DuraLife® FPLP-CI Unshielded

UL 2196 2-Hour Fire Certified Cable


Free-Air Applications
SPECIFICATIONS
UL 2196 2-HR CERTIFIED / UL 1424 LISTED.
LOW SMOKE / PLENUM RATED CONSTRUCTION

Unshielded - 18 AWG, 16AWG, 14AWG, 12AWG; 2-conductor.


NEC Type FPLP-CI; Circuit-Integrity Cables; Horizontal and Vertical Applications Certified

CERTIFICATION LISTINGS:
18AWG / 2C solid OFHC; Free-Air application with 24" spacing support required per NEC Article 760.24. Low smoke
PVC insulation and jacketing. Horizontal splice allowed w / standard type-4S utility box. See Radix DuraLife® FPLP-CI
Splice and Application Guide for splicing instructions.

16AWG / 2C solid OFHC; Free-Air application with 24" spacing support required per NEC Article 760.24. Low smoke
PVC insulation and jacketing. Horizontal splice allowed w / standard type-4S utility box. See Radix DuraLife® FPLP-CI
Splice and Application Guide for splicing instructions.

14AWG / 2C solid and 7-strand OFHC; Free-Air application with 24" spacing support required per NEC Article 760.24.
Low smoke PVC insulation and jacketing. Horizontal splice allowed w / standard type-4S utility box. See Radix DuraLife®
FPLP-CI Splice and Application Guide for splicing instructions.

12AWG / 2C 7-strand OFHC; Free-Air application with 24" spacing support required per NEC Article 760.24. Low
smoke PVC insulation and jacketing. Horizontal splice allowed w / standard type-4S utility box. See Radix DuraLife®
FPLP-CI Splice and Application Guide for splicing instructions.

PRINT: RADIX WIRE-II DURALIFE ™ E241484 2/C # AWG FPLP-CI/CMP-CI E494543 75C / (UL) 2196 CLASSIFIED 2 HOUR
CERTIFIED (MONTH/YEAR) CI - NYC certified fire alarm cable (INCREMENTAL FOOTAGE REQUIRED - EVERY 2 FEET)
CHARACTERISTIC
NOMINAL INSUL NOMINAL JACKET NOMINAL
NOMINAL O.D NET WEIGHT COPPER IMPEDANCE
RADIX P/N #COND AWG THICKNESS THICKNESS CAPACITANCE
(INCH). (LBS/ MFT) LBS/MFT @1MHZ
(INCH) (INCH) (pF/FT) (OHMS)

CFU18A0102 2 18 Solid .022" .022" .280" 41 9.8 11.17 140.7


CFU16A0102 2 16 Solid .022" .022" .308" 45 15.9 12.39 114.6
CFU14A0102 2 14 Solid .022" .022" .320" 50 24.8 - -
CFU14A0702 2 14/7-Strand .022" .022" .330" 52 25.1 14.76 106.7
CFU12A0702 2 12/7-Strand .022" .022" .368" 61 39.9 15.93 99.1

COMPLIANCE:
• UL 1424 Listed FPLP for Power-Limited Fire Alarm Circuits; 300V / 75°C classified.
• UL Certified to UL 2196 2-hour fire rating
• Fire alarm circuit integrity, emergency systems, and healthcare facilities (NEC Articles 760, 700 & 517).
• Meets NFPA 262 for plenum rating
• Meets National Fire Protection Code (NFPA 72) fire alarm survivability circuit requirements.
• Suitable for 2-hr. certified fire-resistive free-air applications
• Fire-resistive certified for Power-Limited system use at 50V phase-to-phase utilization voltages.
• UL Listed File No. E-241484; E-494543.