sensor Hydraulic separators are ideal for use with multiple boiler
boiler systems. Figure 6-25 shows an example.
multiple
system
boiler
controller
system The headers supplying the boilers should be sized
for minimal head loss. A suggested sizing criteria is a
flow velocity of 2 to 4 feet per second when all boiler
circulators are operating.
to loads
The hydraulic separator allows the boiler side flow rate
to be significantly different from the distribution side flow

Figure 6-26

hydraulic
separator

VENT

Courtesy of Coffey Plumbing & Heating

Figure 6-27
rejected heat rejected heat

VFD
chiller #2 chiller #1
HydroCal with
insulation shell
FlowCal valve

motorized 
to / from
ball valve purging chilled-water
valves cooling system

All chilled-water piping must


be insulated and vapor-sealed
VENT