Sunteți pe pagina 1din 11

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

Analysis of Resonance between a VSC-HVDC


Converter and the AC Grid
Changyue Zou, Member, IEEE, Hong Rao, Senior Member, IEEE, Shukai Xu, Member, IEEE, Yan Li, Member, IEEE,
Weiwei Li, Member, IEEE, Jun Chen, Member, IEEE, Xiaobin Zhao, Yu Yang, Bo Lei

 connecting to 525 kV ac grid through a transformer, thus


Abstract — A 1270 Hz resonance happened between ±350 facing much higher reliability requirement. Last year, a 1270
kV/1000 MW Luxi Back-to-Back VSC-HVDC converter and Hz resonance happened between Luxi VSC-HVDC and the
the 525 kV ac grid after disconnection of several ac ac grid with the 1270 Hz phase-to-ground voltage reaching
transmission lines. To understand the resonance and find a 68.9 kV. Although the power transmission and system
solution, the impedance-based stability analysis model
stability were not interrupted, the resonance must be dealt
considering different equipment is first established. Then the
resonance is analyzed and repeated in the simulation based on
with.
the established model. The system stability can be judged by The system stability of small-scale inverter has been
the ratio of grid impedance to the equivalent impedance of all widely studied. For inverters with LCL-type filter, the
parallel connected equipment with the converter. To evaluate oscillations effect of LCL filter may lead to system
the occurrence and risk of resonance, the frequency range instability. Generally, the system stability can be evaluated
where the impedance has a negative-real-part has been by the loop gain using Bode diagram or Nyquist stability
searched and studied. In order to narrow the criterion. To stabilize the system, passive damping [6-8] or
negative-real-part region to avoid potential resonance, active damping methods [9-12] are proposed to damp the
solutions such as control strategy improvement, passive or
inherent resonance. The main defects of passive damping
active impedance adapter may be applicable and are discussed.
For a complex system containing various equipment, the methods, i.e. inserting a resistor in the filter, is the increment
equipment can be divided into several subsectors to avoid of loss and cost which is unlikely to be applied in high
modeling all possible combinations of equipment, which can be voltage large-capacity VSC-HVDC systems as a slight
exhausted. And analysis has shown sufficient but not necessary efficiency decrease will result in a considerable power loss.
condition to stabilize the system is to avoid negative-real-part On the other hand, the active damping methods may fail or
region in each sector. even deteriorate system stability after taking delay time into
consideration which has led to the proposal of active
Index Terms—Resonance, Impedance, Stability, HVDC damping with reduced delay [13]. However, delay time of
transmission VSC-HVDC system is much longer than that in small-scale
converters, e.g. 400 ~ 600 μs, and is difficult to reduce,
especially in existed systems. The influence of grid
I. INTRODUCTION impedance is ignored or modelled together with the

M odular Multilevel Converter (MMC) has been widely


used in high voltage dc transmission (HVDC) system
thanks to its modularity, strong expansibility, and low
grid-side inductance in above-mentioned papers. But for
VSC-HVDC connected to HVAC system, it is hard to model
them together as the grid impedance is usually quite
harmonic injection characteristics. The voltage source complicated. Furthermore, the grid impedance can vary
converter (VSC) based HVDC (VSC-HVDC) has recently greatly along with grid operation mode. Considering the
attracted attention of researchers and been branded a highly changing nature of grid operation mode, it is hardly
available technology [1-5] in engineering field with applicable to consider all operation modes and repeat the
numerous VSC-HVDC projects being planned or stability analysis.
constructed worldwide. China has also experience the Another analytical procedure is to consider the inverter
growth in VSC-HVDC projects, including the ±30 kV/18 and the grid separately, e.g. the impedance-based stability
MW Nanhui project, the ±160 kV/200 MW Nan`ao criterion [14, 15]. Impedance-based stability criterion is
multi-terminal project, the ±200 kV/400 MW Zhoushan established in [14], conclusions show that resonance
multi-terminal project, the ±320 kV/1000 MW Xiamen between grid-connected inverters and the grid can be studied
project, the ±350 kV/1000 MW Luxi back-to-back project. by applying the Nyquist stability criterion to the ratio of grid
In addition, the ±500 kV/3000 MW Zhangbei DC-grid impedance and inverter impedance [16]. This method can be
project and the ±800 kV/3000 MW/5000 MW Wudongde applied to analysis where the ac system is complicated and
multi-terminal LCC-VSC- UHVDC project have finished hard to model together with the inverter as well as dc-side
feasibility study and will soon head to next phase. stability analysis [2]. Concentrating on the ac impedance
With the dc voltage growing from 30 kV to 800 kV and characteristic of VSC, professor Lennart Harnefors has
capacity from 20 MW to 5000 MW, the VSC-HVDC has systematically studied the influence of the inner current
become a common part of the main grid, typically controller and the outer loops controllers, e.g. phase-lock
loop, direct-voltage controller, alternating-voltage controller
_________________________________ [17-21]. The system stability above the Nyquist Frequency
is furthered assessed in [22] by revisiting the modelling of
The authors are with State Key Laboratory of HVDC, Electric Power current control loop, especially the pulsewidth-modulation
Research Institute, China Southern Power Grid, Huangpu District,
Guangzhou City, 510080, P. R. China. (E-mail: zoucy@csg.cn; and sampling process. Research results showed that the
raohong@csg.cn; xusk@csg.cn; liyan@csg.cn; liww@csg.cn; instability phenomena should not occur in frequencies where
chenjun2@csg.cn; zhaoxb@csg.cn; yangyu@csg.cn; leibo@csg.cn).

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

the ac impedance of VSC has a positive-real-part [18]. analyzed in this paper. Generally, a transformer is necessary
Different methods of reshaping impedance to get a positive to match the ac and dc voltage and to satisfy the safety codes
real part in the desired frequency regions by adjusting the in ultra-high voltage system. Therefore, when modeling at
controller parameters are provided in [17, 20]. By reducing the primary side, the VSC-HVDC is equivalent to an
total delay time to 0.5Ts, a positive-real-part of the inner ac inductor, its value is
impedance is guaranteed [18] and the value considered in Larm U H2
[19, 20] is 1.5Ts. The delay time has a great influence on LVSC   2  Lleakage (1)
impedance characteristics [23] and longer delay time could 2 UL
deteriorate the system stability. This feature is more obvious where Larm is the arm inductance, Lleakage is the leakage
in VSC-HVDC case as the delay can be as long as 4 Ts to 6 inductance of the transformer at primary voltage side, UH
Ts. and UL are the primary and secondary voltage of the
There are mainly two differences between VSC-HVDC transformer, respectively. The ac-side modeling of MMC
and small-scale inverters: 1) The control delay is much VSC-HVDC is similar with that of 2-level inverter with
longer, e.g. 400~600 μs, and damping strategies should be L-type filter.
redesigned; 2) The impedance of high voltage ac grid, e.g. In VSC-HVDC, the direct current control is widely used,
525 kV, may vary between capacitive and inductive when the VSC-HVDC projects with indirect current control are
operation mode changes. Such characteristics should be not discussed in this paper. The active and reactive current
considered and evaluated in system stability analysis. The reference generally come from outer loop control. Different
operation experience has shown that resonance can happen. outer loop control configuration is possible, for example, the
The paper is organized as follows. The ac-side modeling of dc voltage control for Id and the reactive power control for Iq
VSC-HVDC and impedance-based stability criterion deployed in the sending terminal, the active power control
considering multi-inverters and passive elements are for Id and reactive power control for Iq applied in the
established in Section II. The characteristic of grid receiving terminal. The bandwidth of outer loop and
impedance and VSC-HVDC impedance in the high-voltage phase-lock loop is quite low and the influence are ignored to
application are introduced, the mechanism of resonance are concentrate on the main influencing factor. The ac
analyzed and discussed in Section III. The solutions are impedance modeling considering outer loop, phase-lock
discussed in Section IV, particularly, the simplified method loop can be found in [15, 17, 26, 27]. Considering only the
for stability analysis when lots of equipment are included is feedforward control and current inner loop control, the
introduced. Finally, Section V draws a conclusion. simplified control strategy is shown in Fig. 2.

+
SM SM SM SM SM SM

SM SM SM SM SM SM

UH UL Larm Larm Larm Larm Larm Larm


A UL UH
B
G C Udc A
B G
C
Larm Larm Larm Larm Larm Larm

SM SM SM SM SM SM

SM SM SM SM SM SM

Fig. 1 Topology of the discussed VSC-HVDC

Gd2 Ugrid
II. AC IMPEDANCE OF VSC-HVDC AND SYSTEM STABILITY Iref + - Iout
GPI Gd1 KPWM 1/sL
CRITERION -
A. AC-side Modeling of VSC-HVDC
A half-bridge based back-to-back VSC-HVDC topology Fig. 2. Simplified control strategy applied in Luxi Back-to-back
is shown in Fig. 1. Thanks to the multilevel characteristics, VSC-HVDC
no ac filter is necessary except for the arm inductor. Thus,
the VSC-HVDC can be modeled as an inductor, which is The output current is given by
equal to half of the arm inductor Larm [24]. The AC I out  AI ref  U grid / Z active
impedance modelling of VSC with LCL filters can be found
in [23]. Recent research [25] showed that the dynamic GPI Gd 1 U grid
 I ref  (2)
behavior of sub-modules can affect MMC model at low sL  GPI Gd 1 sL  GPI Gd 1
frequencies. The model in high-frequency range is not as 1  Gd 2
sensitve and are ignored as high-frequency resonance is

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

where A is the closed loop transfer function, Zactive is the ac


impedance of the VSC, also known as input impedance for Iout
the sending terminal or output impedance for the receiving Zactive
terminal. GPI is the PI controller of the current control loop,
KPWM is the modulation factor, which is 1 here. Gd1 and Gd2 AIref
are the delay in forward and feedforward path, respectively. Fig. 3 ac-side Equivalent model of VSC-HVDC
And
When ignoring the outer loop, Iref includes only fundamental
Gd 1  e  sTd 1
 (3) reference, and is open loop for harmonics. The ac impedance
 sT
Gd 2  e d 2 can vary if outer loop is considered. The outer loop is
where Td1 and Td2 are the time delay in forward and ignored in this paper as bandwidth of outer loop is much
feedforward path, respectively. Generally, Td1=Td2, but they lower and contributes a little to harmonics, especially
high-frequency harmonics.
can be designed to be different[28].
GPI Gd 1  GPI Gd 1
Gopen  (4)  A  sL  G G
sL  PI d 1
 (7)
In order to keep the VSC-HVDC stable when connected Z sL  GPI Gd 1

to an ideal voltage source, the phase margin should be  active 1  Gd 2
greater than zero. The control bandwidth can be estimated as
follows. The phase of sL is , the phase of GPI vary from B. Impedance-based System Stability Analysis
-to 0. The phase of Gd is The ac side of the converter, whether the sending or
Gd1  2 fTd1 (5) receiving terminal of VSC-HVDC, can be substituted by a
To get a /4 phase margin, the maximum crossing Norton branch when the current inner loop is applied. By
frequency is estimated without consideration of phase substituting the ac grid by a Thevenin branch,
correction control: impedance-based system stability analytical model is
  1 obtained, as shown in Fig. 4. To make the analytical model
PM   +GPI  Gd 1   sL   f c  GPI + (6) universal, more than one converter is considered. In the
4 2 Td 1 8Td 1
figure, Zg represents grid impedance, Zactive_n, I0_n are the ac
where PI, Gd1, sL are the phase of PI controler, Gd1 and sL, impedance and the equivalent current source of nth
PM is the phase margin. converter as deduced in Fig. 3. As ac filters are connected to
When Td1=100 μs, fcmax =1.25 kHz. When Td1=600 μs, the 525 kV grid in LCC-HVDC stations and high voltage
fcmax=208.3 Hz. The maximum crossing frequency is inductor are frequently used to adjust the reactive power
estimated supposing GPI is zero, i.e. the corner frequency of when necessary, passive elements are also included in the
PI controller is much smaller. In engineering applications, model.
the crossing frequency can be even smaller to get a larger For ac grid branch
phase margin. The time delay in high-voltage converters is VPCC  Vgrid
much longer than that of small-scale systems due to the I PCC = (8)
complexity of controlling several thousand MMC modules Zg
and multilevel control structure. Typical time delay can For converter branch
include the following parts. VPCC
a. Sampling of high-voltage current and the tranmitting In  I0 _ n  (9)
Z active _ n
the measuring data to pole control, 76 μs.
b. Trasmitting the data inside the pole control, 20 μs. IPCC
c. Filtering and synchronization of the measureing data,
90 μs. +
Zg
d. Fulfilling pole control, 100 μs. VPCC I
passive_1
e. Trasmitting modulation wave from pole control to Vgrid -
valve control, 64.8 μs.
f. Trasmitting the data inside valve control, 10 μs. Zpassive_1
I1
g. Fulfilling the valve control, 100 μs.
h. Sorting algorithm doing by FPGA and send to the Zactive_1
distributed board. 50 μs I01
i. Distributing driving signals, 20 μs.
Part of the delay can be reduced or eliminated by using Ipassive_n
faster CPU, better communication technology or improved
sequential logic, but time delay in VSC-HVDC is much In Zpassive_n
lager than that of small-scale converters. The long delay Zactive_n
greatly limits the bandwidth of VSC-HVDC systems I0n
although the controlling and sampling frequency is as high, Fig. 4. Impedance-based system stability analytical model
10 kHz for example.
According to equation (2), the VSC-HVDC can be The controlled current source I0_n and Zactive_n is related to
modeled as a Norton branch judging from the ac side, as the control strategy of the converter. For passive branch
shown Fig. 3, where A and Zactive are given by (7).

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

VPCC and resonance frequency can vary along with the operation
I passive _ n  (10) mode. It’s hard to keep the magnitude of Zactive larger than Zg
Z passive _ n
at all frequencies, especially when the short circuit ratio
Applying KCL theorem, we get (SCR) is small. Therefore, the magnitude condition
 I n =I PCC   I passive _ n (11) discussed in Section II.B is hardly applicable in large-scale
Therefore, the PCC voltage is obtained VSC-HVDC projects.
As for the phase condition, the grid impedance can be
Vgrid +Z g  I 0 _ n inductive or capacitive, i.e. imaginary-part of Zg can be
VPCC = (12)
Zg Zg positive or negative. It is impossible to ensure that the
1   imaginary part of Zactive and that of Zg have the same polarity
Z passive _ n Z active _ n
as polarity of Zg change frequently along with operation
The system is stable provided that all the poles of equation mode. Fortunately, without considering VSC-HVDC and
(12) are in the left-half plane. I0_n have no right-half plane distributed power generation system (DPGS), the real-part
pole, otherwise, the corresponding converter is unstable of Zg is always positive. As a result, the stability can be
even when connecting to an ideal ac grid. Similarly, Vgrid unconditionally guranteed when Zactive has a
and Zg have no right-half plane pole. Consequently, the positive-real-part for all frequencies.
system stability can be judged by applying Nyquist stability Grid Impedance
criterion to part of the denominator, i.e. MW
Zg Zg Zg
Gstability   
LuXi
= (13) BS
Z passive _ n Z active _ n Z eq
290 km 112 km
where Zeq is the impedance of all the parallel connected
elements YA

84 km
Passive Element

1
Z eq  (14) WP
1 1
Z 
Z active _ n
Fig. 5 The ac network of Guangxi-side of Luxi district
passive _ n

When more than one active or passive elements are 10000


When Red dashed lines are out of service
connected at PCC in parallel, the system stability can be
Magnitude/Ω

judged by the ratio of grid impedance to the impedance of all


the parallel connected elements. When only one converter 5000
When ALL lines are in service
and no passive element is connected to the grid, the stability
transfer function is simplified as
0
Zg Zg
Gstability   (15) 100
Z active sL  GPI Gd
50
Phase/°

1  Gd
0
According to Nyquist Stability Criterion, there are two
typical sufficient but not necessary conditions to keep -50
system stable. -100
The first one is the phase condition, i.e. the system is 0 500 1000 1500 2000 2500
stable if the phase difference of Zg and Zeq is smaller than Frequency/Hz
180°for all frequencies. It means that the stability can be
Fig. 6 Scanned ac grid impedance in two different operation modes
guranteed if the real-part or imaginary-part of Zg and Zeq has
the same polarity for all frequencies.
The second one is the magnitude condition, i.e. the system B. VSC-HVDC ac Impedance Verification
is stable if the magnitude of Zg is smaller than Zeq for all To verify the ac impedance analytical results given by
frequencies, wihch guranteed the magnitude of Gstability equation (7), the VSC-HVDC ac impedance is scanned in
always smaller than 0dB. EMTDC/PSCAD. The control strategy, control parameters
such as time delay, and transient processing logic are the
III. RESONANCE BETWEEN THE VSC-HVDC AND AC GRID same as that in the project. An ideal small harmonic voltage
A. Characteristic of ac Impedance of high voltage ac grid source is connected in series with a 525 kV/50 Hz ideal
voltage source, and the simulation is repeated in a series of
The structure of 525 kV ac grid at Guangxi-side, where
frequencies to get the scanned ac impedance curve. The key
the resonance discussed in this paper occurred, is shown in
parameters and corresponding value of the VSC-HVDC
Fig. 5. The detailed modeling of the ac network is out of this
project are listed in Table I. The scanned and analytical ac
paper’s scope, as a result, the grid impedance are scanned
impedance are illustrated in Fig. 7.
and given here. The grid impedance scan method can be
The phase of VSC-HVDC ac impedance is above zero
found in [29]. The scanned results illustrated below are used
except for the frequencies lower than 200 Hz, i.e. the
to show characteristics of the grid impedance vividly and are
VSC-HVDC impedance shows inductive characteristic for
not used for further study. The grid impedance when all ac
mid- and high-frequencies. Therefore, no high-frequency
lines are in service and when the dashed red-lines are out of
resonance will happen if the grid remains inductive.
service are scanned and shown in Fig. 6.
Generally, the grid impedance is simplified as an inductor
According to the scanned grid impedance result, the
connected in series with a resistor during design of control
magnitude of Zg can be very large at resonance frequencies

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

strategy and high-frequnecy resonance should not happen TABLE I


PARAMETERS AND VALUES OF LUXI VSC-HVDC
under such assumption. To analyze and detect the
high-frequency resonance phenomena, the grid impedance Parameters Value
should not be modelled as a resistor-inductor branch. Proportional Gain of Current Controller 50
The system stability is guranteed if the real-part of Zactive Integral Gain of Current Controller 500
is positive for all frequencies. However, Zactive has a
negative-real-part in quite a large range, which may cause Arm Inductor (Larm/H) 0.14
instability while the phase difference between Zg and Zactive Control Delay in Forward Path(Td1/μs) 600
is greater than 180°. Control Delay in Feedforward Path(Td2/μs) 600
C. High-Frequency Resonance Simulation DC Voltage(Udc/kV) 700
To verify the high-frequency resonance analytical result, Capacity (Per phase/MVA) 375
a simulation is conducted in EMTDC/PSCAD v4.6. The grid Primary Voltage(UH/kV) 525
impedance is simulated by an inductive branch connected in Transformer
Secondary Voltage(UL/kV) 375
parallel with a capacitive branch, as shown in Fig. 8. The
parameters of Zg are listed in Table II, where L and R1 are the Leakage Inductance(%) 14
parameters of a weak ac grid when parasitic capacitance is
TABLE II
ignored. The parameters of VSC are listed in Table I. PARAMETERS AND VALUES OF GRID IMPEDANCE IN SIMULATION
The grid impedance and ac impedance of VSC are
Parameters Value
illustrated in Fig. 9(a), there are two amplitude intersections
at 276 Hz and 1252 Hz. For the latter one, the phase Inductance(Lg/mH) 169.3
difference of Zg and Zactive is -196°. The ratio Zg/Zactive cross Resistance of inductor branch(R1/Ω) 8.4
over -180° from upper to lower when the magnitude is Capacitance(Cg/μF) 0.2
above zero, i.e. the system is unstable. The simulation result Resistance of capacitor branch(R2/Ω) 171.0
is shown in Fig. 10(a), the FFT analysis of phase B current is
shown in Fig. 10(b), the 1250 Hz harmonic current gets
larger gradually and will finally trip the system. By reducing Lg R1
R2, the harmonic increasing rate gets larger. At 2.8 s, the VSC-
capacitive branch is disconnected by a breaker, the harmonic HVDC
disappears immediately, as shown in Fig. 10(c). At 1250 Hz, Model
the real-part of Zactive is negative, which is a necessary Cg R2
condition to destabilize the system. By adjusting parameters Fig. 8 Grid Impedance Structure
of Lg and Cg, the resonance frequency can be designed in the
simulation. In indsturial applications, the grid impedance 6000
AC Impedance of
Grid Impedance
Magnitude/Ω

changes along with operation mode, but only limited cases VSC-HVDC
4000
are included in the analysis. However, by eliminating
negative-real-part region, an unconditionally stability can be
2000
guranteed. 276 Hz
1252 Hz
0
4000 200
135.2° Negative-real-part
Magnitude/Ω

3000 Region
Phase/°

Sca nned AC 87.8°


100
2000 Impedance
0 25.4°
1000 Analytical AC
Impedance -60.8°
0 -100
500 1000 1500 2000 2500
Frequency/Hz (a)
200
5000
Phase/°

100
Magnitude/Ω

0 0
276 Hz 1252 Hz
-100

100 500 1000 1500 2000 2500 -5000


Frequency/Hz
Fig. 7 The Comparison of Simulated and Analytical ac Impedance of 100
VSC-HVDC
0
Phase/°

-100

-200
-180°
-300
500 1000 1500 2000 2500
Frequency/Hz (b)
Fig. 9 Impedance Analytical Result: (a) Zg and Zactive; (b) The ratio of Zg and
Zactive.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

long delay as discussed in Section I.A, which makes the


magnitude GPI smaller than sL. The magnitude comparison
of sL and GPIGd is shown in Fig. 11. Consequently, the
influence of Td1 is also limited. The Bode diagram of Zactive
considering different Kp and L are depicted in Fig. 12. The
magnitude changes nearly proportional to L, but the
negative-real-part region rarely changes when Kp or L
changes. The similar analysis can be done to Ki and Td1 and
similar conclusions are drawn. This is resoanalbe as control
bandwidth is limited by the long delay, and the PI controller
rarely responds to high-frequency signals, thus the Zactive has
a low correlation with PI controller and Td1.
4000

3500

(a) 3000
Fundamental (50Hz) = 148.9 , THD= 19.19%

Magnitude/Ω
2500
15
2000
Magnidute of sL
Mag (% of Fundamental)

1500
10
1000

500 Magnidute of GPIGd


5 0
0 500 1000 1500 2000 2500 3000
Frequency/Hz
Fig. 11 Magnitude Comparsion of sL and GPIGd
0
0 500 1000 1500 2000 2500 10000
Frequency (Hz)
Magnitude/Ω

(b)
200
5000
150

100 0
Phase B Current/A

200
50
Phase/°

0 100
Kp=25
Kp=75
-50 0
Kp=50
-100
-100
500 1000 1500 2000 2500 3000
-150 Cut the Capacitor-Resistor Frequency/Hz
Branch (a)
-200 Bode Diagram
2.76 2.78 2.8 2.82 2.84 5000
t/s
Magnitude (abs)

4000 L=0.42 H
(c)
Fig. 10 Simulation Result: (a) the grid voltage and the output current of 3000
VSC; (b) The FFT analysis result of phase B current; (c) Cut the L=0.21 H
Capacitor-Resistor branch at 2.8 s. 2000

1000
L=0.105 H
0
D. Negative-Real-Part Region Analysis 180

Focusing on the negative-real-part region, parameters 135


Phase (deg)

sensitivity of Zactive can be conducted. According to equation 90


(7) 45
sL  GPI Gd 1 0
Z active ( ) 
1  Gd 2 -45
500 1000 1500 2000 2500 3000
K (16) Frequency (Hz)
j L  ( K p  i )(cos(Td 1 )  jsin(Td 1 )) (b)
j Fig. 12 ac Impedance. of VSC-HVDC considering different Kp and time
=
1  cos(Td 2 )  jsin(Td 2 ) delay Td2: (a) Different Kp, (b) Different L

The ac impedance of VSC-HVDC is affected by inductor


The Zactive when Td2 is 600 μs and 200 μs are calculated
L, PI controller parameters, delay time Td1 and Td2. The
and depicted in Fig. 13(b). There are more than one
influence of GPI is limited as controller parameters are
resonance peaks in Zactive and the resonance frequencies fr are
limited by the phase margin requirement considering the

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

n/Td2, where n is integrals. The negative-real-part region grid in face of serious regional frequency imbalance.
changes completely when Td2 changes. Although VSC-HVDC is capable of bidirectional power
The variation of the denominator of Zactive is cycled with transmission, the main purpose of the project is transferring
frequency 1/Td2, but the numerator gets larger along with power from Yunnan-side to Guangxi-side.
frequency. The smaller the time delay Td2 is, the higher the VSC VSC
first resonance frequency 1/Td2 is, making magnitude of
Zactive inside the first negative-real-part region larger. As a Yunnan LCC LCC Guangxi
result, the resonance is less likely to happen because
LCC LCC
|Zg|/|Zactive| is more likely to be smaller than 0dB. Although
increasing L is also helpful, the increment of cost might not
Fig. 14 Three back-to-back HVDC is built in parallel in Luxi station
be appreciated.
The negative-real-part region of Zactive is highly related to
delay in feedforward path, the conclusion is correct when During the operation of the project, a 1270 Hz resonance
instantaneous feedforward control is applied as the occurred at Guangxi-side. The LCC-HVDC, the related ac
feedforward control reacts to high-frequency signals. filters are not in service when the resonance happened. The
Consequently, one of the solutions is to add a low-pass filter ac lines in the area are mostly out of service when the
in the feedforward path to narrow the negative-real-part resonance happened, as the red dashed lines shown in Fig. 5
region, this will be discussed in the following section. and the short circuit capacity is about 3.3 GVA. The
By conducting negative-real-part region analysis, the harmonic keeps growing after the ac lines are cut off and
major cause triggering the resonance could be found. then maintains at a certain level instead of making the
Effective solutions could be found thereafter. system unstable directly. Some unknown nonlinear factor is
Bode Diagram thought to have stopped the harmonic from getting larger.
5000
Td2=600 ms
The harmonic disappeared after the VSC-HVDC tripped.
4000 The grid voltage and the output current of VSC when
Magnitude (abs)

3000
resonance maintained is shown in Fig. 15(a), the FFT result
of phase B current in depicted Fig. 15 (b). The 1270 Hz peak
2000
value of phase-ground voltage and phase current has reached
1000
Negative-real-part
as high as 68.9 kV and 60.1 A. This is the first
0
Region high-frequency resonance case observed in CSG. The
180
high-frequency resonance is a threat to the system operation
135 and should be dealt with.
Phase (deg)

90 According to the observed harmonic, the output


impedance of VSC-HVDC at 1270 Hz is about
45
1145Ω∠133.9°, while the analytical impedance at 1270 Hz
0
1/Td2 2/Td2 3/Td2 is 1281Ω∠137°. The analytical impedance is close to the
500 1000 1500 2000 2500 3000 3500 4000 4500 5000 observed value.
Frequency (Hz) The Guangxi-side ac grid is modeled in PSCAD v4.6, and
(a)
Bode Diagram
similar resonance can happen when the ac lines are cut off.
5000 The resonance frequency is about 1.1 kHz, several reasons
Td2=200 ms
may be responsible for the difference: 1) Only the 220 kV
Magnitude (abs)

4000
and 525 kV ac line are modeled; 2) The parameters of the ac
3000
transmission line may not be precise enough; 3) The ac loads
2000 model are ideal.
1000 Negative-real-part 500
Grid Voltage

Region
0
/kV

180
0
135
Phase (deg)

90
-500
45
200
Output Current

0 1/Td2
of VSC/A

-45
500 1000 1500 2000 2500 3000 3500 4000 4500 5000 0
Frequency (Hz)
(b) -200
Fig. 13 ac Impedanc of VSC-HVDC when: (a) Td2=600 μs; (b) Td2=200μs.
0 0.05 0.1 0.15 0.2
t/s
E. The 1270 Hz Resonance Happened Between the ±350 (a)
KV/1000 MW VSC-HVDC and ac Grid
The Luxi back-to-back station is located at the border
intersection of Yunnan, Guangxi and Guizhou province, and
is consisted of 2 × ±160 kV/1000 MW LCC and 1 × ±350
kV/1000 MW VSC, as shown in Fig. 14. The topology and
control strategy are shown in Fig. 1 and Fig. 2. The project is
built to separate Yunnan grid to the rest of the CSG main

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

Fundamental (50Hz) = 145 , THD= 47.30% acceptable solution from project engineering perspective,
but not an ideal solution as high-frequency resonance may
40 still happen under some specific unpredicted ac system
Mag (% of Fundamental)

conditions as the negatve-real-part region has not been


30 eliminated.
Bode Diagram
4000
Without LP filter

Magnitude (abs)
20 3000
With LP filter
2000
10
1000

0 0
180
0 500 1000 1500 2000 2500
Frequency (Hz) 135

Phase (deg)
(b) 90
Fig. 15 The 1270 Hz resonance occurred in Luxi back-to-back VSC-HVDC: 45
(a) the grid voltage and the output current of VSC; (b) The FFT analysis
result of phase B current. 0
-45
500 1000 1500 2000 2500
Frequency (Hz)
IV. DISCUSSION OF SOLUTIONS (a)
High-frequency resonance could gradually grow into a
severe stability problem for grid operation if neglected. An
acceptable solution must be found, otherwise, further
development and application of VSC-HVDC in bulk power
system will be limited. Although the high-frequency
resonance may happen only under specific ac system
conditions, limiting ac system operation mode is generally
not a good solution as that is against the goal of constructing
HVDC by utilities.
A. Improving Control Strategy
The VSC-HVDC ac impedance is highly related to delay
in feedforward control because feedforward reacts to
high-frequency and can be adverse when the delay is great
enough. A direct and simple idea is to filter high-frequency
(b)
signals in the feedforward path. For example, inserting a 200 Fig. 17 The Verification of Improving Control Strategy: (a) The Bode
Hz low pass filter in the feedforward control, as shown in diagram of Zactive before and after low pass filter is inserted in feedforward
Fig. 16. path;(b) Simulation Result

Gd2 Filter Ugrid Similar solutions can be found, e.g. inserting notch filter
Iref + - Iout in feedforward path can help avoid resonance in a narrow
GPI Gd1 KPWM 1/sL
- frequency range, and therefore self-adapted notch filter may
be a good choice. Such controller improving methods still
need verification before applying in large-scale VSC-HVDC
Fig. 16. Inserting a LP filter in Feedforward Path to Suppress the Resonance systems.

The ac impedance of VSC-HVDC turns to be B. Connecting a Passive Impedance Adapter in Parallel


sL  GPI Gd 1 According to equation (13), the system stability change
Z active  (17) when passive element is connected in parallel, and stability
1  Gd 2G filter
criterion is as follows when one converter and one passive
where Gfilter is the low-pass filter inserted in feedforward element are in service
path. Zg Zg Zg
The Bode diagram of Zactive before and after the filter`s Gstability  + = (18)
Z passive Z active Z passive Z active
insertion is shown in Fig. 17(a). The negative-real-part
region has been greatly narrowed. According to the ac Z passive +Z active
system impedance scan result, no high-frequency resonance To illustrate the influence of passive impedance adapter,
should happen under all possible operation modes for Luxi taking the A-type filter shown in Fig. 18 which used in Luxi
Project. The simulation results are shown in Fig. 17(b), the project as an example, the parameters of the filter are listed
filter is inserted at 2.9 s and the resonance disappears in Table III. The impedance of Zpassive, Zactive and Zpassive //
immediately. Zactive are shown in Fig. 19. The negative-real-part region
This method is applied in Luxi project, numerous disappeared after applying an A-type filter, which
simulations have shown that resonance should not happen guaranteed a good stability performance of the station. It
under all considered ac conditions and no resonance has should be noted that the outer control loops of VSC-HVDC
happened yet after adopting the new strategy. This can be an are ignored, and the VSC-HVDC impedance in

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

low-frequency range may not be accurate. any of the equipment is put into service or cut off. The
For VSC-HVDC station without a passive element, number of equipment combinations can be enormous, thus
inserting a passive impedance adapter may be an option as making analysis quite time-consuming and exhausting. To
the 525 kV passive elements are technically and simplify the analysis, the equipment should be divided into
economically mature for applications. Unlike passive several sectors.
damping methods used in LCL-type filters, well designed In this paper, the whole system is divided into two parts:
passive impedance adapter causes little power loss. the grid (Zg) and the equipment(Zeq) as shown in Fig. 20. For
the equipment, more than two elements are considered.
C1 Dividing the n equipment into m sectors, it can be proven
that
Z Z
iZ A , Z B  (90 , 90 )  Z AB  A B  (90 , 90 ) (19)
L2 R2 Z A  ZB
Consequently, Zeq has a positive-real-part if impedance of
each sector has a positive-real-part. Thus, the state change of
each sector whose impedance has a positive-real-part should
C3 L3
not deteriorate system stability, and the problem is
simplified. By doing so, there is no need to analyze all
possible combinations of the equipment in service. Every
Fig. 18 A-type filter adopted in Luxi Station time an active element is connected, the operator should
check its impedance. During the check, inserting an adaptor
or assigning an element to compose a subsector may be
TABLE III
PARAMETERS AND VALUES OF THE A-TYPE FILTER necessary. For the checked subsectors, there is no need to
Parameters Value
double check again.
For each equipment containing negative-real-part region,
C1/μF 1.3 a new equipment or the existed equipment should be
L2/mH 26.1 assigned to the sector to eliminate negative-real-part region.
R2/Ω 500.0
V. CONCLUSION
C3/μF 2.4
L3/mH 18.8
This paper discusses the resonance between a
VSC-HVDC converter and the ac grid. The system stability
analysis model considering different equipment is
Bode Diagram
4000 established and the system stability is judged by the ratio of
Zpassive Zpassive||Zactive
grid impedance to the equivalent impedance of all parallel
Magnitude (abs)

3000
connected equipment. The 1270 Hz resonance case
Zactive
2000 happened in Luxi VSC-HVDC project is analyzed using the
criterion and phenomena is repeated in the simulation. The
1000
impedance of VSC-HVDC has a neagtive-real-part in
0 high-frequency range due to its instantaneous feedforward
180
135
and long control delay, and such characteristics results in a
high-frequency resonance when several ac lines are cut off.
Phase (deg)

90
45 The negative-real-part region can be used to evaluate the
0 risk of resonance. Improving control strategy, inserting
-45 passive impedance adapter, inserting active impedance
-90
500 1000 1500 2000 2500
adapter may be applicable to narrow or eliminate the
Frequency (Hz) negative-real-part region. The design of high-voltage active
Fig. 19 The Bode diagram of Zactive , Zpassive and Zactive // Zpassive. impedance adapter and control strategy improving methods
need further study.
For a complex system containing lots of equipment, by
C. Connecting a Small-Scale Converter in Parallel dividing them into several subsectors, system stability can
For small-scale converters with a small control delay, its be guaranteed by avoiding negative-real-part region for each
ac impedance can be controlled in a larger frequency range. subsector. By doing so, there is no need to analyze all
Similar to connecting a passive impedance adapter, such possible combinations of running equipment.
method may be applicable. However, connecting a
small-scale converter to 525 kV grid may need a step-up
transformer, which needs be further studied.
D. System Stability when Lots of Equipment Are
Considered
In the analysis above, only the VSC-HVDC and one
adapter are considered. In reality, other equipment besides
the concerned VSC-HVDC and the adapter may exist, e.g.
more than one ac filter could be connected when
LCC-HVDC is in service. The Zeq changes every time when

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

Sector 1 [12] C. Zou, B. Liu, S. Duan and R. Li, “Influence of Delay on System
PCC Stability and Delay Optimization of Grid-Connected Inverters With
LCL Filter”, IEEE Trans. Industrial Informatics., vol. 10, no. 3, pp.
Zg
Z1 1775-1784, 2014.
VSC- [13] D. Pan, X. Ruan, C. Bao, et al., “Capacitor-Current-Feedback Active
Grid Damping with Reduced Computation Delay for Improving
HVDC1
Robustness of LCL-Type Grid-Connected Inverter”, IEEE Trans.
Power Electron., vol. 29, no. 7, pp. 3414-3427, 2014.
[14] J. Sun, “Impedance-Based Stability Criterion for Grid-Connected
Z2 Inverters”, IEEE Trans. Power Electron., vol. 26, no. 11, pp.
Filter 1 3075-3078, 2011.
Example:
[15] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli and Z. Shen,
Z1 (-90°,+90°)
“Inverse Nyquist Stability Criterion for Grid-Tied Inverters”, IEEE
Z2 (-90°,+90°) Trans. Power Electron., vol. 32, no. 2, pp. 1548-1556, Feb. 2017.
Z12 (-90°,+90°) [16] M. Cespedes and J. Sun, “Mitigation of Inverter-Grid Harmonic
Dangerous Range Avoided. Resonance by Narrow-Band Damping”, IEEE Journal of Emerging
and Selected Topics in Power Electronics, vol. 2 no. 4, pp. 1024-1031,
Zn-2 2014.
LCC- [17] L. Harnefors, M. Bongiorno and S. Lundberg, “Input-Admittance
HVDC2 Calculation and Shaping for Controlled Voltage-Source Converters”,
IEEE Transactions on Industrial Electronics, vol. 54, no. 6, pp.
3323-3334, 2007.
[18] L. Harnefors, X. Wang, A. G. Yepes, et al., “Passivity-based Stability
Zn-1 Assessment of Grid-Connected VSC: An Overview”. IEEE Journal of
AC Filter Emerging and Selected Topics in Power Electronics, vol. 4, no. 1, pp.
116-125, 2016
[19] L. Harnefors, A. G. Yepes, A. Vidal, et al., “Passivity-Based
Stabilization of Resonant Current Controllers With Consideration of
Zn High Time Delay”, IEEE Trans. on Power Electron., vol. 29, no. 12, pp.
Voltage 6260-6263, 2014.
Inductor [20] L. Harnefors, A.G. Yepes, A. Vidal, et al., “Passivity-Based
Controller Design of Grid-Connected VSCs for Prevention of
Sector m Electrical Resonance Instability”, IEEE Trans. on Industrial
Electronics, vol. 62, no. 2, pp. 702-710, 2015.
Fig. 20 System Stability Analysis Model [21] L. Harnefors, L. Zhang and M. Bongiorno, “Frequency-domain
Passivity-based Current Controller Design”, IET Power Electronics,
vol. 1, no. 4, pp. 455-465, 2008.
[22] L. Harnefors, R. Finger, X. Wang, H. Bai, and F. Blaabjerg, "VSC
REFERENCES input-admittance modeling and analysis above the Nyquist frequency
for passivity-based stability assessment," IEEE Trans. Ind. Electron.
[1] F. A. R. Jowder and Boon Teck Ooi, “VSC-HVDC station with SSSC vol. 64, no. 8, Aug. 2017.
Characteristics”, IEEE Trans. Power Electron., vol. 19, no. 4, pp. [23] X. Wang, F. Blaabjerg, and P. C. Loh, "Passivity-based stability
1053-1059, July 2004 analysis and damping injection for multiparalleled VSCs with LCL
[2] M. Amin, M.M., J. Lyu and X. Cai, “Impact of Power Flow Direction filters," IEEE Trans. Power Electron., vol. 32, no. 11, Nov. 2017.
on the Stability of VSC-HVDC Seen from the Impedance Nyquist [24] K. Sharifabadi, L. Harnefors, Hans-Peter Nee, et al., “Design Control
Plot”, IEEE Trans. Power Electron., vol. 32, no. 10, pp. 8204-8217, and Application of MMC for HVDC Transmission System”, John
Oct. 2017. Wiley & Sons Ltd , Agu. 2016. [Online]. Available: http://www.
[3] G. P. Adam, I.A., J. E. Fletcher, G. M. Burt, D. Holliday and S. J. wiley.com.
Finney, “New Efficient Submodule for a Modular Multilevel [25] J. Sun, and H. Liu, “Sequence Impedance Modeling of Modular
Converter in Multiterminal HVDC Networks”, IEEE Trans. Power Multilevel Converters”. IEEE Journal of Emerging and Selected
Electron., vol. 32, no. 6, pp. 4258-4278, June 2017. Topics in Power Electronics, vol. 5, no. 4, pp. 1427-1443, 2017.
[4] P. M. Meshram and V. B. Borghate, “A Simplified Nearest Level [26] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli and Z. Shen,
Control (NLC) Voltage Balancing Method for Modular Multilevel “Analysis of D-Q Small-Signal Impedance of Grid-Tied Inverters”,
Converter (MMC)”, IEEE Trans. Power Electron., vol. 30, no. 1, pp. IEEE Trans. Power Electron., vol. 31, no. 1, pp. 675-687, Jan. 2016.
450-462, Jan. 2015. [27] M. Cespedes and J. Sun, “Impedance Modeling and Analysis of
[5] Q. Song, W.L., X. Li, H. Rao, S. Xu and L. Li, “A Steady-State Grid-Connected Voltage-Source Converters”, IEEE Trans. Power
Analysis Method for a Modular Multilevel Converter”, IEEE Trans. Electron., vol. 29, no. 3, , pp. 1254-1261,2014.
Power Electron., vol. 28, no. 8, pp. 3702-3713, Aug. 2013. [28] C. Zou, B. Liu, S. Duan, R. Li. “A Feedforward Scheme to Improve
[6] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and Control of an System Stability in Grid-connected Inverter with LCL Filter”, in
LCL-filter-based Three-phase Active Rectifier”, IEEE Trans. Energy Conversion Congress and Exposition (ECCE), 2013, pp.
Industry Applications,, vol. 41, no. 5, pp. 1281-1291, 2005. 4476-4480.
[7] T. C. Y. Wang, Z. Ye, G. Sinha, and X. Yuan. “Output Filter Design [29] Z. Yang, Y. Li, W. Yin, et al., “Study on Harmonic Impedance
for A Grid-interconnected Three-phase Inverter”, in Power Equivalents Used for AC Filter Design of ±800 kV UHVDC
Electronics Specialist Conference, 2003, pp. 779-784. Transmission Project from Xiangjiaba to Shanghai”, Power System
[8] R. Pena-Alzola, M. Liserre, F. Blaabjerg, R. Sebastian, J. Dannehl, Technology, vol. 31, no. 18, 1-4+14, 2007. (in Chinese)
and F. W. Fuchs, "Analysis of the Passive Damping Losses in
LCL-Filter-Based Grid Converters", IEEE Trans. Power Electron.,
vol. 28, no. 6, pp. 2642-2646, 2013.
[9] I. J. Gabe, V. F. Montagner, and H. Pinheiro, "Design and Changyue Zou (M’17) received the B.S. and
Implementation to the Grid Through an LCL Filter", IEEE Trans. Ph.D. degrees from the Huazhong University of
Power Electron., vol. 24, no. 6, pp. 1444-1452, 2009. Science and Technology, Wuhan, China, in
[10] R. Pena-Alzola, M. Liserre, F. Blaabjerg, R. Sebastian, J. Dannehl, electrical engineering in 2010 and 2015,
and F. W. Fuchs, "Systematic Design of the Lead-Lag Network respectively.
Method for Active Damping in LCL-Filter Based Three Phase He is currently an Electrical Engineer with the
Converters", IEEE Trans. Industrial Informatics., vol. 10, no. 1, pp. Electric Power Research Institute, China
43-52, 2014. Southern Power Grid Co., Ltd., Guangdong. His
[11] J. Dannehl, M. Liserre, and F. W. Fuchs, "Filter-Based Active main research interests include control and design
Damping of Voltage Source Converters With LCL Filter", IEEE of VSC-HVDC.
Trans. Industrial Informatics., vol. 58, no. 8, pp. 3623-3633, 2011.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2018.2809705, IEEE
Transactions on Power Electronics
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) <

Hong Rao (SM’12) received the B.S. degree in Zhao Xiaobin received the B.S. degrees
electrical engineering from Huazhong University from Huazhong University of Science and
of Science and Technology, Wuhan, China, in Technology in 2008 in electrical engineering.
1983. He is currently an engineer with the Electric
He is currently the director of Electric Power Power Research Institute, China Southern
Research Institute, China Southern Power Grid Power Grid Co., Ltd., Guangdong, China. His
Co., Ltd., and the chief specialist of China main research interest includes Power system
Southern Power Grid Co., Ltd.. His main research analysis, AC&DC filter design, Overvoltage
interests include design of advanced HVDC based and insulation coordination research of HVDC.
projects and operation of bulk AC/DC power
system.
Mr. Rao is a committee member of ClGRE SC
B4. His awards and honors include the first prize of National Science and
Technology Progress Award, the first prize of China Electric Power Yu Yang received the B.S. and Ph.D. degrees
Science and Technology Progress Award, and the Outstanding Contribution from Shanghai Jiaotong University in 1995 and
to China Electric Power Science and Power Technology Award. 2000, respectively, both in electrical
engineering.
Shukai Xu (M’13) received the B.S. and Ph.D. He is currently an engineer with the Electric
degrees from Tsinghua University, Beijing, China, Power Research Institute, China Southern
in electrical engineering in 2002 and 2007, Power Grid Co., Ltd., Guangdong, China. His
respectively. main research interest includes Power system
He is currently the deputy director of HVDC and analysis, control and design of HVDC.
Power Electronics Department of Electric Power
Research Institute, China Southern Power Grid Co.,
Ltd., and the deputy executive director of State
Key Laboratory of HVDC. His main research
interests include control and design of Bo Lei received the B.S. and M.S. degrees
VSC-HVDC and FACTS. from the Hunan University, Changsha, China,
in electrical engineering in 2011 and 2014,
Yan Li (M’12) received the B.S., M.S. and respectively.
Ph.D. degree from Huazhong University of He is currently an Engineer with the
Science and Technology, Wuhan, China, in Electric Power Research Institute, China
electrical engineering in 1996, 1999 and 2003, Southern Power Grid Co., Ltd.. His main
repsectively. research interests include design of
He is currently the director of HVDC and VSC-HVDC and application of Battery
Power Electronics Department of Electric Power Energy Storage System.
Research Institute, China Southern Power Grid
Co., Ltd., and the deputy executive director of
State Key Laboratory of HVDC. His main
research interests include control and design of
LCC-VSC and VSC-HVDC.

Weiwei Li (M’12) received the B.S. and


Ph.D. degrees in electrical and electronic
engineering from Huazhong University of
Science and Technology, Wuhan, China, in
2009 and 2014, respectively.
He is currently an Electrical Engineer with
the Electric Power Research Institute, China
Southern Power Grid Co., Ltd., Guangzhou,
China. His research interests include digital
control techniques and renewable-energy
generation systems.

Jun Chen (M’17) received the B.S and M.S


degrees from the Huazhong University of
Science and Technology, Wuhan, China, in
2009 and 2012, respectively, both in electrical
engineering.
He is currently an Engineer with the Electric
Power Research Institute, China Southern
Power Grid Co., Ltd., Guangzhou, China. His
main research areas are VSC-HVDC and power
electronic systems.

0885-8993 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

S-ar putea să vă placă și