Sunteți pe pagina 1din 5

Data Sheet HE400, HE600

22.01.2009

Tixi Data Gateway LAN


• Remote Maintenance and Control
• Fault Messaging
• Data Logging
• Web Server
• PLC Protocols

Energy Monitoring with M-Bus:


Up to 100 M-Bus energy meters can be monitored
by a single Tixi Data Gateway LAN
Tixi Data Gateway with 4 I/O Modules

Tixi Data Gateways for cellular GSM, WLAN or telephone networks: HG400/600, HW400/600 and HMxx.

Tixi Main Unit Tixi I/O-Modules


Series HE400 HE600 Type XP84D XP84DR XP88D XR46 XYZ
CPU ARM7 ARM9 Digital inputs 8 8 8 4

modules
Speed 60 MHz 200 MHz Digital outputs 4 - 8 -

custom
RAM 8 MB 64 MB Relays - 4 - -
Flash Memory 8 MB 64 MB RS232 - - - 1
SD-Card (max.) 2 GB 2 GB RS485 - - - 1
Operating System MQX-RTOS Linux 2.6 Max. number of I/O-Modules 8 8 8 2 8
Max. number of I/O-Modules 8 4-8

Models
HE430/ HE423- HE443- HE445-
HE400 HE421 HE427 HE441 HE447 HE471 HE476 HE425-2S0
32/34 Mxx Mxx Mxx
COM1 RS232 RS232 RS232 RS232 RS232 RS232 RS232 RS232 RS232 RS232 RS232
COM2/ RS485/ RS485/ Siemens Siemens
RS232 RS232 RS232 RS232 RS485 2xRS485 RS232
COM3 422 422 S7-MPI S7-MPI
Digital Input - 2 12/8/4 - 2 - 2 2 2 - 2
Analog Input - 1 1 - 1 - 1 - - - 1
Digital Output - 2 0/2/4 - 2 - 2 1 1 - 1
Relay - 1 - - 1 - - - - - -
M-Bus M-Bus M-Bus 2x S0 pulse
Metering Interface - - - - - - -
25/60/100 25/60/100 25/60/100 input
HE630/ HE623- HE643- HE645-
HE600 HE621 HE627 HE641 HE647 HE671 HE676 HE625-2S0
32/34 Mxx Mxx Mxx

PLC Options
Optional PLC protocols (Feature Packs) enable direct communication between
Tixi Data Gateway and PLCs - without the need for special drivers inside the PLC:
Saia Allen
Mitsubishi Moeller Siemens VIPA ABB Burgess Bradley Theben
Alpha XL EASY400 S7-200 100V AC010 PCD1 Serie A Pharao2
FX1S EASY500 S7-300 200V AC31 PCD2 Serie B
PLC Protocols FX1N EASY600 S7-400 300V AC500 PCD3 GFX
FX2N EASY700 SPEED7 AC800 PCS
FX2NC EASY800 CL
FX3U MFD-Titan
Drives PS4-Serie
EasyControl
XC/XVC

MODBUS (RTU, ASCII) for WAGO, Rockwell Automation, Allen Bradley, Schneider Electric, B&R etc.
TixiBus simple protocol for „small“ PLCs (master-slave principle)
Upon customer orders for pumps, heating systems (eBus), air conditioning, data loggers, temperature
OEM Protocols
sensors, radio systems etc.

TIXI_DATA_HE400+600_EN_090222.DOC 23.02.2009 07:02 www.Tixi.Com


Tixi Data Gateway LAN HE400/HE600 Data Sheet Page 2 / 5

Features
Alarm and Fault Notifications
Automatic generation and dispatch of more than 100 fault notifications
Condition based monitoring of data may launch events
Fault Notification
Message templates may include current values from PLC or Tixi Data Gateway
Up to 100 predefined events may trigger actions.
Alarm Cascade Message confirmation may be implemented by means of freely definable alarm levels.
Address Book Address book with more than 100 contacts
More than 100 message templates may contain variable values from PLCs or the Tixi Data Gateway.
Message Templates Destination addresses and PLC variables are defined as references.
Message length is not restricted (only by memory size).

Neutral Data
All data of local systems connected to the device (PLCs, meters, sensors etc) are managed by means of a
neutral variable table (XML). These XML-data are independent of their origin.
Data Converter All Tixi functions use these neutral data.
Local PLC data may thus be translated from one system to another, e.g. meter data may be handed to a
PLC or BMS (building management system).

Data Logger
All values (e.g. PLC or meter values) may be logged on a regular basis.
Data Logging (e.g. every 1 min, 15 min, 1h, 1d, …) or upon certain events.
Data is automatically compressed (binary format).
Saved Log data may be sent as E-Mail attachments at scheduled times or as a result of any event. Their
Data Dispatch
format is to be freely defined, such as XML or Microsoft Excel CSV.

Embedded Webserver
The user may create custom websites with any HTML editor, including XML placeholders for system values.
By means of these websites, current data may be displayed or custom input masks can be defined.
Webserver
Common Gateway Interface (CGI) for dynamic read and write of values and for log data readout.
Special SSI (Server side Includes) allow embedding of values and log data into websites.

Remote Control
Switching commands may be transmitted via E-Mail, HTTP or TiXML command onto the Tixi Data Gateway.
Switching Commands
HTTP and TiXML commands may be defined freely and may contain e.g. setpoint values.
If need be, the device may send confirmation commands upon receipt and execution of a remote switching
Confirmation
command, in order to report the positive (or negative) result of such.

Programmable Features
Event Calendar may trigger the following actions:
- Creation of logfile entries or dispatch of logfiles,
Scheduler - Switching I/Os or setting PLC variables,
- Dispatch of periodic status messages
- Automatic shift schedules may change the receiver of messages.
Functions (e.g. AND, OR, XOR, NOT) and
Logical Operations Comparisons (z.B. GT, LT, EQ) can be applied to variable values,
even along with time schedules, may trigger actions.
Time-dependent data arrays can be preset over a specific span of time, either via configuration or by
message. E.g monitoring of current values and dispatch of messages in case that current values exceed
Sequencer min./max. curves (depending on a time grid of 15-min-steps up to one year).
Several curve sets may be used in conjunction or as separate data sets.
Arithmetic Operations Simple arithmetics (ADD, SUB, MUL, DIV) allows calculation with PLC and variable values.

Configuration
TiXML is the XML based command language used to configure Tixi devices.
TiXML
Via TiXML, programs and devices may easily communicate with Tixi devices.
Configuration TiXML via TCP/IP or COM1 RS232 or via batch file on an SD card.
Access to the Tixi device and to the configuration is protected by several levels of login and password - both
Security
remotely and locally.

TIXI_DATA_HE400+600_EN_090222.DOC 23.02.2009 07:02 www.Tixi.Com


Tixi Data Gateway LAN HE400/HE600 Data Sheet Page 3 / 5

System and General Features


e.g.: change of PLC variable(s), exceeding a threshold,
Event
scheduled point in time reached, error, PLC connection interrupted etc.
E-Mail E-Mail dispatch (SMTP, ESMTP), e.g. with log file attachment, retrieve of POP3 E-Mail for remote control
Reset / Restart the device and retain the current configuration or do a
Factory Reset Factory Reset which deletes all settings and returns the device to factory settings
IP settings via configuration or automatically via
IP / DHCP
DHCP (Dynamic Host Control Protocol)
TFTP Upload of websites via TFTP (Trivial File Transfer Protocol)
Local Transparent Mode Transparent loop-in of serial COM1 interface to PLC-Interface COM2.
Special Features Upon customer request, features and protocols may be implemented into the Tixi Data Gateway.

Hardware
CPU System
HE400: 32 bit ARM7 Processor, 60 MHz
CPU
HE600: 32 bit ARM9-Processor, 200 MHz
HE400: 8 MB SDRAM
RAM
HE600: 64 MB SDRAM
HE400: 8 MB (Options: 4 MB, 24 MB, 40 MB
FLASH Memory
HE600: 64 MB (Options: 32 MB, 128 MB)
Real Time Clock (RTC), battery buffered
System Clock
Synchronisation with internet time server optional

Memory Card
green: SD card mounted
Active LED
red: Read/write access in progress
Before removing the SD card, press the "Unmount Button" first
Unmount Button
and wait until the "Active" LED is off
Batch Mode Upload TiXML configuration, download logged data from internal memory to the SD card
Updates Firmware and boot loader update via RS232 or SD card
SD cards up to 2 GB
Memory Cards
internal Micro-SD card adapter (optional, access requires opening the device case)

Controls
Service Button To be configured by the user: Allows triggering of any kind of event or action.
red/green: User-definable, controllable via TiXML (red-green flashing, 32 variants), e.g.
Signal LED red = faulty
green = operational
Speaker Micro-speaker for signal tones
System LEDs Power, Process, Connect, Data out, Mode

Serial Interfaces
D-Sub 9 female, max. 230.400 bps,
ITU-T V.24, V.28, Hardware Handshake, FIFO 16550,
COM1 RS232 All signals: DTR, DSR, RTS, CTS, DCD, GND, RI, RxD, TxD,
Transmission distance: 12 m
COM2 RS232 D-Sub 9 male, otherwise the same as COM1
According to EIA/TIA-485, 3- or 5-pin screw terminals
max 230 kbit/s, not galvanically insulated
COM2 RS485
integrated termination, can be activated by means of DIP switches
Transmission distance: 1200 m depending on transmission rate and type of bus and cable

Firmware
Tixi Embedded Communication System
TECom offers all basic features for local communication to PLCs and remote communication via cellular and
TECom
analogue phone networks, LAN/WLAN and IP-based networks.
TECom is a platform independent and portable protocol.
HE400: commercial RTOS (Real-Time Multitasking Operating System MQX)
Operating System
HE600: Linux 2.6
DOS-compliant Flash file system (with wear leveling)
File System
All data is retained during power failure.
Firmware is open to custom upgrades, such as:
OEM Features
New PLC protocols, calculating and processing functions, additional web server features

TIXI_DATA_HE400+600_EN_090222.DOC 23.02.2009 07:02 www.Tixi.Com


Tixi Data Gateway LAN HE400/HE600 Data Sheet Page 4 / 5

M-Bus
Conformity DIN EN 13757-2, DIN EN 13757-3
HE400-M25: M-Bus Master for up to 25 meters
HE400-M60: M-Bus Master for up to 60 meters
HE400-M100: M-Bus Master for up to 100 meters
Connection
short-circuit-proof
M-Bus Voltage: 36 V, Bus length: approx. 1 km with M25, telephone wires ø 2×0,8mm, unshielded,
3 screw terminals (grid dimension: 5,08 mm / 0,1"), section max. 2,5 mm²
Data Rate 300 Baud to 115 kBaud
Data Format 8 data bits, 1 start bit, 1 stop bit and 1 parity bit (even)
Electrical Isolation: 1500 Volt

Pulse Inputs for Energy Meters (S0 Input)


Conformity DIN 43864
2 connectors, active and passive devices may be connected
Current: usually 24 V, range 12-24 V, 30 mA, Amperage: inactively: 0...2 mA, actively: 10...27 mA
Connection
Debouncing time: 13 ms, line length: max. 3 m, unshielded
6 screw terminals, grid dimensions 5,08 mm, diameter max. 2,5 mm²

Inputs and Outputs (I/Os)


Up to 13 inputs (HE430) and 4 inputs and 4 outputs (HE434) are available in the main unit.
Up to 8 I/O modules with up to 128 I/Os can be connected and controlled via one Tixi device, using the Tixi I/O bus.
I/Os of the Tixi device
Digital via potential-free contacts
Inputs
Analog 0...10 V DC, resolution: 12 bit
Digital potential-free, AC/DC 125 V, 120 mA
Outputs
Relays potential-free, 230 V AC 3 A or 110 V DC 0,3 A
Connectors Screw terminal (grid dimension: 5,08 mm / 0,1"), section max. 2,5 mm²

I/Os of the Tixi I/O modules


XP84D 8 digital inputs, 4 digital outputs
Inputs XP88D 8 digital inputs, 8 digital outputs
XP84DR 8 digital inputs, 4 relay outputs
OEM-I/Os Upon custom order: digital and analogue inputs and outputs, RS232, RS485, relay, ...

Power Supply
10...30 V DC, max. 0,7 A (with up to 8 I/O modules)
Standard Model
24 V DC and without I/O modules: max. I = 250 mA
M-Bus Model 18 .. 30 V DC, max 0,7 A
Connectors 2 screw terminals (grid dimension: 5,08 mm / 0,1"), section max. 2,5 mm²

Case
Mounting at DIN Rail 35 mm (EN50022), vertically or horizontally
Type Tixi-H5 Case: DIN-Rail Case
OEM Case Standard OEM DIN-Rail Case: Tixi-H5
Width / Height / Depth 88 mm × 57 mm × 91mm
Weight 225 g

Compliance
Safety: EN60950
Conformity
EMV: EN55022 (9:2003), EN55024 (10:2003)
Temperature Range Operation: 0...50°C, Storage: -30...+70°C
Permitted Humidity 5...95% relative humidity, non-condensing
Protection IP20
Degree of fouling 2
Vibration (Sinus) according to IEC 60068-2-6, Vibration (Broadband) according to IEC 60068-2-64
Mechanical Fastness
Shock according to IEC 60068-2-27

OEM Models
OEM Models may be manufactured in different case colors and shapes,
as well as in hardware interfaces or design and software.

TIXI_DATA_HE400+600_EN_090222.DOC 23.02.2009 07:02 www.Tixi.Com


Tixi Data Gateway LAN HE400/HE600 Data Sheet Page 5 / 5

Ethernet

10/100 Base-T IEEE 802.3,


Connection
RJ45 jack (8P8C), shielded
Operating Mode Auto-Negotiation, Auto-MDI-X (crossover cable not required)
green flashing Data transmission in progress
Status LEDs yellow off 10 Base-T
yellow on 100 Base-T
Electrical Isolation 1500 V

Wireless LAN: Alle HE400 and HE600 models are available with Wireless LAN interface as HW400 and HW600.

Illustration
HE627 or HE427 XP88D

TIXI_DATA_HE400+600_EN_090222.DOC 23.02.2009 07:02 www.Tixi.Com