1.1 SCOPE
The scope of this section comprises the supply, installation, testing and commissioning
of Ecology unit conforming to these Specifications and in accordance with the
requirement of Drawings and Schedule of Quantities. Below specification will be valid
where proper grease trap device is attached to the kitchen hood. Unit should be
capable for conveying air with maximum temperature up to 80°C in continuous
operation.
1.2 CAPACITY
1. EN 779 : G4
2. Arrestance (ASHRAE 52.1) : 90-94%
3. MERV Rating (ASHRAE 52.2) : MERV7
4. Eurovent : EU4
5. Dust Spot Efficiency (ASHRAE 52.1) : 30-35%
6. Size of filter to suit the design requirement
Air is drawn by the blower through a washable metal mesh pre-filter & Bag Filter
which traps large dust particles. The remaining particles, some as small as 0.01
microns, pass into a strong electrical field (ionizing section) where the particulate
receives an electrical charge. The charged particles then pass into a collector plate
section made up of a series of equally spaced parallel plates. Each alternate plate is
charged with the same polarity as the particles, which repel, while the interleaving
plates are grounded, which attract and collect. Should have following features:-
Fans, backward curved, DIDW, shall be licensed to bear the AMCA Air and Sound
Certified Ratings Seal. The test standard used shall be ANSI/AMCA 210-85,
ANSI/ASHRAE Standard 51-1985 “Laboratory Method of Testing Fans for Rating”
and AMCA 300 “Reverberant Room Method for Sound Testing of fans”.
All fans shall be dynamically trim-balanced to ISO1940 and AMCA 204/3 - G2.5
quality grade after assembly.
Fan outlet velocity shall not exceed 10 m/s and maximum fan speed shall be 1450 rpm
for fan up to 450 mm dia. For fans above 450 mm dia the outlet velocity shall be
within 11.5 m/sec. and maximum fan speed shall not close to critical speed.
1.3.3 HOUSING:
Fans must be physically capable of operating safely at every point of rating at or below
the “minimum performance” limit for that class as defined in AMCA standard 99-2408-
69 “Performance Class of Operating Limits for Centrifugal Fans”.
All Ventilation Fan wheel shall be backward curved inclined non-over loading type. Fan
wheel and housing shall be statically and dynamically balanced to G2.5 quality grade.
1.3.5 SHAFT:
Shafts shall be made of carbon steel (C40) machined and polished to tolerance of
standard ISO 286-2 - grade g6. Protective coat of anti-rusting shall be applied to all
bare surfaces of the shafts at the factory.
Shafts sizes shall be carefully calculated and designed such that the maximum
operating speed (RPM) shall not exceed 75% of the first critical speed. For any
application that is not a standard product from catalogue of the fan manufacturer
detailed calculation of critical speed characteristic shall be submitted for approval.
1.3.6 BEARINGS:
1.3.7 MOTORS:
Fan motor shall be suitable for 415 10% volts, 50 cycle 3 phase power supply,
squirrel cage, TEFC motor, provided with class F insulation, and of approved make.
Motor nameplate horsepower shall exceed brake horsepower by a minimum of 10%.
Motor shall be designed especially for quiet operation. The fan and motor combination
selected for the particular required performance, shall be of the most efficient (smallest
horse power), so that noise level and power consumption are lowest.
1.3.8 DRIVE:
Drive to fan shall be provided through belt with adjustable motor. Belt shall be of the
oil resistant type.
Belts and pulleys shall be sized for a minimum 150% of the installed motor
horsepower. The belt speed shall not exceed 30m/s. The pulley shall be of Taper Lock
SPZ, SPA, SPB or SPC type. Conventional type of pulley is not acceptable.
GSS / MS base shall be provided for both fan & motor, built as an integral part, and
shall be mounted on a concrete foundation through vibration spring isolators/cushy
foot mountings.
a. Filter Section: Pentapost design & have strong three way angle joints of
reinforced nylon corners to form a rigid frame structure. Rigid frame work
comprises an assembly of externally chamfered extruded aluminium profile &
nylon corner joints.
b. Inner & Outer Skin: standard pre-coated GI sheet, the double skin (25/50
mm) is to retain the insulation surface clean & to have a smooth surface.
OMAN LNG SCHOOL AT HAY SHAROOQ- SUR ME-85/C
M&E WORKS SPECIFICATION MECHANICAL WORKS
SECTION M.01 AIRCONDITIONING & VENTILATION
1.5 ACCESSORIES:
a. Control Panel (Motor Starter, Status Panel for Filter Bank).
b. Fire Damper.
c. Inlet/outlet flexible connectors
d. Ant vibration supports
e. Outlet flange
f. Inverters speed controllers.
g. Weather proof Construction for Fan Section (Optional – As per site
Requirements)