each sheet of the table of calculation, the presentation is done, such as:

In basic display:

The hygienic airflow or smoke extract systems are indicated generally in the standards on a air
mass of reference of 0.0746 lb/ft^3 (1,200 kg/m3) - (equivalent to: 68°F (20°C) - 40%)

The basic airflow is corrected automatically in function:

• Of the altitude of the site.


• Of the leakage rate of air estimated in the ductworks.
• Of the temperature of airflow in the ductwork compared to the basic temperature taken
into account in the calculation of the installation or the airflow of reference.

The real speed of the airflow in the ductwork is carried out from the corrected airflow.

Page : 3 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

A displaying in yellow of the cell concerned indicates speeds of air higher than the quiet values
recommended in the installations at low pressure.

It is highly advised to envisage a coefficient of safety margin:

• The assemblies are often badly carried out, blocking partially the passage of the fluid.
• An estimated dusty ductwork can be considered.
• With the ageing of the ductwork, a possible corrosion can increase the pressure losses by
friction.

In total displaying, the table visualizes in complement:

• Indices of surface roughness.


• The air density.
• The dynamic viscosity of the air.
• The Reynolds number.

All the colour cells of calculation are programmed.

Air speeds recommended

Installations "low pressure" (maximum Speed 1550 to 2000 Ft/min - 8 to 10 m/s)

Airflow in ducts Maximum velocity


- Maxi flow rate < 175 CFM (300 m³/h) 490 ft/min ( 2.5 m/s)

Page : 4 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

- Maxi flow rate < 590 CFM (1000 m³/h) 590 ft/min ( 3 m/s)
- Maxi flow rate < 1200 CFM (2000 m³/h) 785 ft/min ( 4 m/s)
- Maxi flow rate < 2350 CFM (4000 m³/h) 980 ft/min ( 5 m/s)
- Maxi flow rate < 5900 CFM (10000 m³/h) 1180 ft/min ( 6 m/s)
- Maxi flow rate > 5900 CFM (10000 m³/h) 1380 ft/min ( 7 m/s)

Installations "high pressure" (speeds of air > to 2000 ft/min - 10 m/s) - Ejector-convectors,
Variable Air Volume Systems (VAV) or variable Induction units, etc.

Airflow in ducts Shaft Corridors Premises


- 59000 to 41000 CFM - (100000 5800 ft/min (30
to 70000 m3/h) m/s)
- 41000 to 23500 CFM - (70000 to 4900 ft/min (25
40000 m3/h) m/s)
- 23500 to 14700 CFM - (40000 à 4300 ft/min (22 3940 ft/min (20
25000 m3/h) m/s) m/s)
- 14700 to 10000 CFM - (25000 à 3940 ft/min (20 3350 ft/min (17 3150 ft/min (16
17000 m3/h) m/s) m/s) m/s)
- 10000 to 5900 CFM - (17000 à 3350 ft/min (17 2950 ft/min (15 2750 ft/min (14
10000 m3/h) m/s) m/s) m/s)
- 5900 to 2950 CFM - (10000 à 2950 ft/min (15 2350 ft/min (12 2350 ft/min (12
5000 m3/h) m/s) m/s) m/s)
- 2950 to 1200 CFM - (5000 à 2350 ft/min (12 2000 ft/min (10 2000 ft/min (10
2000 m3/h) m/s) m/s) m/s)
- Inferior to 1200 CFM (2000 2000 ft/min (10 2000 ft/min (10 2000 ft/min (10
m3/h) m/s) m/s) m/s)
2000 ft/min (10 2000 ft/min (10 2000 ft/min (10
- Fire dampers
m/s) m/s) m/s)

• It is recommended to leave in the main ducts at a speed of 3940 to 4300 ft/min (20 to
22m/s).
• The main and secondary ducts are generally calculated on a basis of 0.0034 In.wg (0.85
Pa).
• The boxes are selected on the basis of acceptable noise level when the pressure at the
entry of the boxes is of 3 In.wg (750 Pa).
• The reduction speed can cause a renewal speed.

Dual-Duct VAV Systems (average or high pressure)

• The circuit of the cold air ducts is calculated for 100% of the necessary flow.
• On the other hand, for the hot air ducts, one admits 50% to 75% of the cold air flow
according to thermal loads.
• The variation between the temperature of the buildings in summer and the air in the cold
air duct is 50 to 55.5 °F (10 to 13°C).
• In summer, the temperature of the hot air in the duct is maintained at least with +5.4°F (+
3°C) above the average temperature of the air outlet.

Page : 5 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

The air velocity in the ducts cannot exceed a certain value. It results a minimal section of ducts
below from which it is misadvised going down for following reasons:

• Increase the noise of rustle of the air in the strait ducts and especially on the level of the
deviations.
• Increase the pressure losses and the energy consumed by the ventilator.

Example: a reduction in half of the section doubles the air velocity increases the pressure losses
and the absorptive power by the ventilator by a factor 4.

AeroDuct can be distributed with calculation in Metric system or English unit.

K-factor editor for local pressure loss

The program includes 2 procedures placed on customized command bar use to know the value of
the coefficient K.

1° / - Module of imputation on the working sheet of the designation and the value of the K-
factor.

2°/ - Data Visualization Module of the pressure loss coefficients according to the duct shape.

Page : 6 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

Oblong ducts

In the case of oblong ducts.

Page : 7 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

Roughness factors

The index of roughness (k) will be modified directly according to the type of duct employed in
the calculation of the pressure loss with visualization by procedure placed on the customized
command bar.

Equivalent-K calculator

Page : 8 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

Ventilator motor

Page : 9 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

The absorptive energy by the ventilator breaks up into:

Mechanical energy provided to the fluid

It is the communicated power to the air during of its passage through the ventilator.

This mechanical power is given by the following formula:

with:

• P = Power transmitted to the fluid by the ventilator in W (W = 0.736 Cv).


• Q = Flow in m3/s (1 CFM = 0.0004719 m3/s)
• Hm = Air pressure losses in Pa (In.wg = 248.6 Pa).

Degraded energy expressed by the output of the ventilator

It is the power measured on the coupling shaft of the ventilator.

Page : 10 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

Mechanical energy necessary to a ventilator is always higher than the energy transmitted to the
fluid consequently to various frictions of the transmission systems.

With:

• Pmec = Mechanical power necessary to the ventilator.


• Pfl = Power transmitted to the fluid.
• R = Mechanical output of the ventilator.

The generally allowed outputs are:

Ventilator type Outputs


- Centrifugal fan with paddles bent backwards (6 to 16 units) 80…77%
- Centrifugal fan with blades bent forwards (38 to 42 units) 57…73%
- Propeller fan without diffuser but with rectifier 50…88%
- Propeller fan with diffuser and rectifier 60…89%
- Wall ventilator 35…50%

The only types of ventilators, which are appropriate for the installations for constant pressure or
variable air volume, are the centrifugal blades fans inclined backwards and the propeller fans
(curved steeply sloping characteristics)

The Flow Volume cannot be reduced generally to the 1/3, seldom below 50%.

In the contrary case, it is necessary to use engines with progressive regulation, that is to say
mobile blading.

Transmission output

The transmission of the energy of the engine to the ventilator is done with a certain loss, mainly
in the case of a belt drive, because of the slip of the latter on the pulleys.

Mode of drive Losses


- Motor with direct drive (wheel of
ventilator 2 to 5 %
directly fixed on the shaft of the motor)
- Drive shaft 3 to 8 %
- Belt drive P moteur < 5.5 Cv (7.5 kW): 10%
- Belt drive 5.5 Cv (7.5 kW) < P moteur < 8 Cv 11 kW): 8%
- Belt drive 8 Cv (11 kW) < P moteur < 16 Cv (22 kW): 6%
- Belt drive 16 Cv (22 kW) < P moteur < 22 Cv (30 kW): 5%

Page : 11 / 12
ThermExcel – Jean Yves MESSE – 50 rue d’Erevan (35 le Capricorne) - 92130 ISSY LES MOULINEAUX

- Belt drive 22 Cv (30 kW) < P moteur < 40 Cv (55 kW): 4 %


- Belt drive 40 Cv (55 kW) < P moteur < 55 Cv (75 kW): 3 %
- Belt drive 55 Cv (75 kW) < P moteur < 75 Cv (100 kW): 2.5%

Page : 12 / 12