Documente Academic
Documente Profesional
Documente Cultură
Abstract--Nowadays, in Egypt the power electricity demand as voltage fluctuations, phase unbalance, distribution
is increasing continuously and rampant power cuts are a norm, transformer overloading, reactive power compensation,
and the scheduled outages can be as high as 8 hours a day in harmonic injections that detract the overall power quality of the
some parts of the country. During the outages, industries, typical distribution subtropical climate.
commercial establishments and residential consumers tend to use Furthermore, the impacts of solar PV on low voltage distribution
diesel generators, which not only expensive, but also leads to network where loads connected through distribution transformer
pollution. and finally further investigation was conducted with the
One of the main tasks for The Egyptian government is to deployment of energy storage into the respective load centers
generate electricity from renewable energy sources to overcome
this increase in the energy consumption and at the same time Keywords: LV - PV - RTPV – TDL – DT - DN
reduce environmental impact of power generation
New technologies allow the electricity to be generated in small 1. Introduction.
sized plants .Large scale integration of distributed generators at The Egyptian government has proposed a new law to govern
either LV or MV is at the present the trend followed in power the electricity sector. It represents the most recent legal
systems to cover the supply of some loads. These generators are
of considerable smaller size than the traditional generators.
initiative to encourage Renewable Energy use whereas the
So importance of Installation of renewable energy such as roof contribution from Renewable Energy Sources low, by
top solar photovoltaic will be increase. Roof top solar projects are providing subsidies to either the developers who would then
a known phenomenon nowadays. These PV systems offer a great set up installations on rooftops; or to the citizens – who can
opportunity for institutions, industries, and all other buildings then invest in the huge upfront costs required to procure and
already using UPS, inverters, batteries and diesel generators to install a rooftop solar system.[1]
reduce energy costs and to ensure power continuity in the event
of grid unavailability
encouraging Integration of roof-top solar PV for three main
Integration of roof-top solar PV is suitable for use at the low reasons: i) to reduce its dependence on imported fossil fuels,
voltage (LV) level in Egypt where integration can meet ii) to protect the environment, and iii) to contribute to
residential consumers’ needs. So, governments must encourage sustainable development
households to build a sustainable climate-friendly society for the In Egypt, residential buildings are the major consumer of
future and give incentives to the individual owners.., energy, in a country where 45% of the population live in
These small scale rooftop PV (RTPV) systems have some very
obvious advantages, such that , No additional land that could be
urban areas. residential building sector consumed more than
used for other purposes is required for rooftop PV systems, 47% of the total nationally generated electricity.
Huge savings in the Transmission and Distribution losses (TDL), Approximately 11 Million tons of oil equivalents (Mtoe) of
In the other side the uncontrolled and intermittent characteristic energy were consumed by approximately 20 million
of solar PV which causes voltage fluctuation within the network apartments [1]. And electrification has reached 99% of
and this is significant in the single phase PV system connection. households, where 80% of the residential customers use 50%
Also, phase unbalance, loading on the distribution transformer,
power factor, reactive power compensation, and harmonics is
of the total households’ electricity [2].
expected to have greater impacts on distribution network. And The key major barriers to the integration of roof-top solar PV
are the key influences at the point of PV connection that affects systems are the uncertainties in the performance of the low
the power quality of the distribution network. voltage distribution network due to the intermittent nature of
So, this paper discuss The key major barriers to the integration solar PV sources
of roof-top solar PV systems which are the uncertainties in the Rooftop photovoltaic (PV) systems can be hugely
performance of the low voltage distribution network due to the
intermittent nature of solar PV sources.
advantageous for commercial as well as domestic institutions
also, a model was developed to investigate the potential technical which use inverters, diesel generators and other auxiliary
impacts of integrating roof-top solar PV systems into the low sources to diminish energy costs and also guarantee power
voltage distribution network in Egypt and the uncertainties such continuity in the event of faults/ outages it is proposed to have
Rooftop Solar Panels.
With fast growing penetration of PV and other distributed
power generation capacity, the impact of PV on the grid and
2
vice versa is under discussion. So, in this work a model was January April
1200
developed to investigate the potential technical impacts of July October
integrating roof-top solar PV systems into the low voltage 1000
1
0.5 shown in Figure fig (4)
0 Scenario 3: Base case Grid with 100% PV integration
Scenario 4: Grid with 150% PV integration
3- 2 Application:
It was observed from load flow analysis that the voltage level
Day hours
gradually decreases from source or electricity transmitting
point to the receiving point or end load and shown in fig ( 5 )
Fig (1) average load pattern of south delta residential areas That shows the voltage changes of a three-phase balanced
system from the LV side of the transformer to the end busbar
(Busbar 1& 2) for cenario 2. As changes of voltage in
different busbars or node points are the same for all of the
phases. Figure 6 shows Voltage regulation of studied case
scenarios. This figure presents the voltage changes with
respect to nominal voltage at different observation points only
for phase 1as it is a balanced system. It also clearly indicates
that system voltage rises with the increase of solar PV
penetration. PV penetration level is gradually increasing from
3
case 2 to case 4 and voltage of these systems also rises Fig ( 6 ) Voltage fluctuations for different studied scenarios.
gradually. Furthermore Voltage variations over time in the LV
DN and different busbars for case 1 (i.e., without PV
BUS1 BUS2
integration) and case 3 (i.e., 100% PV of total loading) are
BUS3 terminal
shown in Figures 7 and 8 respectively. These figures also 100.5
indicate that the receiving end voltage of the system is lower 100
than the sending end voltage. Figure 8 shows that the middle 99.5
of the day voltage increases notably corresponding to
99
maximum generation from PV with minimum household
98.5
demand. Also, from power flow analysis as depicted in Figure
9, it can be seen that, for scenario 1, i.e., without any PV 98
generation the grid needs to supply 110 kW active power with 97.5
70 kVar reactive power to fulfill household load demand, 97
while in scenario 4, the system, after meeting household
demand, has surplus electricity of 60 kW that is feeding back
to the grid. Also, Figure 9 illustrates Current harmonics
emissions in the DT, for all cases and it is clear that case 2 and
3 exceed the regulatory standard limit, moreover Current
harmonics emissions in the DT, Busbar 1, Busbar 2, and Fig ( 7 ) Load curve –bus voltage . scenario 1.
Busbar 3 are shown in Figure 10, it can be seen that harmonic
emissions for case 4 is reduced to 11.1% as this system
Terminal BUS1
generates PV power greater than the household load and
causes reverse power flow in the system by feeding back BUS2 BUS3
100.5
surplus electricity to the grid. Also, current harmonic
distortion across the DT is maximum (12.5%) for scenario 3 100
and minimum (6 %) even though both of the systems have the 99.5
same solar PV generation with similar household load
demand. 99
98.5
120
% Of nominal voltage
98
100
97.5
80
97
12:00:…
2:00:0…
4:00:0…
6:00:0…
8:00:0…
10:00:…
12:00:…
2:00:0…
4:00:0…
6:00:0…
8:00:0…
10:00:…
12:00:…
60
40
20
0 Fig ( 8 ) Load curve –bus voltage . Scenario 3.
bus62
Bus 55
Bus 56
Bus 57
Bus 58
Bus 59
Bus 54
Bus 53
Bus11
Bus10
Bus27
Bus2
Bus3
Bus4
Bus5
Bus8
100
Fig (5). Voltage fluctuations in 2 busbars for scenario 2.
50
Series1 Series2 Series3
P 0
Series4 Series5
100.5 Scenario S1cenario S2cenario S3cenario 4
Q -50
100
% of nominal voltage
99.5
-100
99
98.5
98 -150
97.5
97
96.5 Fig (9) Active and reactive power of balanced roof-top solar PV systems.
scenario 1 scenario 2 scenario3 scenario 4
4
15
10
%THD
0
DT BUS1 BUS2 BUS3
5- CONCLUSION
. Integration of PV in the system causes bi-directional power
flow at the point of connection which also increases the
voltage level of the studied system. In case 4, 150% PV of
total loading is injected which increases the voltage
level equal to the nominal voltage as households generate
more power than they require and are feeding back the surplus
electricity to the grid. However, voltage significantly drops for
flow study only gives the maximum voltage of the feeders,
however load curve analysis show the voltage variation over
time of the feeders. Also it is observed that The harmonic
currents which represent the net balance of the total
current of inverters and the connected domestic loads from
homes. All harmonic current levels stay well below the
permissible limits. in casesof high production of PV some
voltage harmonics were found.
6- REFERENCES
[1] Cobben, B. Gaiddon, and H. Laukamp, "WP4 – Deliverable 4.3- Impact
of Photovoltaic Generation on Power Quality in Urban Areas with High
PV Population," EIE/05/171/SI2.420208, 2008.
[2] R. M. ElShazly " “Feasibilty of Concentrated Solar Power Under
Egyptian Conditions” Master's Thesis , 2008
[3] http://www.google.co.in/#output=search&sclient=
psyab&q=India%27s+PPP+Model+for+rooftop+solar+programme&oq=
India%27s+PPP+Model+for+rooftop+solar+programme&gs_l.
[4] Masters M Gilbert 2004 Renewable and Efficient Electric Power Systems
John Wiley & Sons.
[5] J. Scheffler; Bestimmung der maximal zulنssigen Netzanschlussleistung
photovoltaischer Energiewandlunganlagen in Wohnsiedlungsgebieten
(Determination of the maximum permissible power capacity of PV