UPS Technical Specification V10 18/11/2013
1 Creation MO 05/08/08
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Note :
When the document is updated, the writer has to validate the modification through the examiners, and
transmit to the approval representatives a complete copy of the document :
- cover sheet, with incremented version, for signature
- The updated “update history of document” and distribution list
The rest of the document clearly indicating the added/modified paragraphs to aid the reader
(underlining)
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Note :
Once the document update is approved , one copy of the document must be sent to each person of the
distribution list :
-
- A copy of the cover sheet, with incremented number of version and signed by the approval
representatives
- An updated “history of document”
- The rest of the document for archive.
Furthermore, The electronic address will be indicated, where one can find the controlled and protected
document on the network (*.pdf)
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Contents :
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
The UPS (Uninterruptible Power System) isolates the load from the AC mains supply, protecting
it from voltage drops, spikes, transients, RFI and frequency variations.
In the event of total or partial AC mains power failure, the UPS will continue,
without interruption, to provide power to the load from the sealed battery.
Duration will depend on battery capacity and output load.
When the AC mains supply is restored, the UPS automatically
recharges the batteries, ready for any power failure emergency.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
The UPS system is composed of two main components ; the control unit and the Battery unit.
Were :
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
The control unit is a electronic unit dedicated to monitor the power supply line and to manage the
Battery unit.
-1 ) ON-Line Operation
Normal UPS operating mode. The connected loads are supplied from the mains via the Inverter. The
batteries are charged as necessary.
The inverter reliably filters mains disturbances and provides a stable, interference-free supply to the
load. In this operating mode, if a mains failure occurs, the UPS switches to battery operation. If an
overload or short circuit occurs at the UPS output, or if there is a fault in the inverter, the UPS
switches to bypass operation.
In this mode, the connected loads are supplied from the mains via the Inverter and the batteries are recharged
via the rectifier.
In the event of power failure, battery operation is automatically activated and supplies the loads interruption
free.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In the event of power failure, battery operation is automatically activated and supplies the loads
interruption free.
If the back-up time has not expired, the UPS automatically returns to on-line operation, once the
mains supply returns.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In this mode, the connected loads are supplied from the bypass mains via the electronic bypass.
The electronic bypass serves to further ensure power to the loads. If an overload exceeds the
capability of the UPS, it is automatically activated to ensure uninterrupted power supply to the loads.
From this operating mode, the UPS automatically returns to on-line operation after the fault is
corrected.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In this operating mode, the connected loads are supplied directly from the bypass mains supply.
The service bypass is used to supply the connected loads with voltage during maintenance work on the
UPS.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
As a standard Sidel Industrial Operation does not include in the scope of supply :
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
The size of the cables between UPS and filler control cabinet is in relation to the load power and the
distance between UPS and filler control cabinet.
The maximum cable length allowed between customer distribution control cabinet and filler control
cabinet is 110 meter ( L1 + L2 or L3 ).
For greater lengths a special study will be necessary.
Distribution block :
Customer distribution
cabinet
L1
Filler UPS
L2 L3 ( L2 = L3 )
Filler control
cabinet
Legenda :
L1 = Line 1 ( from Customer distribution cabinet to UPS )
L2 = Line 2 ( from UPS to FMa Filler )
L3 = Line 3 ( from UPS to FMa Auxiliary Unit )
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
The tables below is the result of the electrical calculation performed with the data present in the
table.
The cables data (sizes and characteristics ) presents in the table is valid ONLY if ALL information
presents in the table are respected.
A dedicated electrical calculation will be realized and included in the electrical drawing for each
installation.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 20 + 20 meters , 40 + 40 meters and 60 + 60 meters.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 25 + 25 meters , 40 + 40 meters and 60 + 60 meters.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 3 ( three ) different lengths are analyzed : 25 + 25 meters , 40 + 40 meters and 60 + 60 meters.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 2 ( two ) different lengths are analyzed : 40 + 40 meters and 60 + 60 meters.
In the table the UPS is positioned in the middle between the customer distribution cabinet and the Filler/Aus electrical
cabinets.
In this configuration 2 ( two ) different lengths are analyzed : 40 + 40 meters and 60 + 60 meters.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In red : OBLIGATORY
In blue : Optional (they don't compromise the cable sizing)
Customer distribution
cabinet
L1
Filler UPS
L2 L3 ( L2 = L3 )
Filler control
cabinet
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
2.5.1. Control unit and Battery unit dimension ( UPS size 80,100,120 KVA ):
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
2.5.3. Control unit and Battery unit dimension ( UPS size 160 KVA):
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
2.5.5. Control unit and Battery unit dimension ( UPS size 200 & 250 KVA):
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
2.5.6. Typically installation dimension (UPS size 200 & 250 KVA):
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
2.5.7. Location:
To ensure correct ventilation, leave nothing on top of the UPS.
Leave one meter of free space in front of the UPS for door opening.
The cubicle rests on four cylindrical feet, 40 mm in diameter, positioned in the four corners of the
cubicle to spread the weight.
If 600 mm of free space is not maintained above the UPS, abnormal temperature rise
may occur. The UPS must be installed in a room with restricted access (qualified personnel
only).
(*) The UPS can operate correctly back to the wall, but it is preferable to leave some space for easier
maintenance.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In case of close installation between Control unit and Battery unit or in case of installation inside the same room,
respect the most restrictive data (see next paragraph related to BATTERY UNIT Service Temp.).
Each increment of 10°C above 25°C reduces the expected battery life by 50%.
Note : Air enters through the bottom. Air exits through the top.
2.12. UPS ( CONTROL UNIT AND BATTERY UNIT ) RELATIVE HUMIDITY RANGE:
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Key 12
This key is used to validate the user’s "A" key 15
choice. This key is used to access current
Key 13 measurements:
This key is used to access the main normal AC source, bypass AC source
menu: display language, display contrast and load currents;
setting, sound level of the percent load;
buzzer, lamp test, date and time load crest factor.
settings, inverse-video and event log. "W.Hz" key 16
"V" key 14 This key is used to access other
This key is used to access voltage measurements:
measurements: normal AC source, bypass AC source
normal AC source phase-to-phase and inverter frequencies;
voltages; level of active and apparent power
bypass AC source phase-to-phase drawn by the load;
and phase-to-neutral voltages; load power factor;
load phase-to-phase and phase-to neutral inverter load level (percent).
voltages. "Anomaly" indicator light 17
This indicator light indicates the
presence of anomalies.
key 18
This key is used to access the primary
messages.
"Battery" key 19
This key is used to access battery
measurements:
battery voltage (or the DC voltage on
frequency converters without a battery);
battery current (charge or discharge);
battery temperature;
available battery backup time;
inverter load level (percent).
"Forced-transfer" key 20
This key is used to voluntarily transfer
the load to the inverter or from the
inverter to the static bypass (return
transfer). Transfer and return transfer
are carried out only following
confirmation requested by the system
display and a warning as to the risk of
an interruption in the supply of power to
the load.
"Alarm reset" key 21
This key is used to reset stored alarms.
The system accepts resetting only
when alarms have been cleared.
"Buzzer reset" key 22
This key is used to stop the buzzer.
However, new alarms set the buzzer off
again.
Display 23
The display continuously indicates the
system operating status.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
3. UPS INSTALLATION
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
By a hardware signal exchange between filler’s control cabinet and the UPS Control unit,in the filler
HMI is possible monitoring the UPS status.
In case of fault or warning active on the UPS, a dedicated fault will appear on the filler HMI.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
As a standard Sidel Industrial Operation does not include in the scope of supply :
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
DISTRIBUTION
CABINET
CUSTOMER
FMa
Filler UPS
Filler
AUS
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
SIDEL
( FMa )
CUSTOMER
UPS technician
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Here are indicated the internal standard connection of the Battery Unit.
ALL THESE CONNECTIONS MUST BE PERFORMED ONLY BY A UPS TECHNICIAN.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
4.4.1. Connection :
In this chapter are indicated the operation that are necessary in order to give power to FMa without
switch on the UPS :
Operation list :
WARNING :
WITHOUT UPS TECHINICAN :
BEFORE SWITCH ON THE POWER SUPPLY TO UPS ( FROM MAIN DISTRIBUTION CABINET ) :
VERIFY THE FILLER AND AUS SWITCH POSITION : IT MUST BE ALL IN OFF POSITION.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
Verify ( by tester ) the good voltage of the 3 phase and Neutral (if present ) on Q3PB and Q1.
Verify ( by tester ) the good voltage of the 3 phase and Neutral (if present ) on Q5N.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In this configuration the UPS is switched OFF and in Maintenance By-pass configuration.
Verify ( by tester ) the good voltage of the 3 phase and Neutral (if present ) on Filler control
cabinet and AUS control cabinet.
NOTE :
LEAVE THE UPS IN THIS STATE.
DO NOT SWITCH ON THE OTHERS UPS SWITCH.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
In order to organize the UPS start-up intervention, is necessary take contact with the Italian UPS’s
supplier.
On the UPS and on the Battery unit is possible to find a label with the Italian supplier’s reference :
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
This procedure is valid after the first start-up performed by the UPS technician.
In this procedure is described the correct sequences in order to switch OFF and switch ON the UPS
unit.
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
• Verify the correct switching off operation by the Led in position 2 ( MUST BE OFF ).
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
• Open the BATTERY Switch QF1 ( located in the Battery control cabinet : In case of
double battery cabinet perform this operation on each battery cabinet )
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
• Switch ON the power supply from distribution control cabinet to UPS ( in case was
OFF )
• Wait minimum 10 second. Verify the correct switching on procedure by the Led
indicated below ( MUST BE ON )
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY
UPS Technical Specification V10 18/11/2013
• Wait minimum 10 second. Verify the correct switching on procedure by the Led
indicated below ( MUST BE ON )
• Switch ON UPS Switch QF1 ( in the Battery control cabinet : In case of double battery
cabinet perform this operation on each battery cabinet )
The UPS will restart in automatic way ( function AUTO RESTART enabled on ALL our UPS as
default )
Sidel s.p.a.
Via La Spezia 241 A,
43100, Parma, ITALY