Sunteți pe pagina 1din 3

INGECEP LTDA.

®
FirePro
Design Calculation Software
Fire Extinguishing Aerosol Systems

Distributor/Master Dealer: TDS CHILE S.A

Project Name: PROTECCIÓN SALA ELÉCTRICA

Date: 07-jul-17

Client's Name: EDAM PLANTA FARFANA


Clinent's Code:

Address: LA FARFANA, MAIPÚ.

Tel.: 56 2 29658963

Fax:
Email: rvasquezv@edam.cl
Website: www.firepro.info

Special Notes:
No Special Notes Required

Please start from Volume Calculation Sheet

FirePro Systems Ltd all rights reserved


INGECEP LTDA.
FirePro®
Design Calculation Sheet

VOLUME 1

SELECT UNITS Meters

VOLUME 642
(if not to be calculated)

ROOM NAME & No. Sala de cloración

SPACE TYPE Other Very Large Size Encl. >4m Height

ROOM SHAPE Rectangular


Length Width Height
SECTION DIMENSION 21,00 m x 6,00 m x 5,00 m = VOLUME = 642,000 m3

5,00
CLASS OF FIRE Class C - Electically Energized Fires

STREAM REQUIRED (m) 2.5<SL<4.0

SAFETY FACTOR (sf)** 0,8

**FOR ADDITIONAL SAFETY REPLACE CURRENT SAFETY FACTOR AS APPLICABLE

TOTAL VOLUME THIS ROOM IN CUBIC METERS (m3) 642,00 m3

3 3
M (g) V (m ) D (g/m )
Mass of FirePro® Aerosol Total Volume EAD SF

40446,00 g
3 3
Extinguishing Application Density (g) = 642,00 m x 84 g/m x 0,8 =

RECOMMENDED GENERATOR MODEL(S) SELECTION


Recommended Models by Stream Lenth:
FP-500S, FP-1200, FP-2000, FP-3000

Recommended Models by Volume:


FP-5700

CONFIRM STREAM LENGTH CORRECTNESS OF RECOMMENDED GENERATOR-ROOM HEIGHT Vs STREAM REQUIRED

CONFIRM SIZE CORRECTNESS OF GENERATOR RECOMMENDED - ROOM VOLUME Vs GENERATOR COVERAGE

IMPORTANT REMARKS:
1. THIS SOFTWARE IS ONLY A GUIDING TOOL - SELECTION OF GENERATORS IS THE USER's RESPONSIBILITY.

2. ABOVE SELECTION IS JUST A RECOMMENDATION. ENGINEERING JUDGMENT SHOULD BE APPLIED FOR PROPER
SELECTION OF GENERATORS TAKING INTO CONSIDERATION ROOM HEIGHT(STREAM LENGTH), GENERATOR ORIENTATION
IN RELATION TO THE VOLUME ARRANGEMENT, OPENINGS etc.
3. FOR PROTECTED VOLUMES EXCEEDING 4M HEIGHT GENERATORS SHOULD BE INSTALLED IN STAGGERED
ARRANGEMENT TO ENABLE PROPER TOTAL FLOODING - PLEASE CONSULT MANUFACTURER.
4. ALWAYS CHECK CALCULATIONS FOR CORRECTNESS

TOTAL VOLUME THIS SECTION 642,00 m3


®
TOTAL FirePro MASS REQUIRED FOR VOLUME 1 40446,00 g
FirePro Systems Ltd all rights reserved
INGECEP LTDA.
FirePro®
Generator Selection Sheet

VOLUME 1

Mass of FirePro® Aerosol


Extinguishing Material Required (g) 40446,00 g

VOLUME 1 642,00 m3

RECOMMENDED GENERATOR MODEL(S) SELECTION


BY Stream Length By Volume Capacity
FP-500S, FP-1200, FP-2000, FP-3000 FP-5700

MODEL SELECTION

REF MODEL Concentr. QTY TOTAL CONCENTRATION


(g) (g)
1 FP-100S 0 100 0
2 FP-200S 0 200 0
3 FP-500S 0 500 0
4 FP-1200 0 1200 0 0
5 FP-2000 0 2000 0
6 FP-3000 0 3000 0 0
7 FP-5700 ## 5700 9 51300
8 Heat Impulse Translator (H.I.T.) ## (meters)

TOTAL 51300 g

(+) EXCESS / (-) SHORTAGE CONCENTRATION 10854 g


DEVIATION (+/-) 27%

CHECKED FOR CORRECTNESS:


APPROVED - CONCENTRATION IS TOO HIGH - ABOVE +20% - CHECK GENERATOR SELECTION
FOR CORRECTNESS
REMARKS:
AEROSOL TOTAL FLOODING COVERAGE IN PROTECTED SPACE SHALL BE ACHIEVED WITH EVEN
DISTRIBUTION OF GENERATORS AS PER MANUFACTURER'S RECOMMENDATIONS

FirePro Systems Ltd all rights reserved