Technical data sheet

UniPack - up to 40.5 kV and transformer 3.5 MVA


Steel housing – Mercury layout

A Compact Secondary Substation (CSS) is a type-tested


assembly comprised of an enclosure containing medium
voltage switchgear, a distribution transformer, a low voltage
switchboard, connections, and auxiliary equipment to
transform energy from medium to low voltage systems
(typical application is distribution networks), or from low to
medium voltage systems (typical application is solar and
wind farm applications).

Features
− High level of safety for equipment and personnel:
− Type tested as per the latest international standard IEC
62271-202
− No access to live parts
− Internal Arc Classification (IAC) AB with short-circuit current
20 kA for 1 sec.
− All equipment inside CSS is type tested as per their relevant
standard
− Engineered footprint to meet the required clearance standards
− Oil collection pit underneath the transformer Optional equipment
− Can be lifted with the transformer installed − Devices for metering and control circuit are available
− Designed with natural cooling and smooth air flow − The communication equipment and interphases for easy con-
− Locking system for all doors prevent unauthorized entry of nection to any SCADA System through the standard commu-
personnel nication protocols
− Stainless steel hinges for corrosion resistance − Remote Terminal Unit (RTU) to monitor the CSS and store the
− Steel parts are tested according to ISO 6988 data for operation, maintenance, and fault analysis. Local and
remote monitoring and commands are available
Equipment description
− Designed and manufactured to install both dry or oil trans- Installation
formers up to 3.5 MVA − A factory-tested solution is delivered directly to the installation
− Designed to accommodate medium voltage secondary site and all necessary lifting devices for moving the substation
switchgear up to 40.5 kV are also provided
− Can be provided with different options of medium voltage − No complicated civil engineering job is needed in advance or
switchgear from ABB’s SF6 gas-insulated secondary switch- during the installation
gear portfolio (also available with air-insulated switchgear) − Only a pit needs to be excavated with the substation being
− Able to accommodate a low voltage switchboard with differ- placed into this installation pit
ent options: − Only external connection to be done at site, resulting in sig-
− Breaker (ACB or MCCB) capable of disconnecting the nificantly reduced installation time
transformer and LV busbar
− Low voltage cables mounted directly on the busbar For detailed information, please see the installation manual.

There are various numbers and ratings of low voltage feeders


depending on transformer size and customer needs. Special LV
equipment is also available upon request.
Technical data

Description
Transformer (KVA) Up to 2000 Up to 3500
Type of layout Mercury 20 NS Mercury 35 NS
Max. rated voltage (kV) Up to 40.5
Short circuit withstand current of internal earthing network 20kA/1s
Overall dimensions (LxWxH) 4764 X 2250 X 2830 mm 5214 X 2250 X 2830 mm
Weight of substation excluding transformer (approximate) 4.5 tons 5 tons

1VPD110001A0244 Rev A September 2015


Transformer compartment dimension (LxWxH) 2416 X 1851 X 2300 mm 2866 X 1851 X 2300 mm
Total transformer load losses 16800 W 34000 W
Transformer compartment protection degree (IP) IP 23D
MV and LV compartment protection degree (IP) IP 54
CSS enclosure thermal class Class 10 (K10) Class 15 (K15)
MV compartment Up to 3-Way SafeRing
LV compartment LVS3 – 16M or equivalent
MV cabling The connecting cables can be from Al or Cu according to customer request. If not spec-
ified, then the cross section is selected to fulfill short circuit requirement of the arrange-
ment.
MV terminations The connecting cables can be equipped with pre-molded/cold shrink/heat shrink
Internal connection between LV switchgear and transformer Busbar or double insulated cable sized according to the rated power of transformer
Rated current of LV panel Up to 3200 A
Rated short circuit withstand capacity of LV busbar system 50 kA/1s

Layout For more information please contact:

MV TR LV
Up to 40.5 kV Up to 3500 kVA Up to 16 modules

3
A
M
V

www.abb.com/mediumvoltage

Note: We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB
does not accept any responsibility whatsoever for potential errors or possible lack of infor-
mation in this document. We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its
contents – in whole or in parts – is forbidden without prior written consent of ABB.