Documente Academic
Documente Profesional
Documente Cultură
4 4
pu.
quence loop, to the detriment of their usable thermal capaci-
ties. This effect assumes particular importance when third-
harmonic current flows continuously through a short-tinie-
The foregoing is 233 percent of the corresponding three- rated neutral grounding resistor. At best, the resulting losses
phase fault current. In the absence of some limiting imped- waste energy and raise the initial operating temperature
ance, this would be disastrous. of the resistor, requiring its deratiing either in current or
In even the least severe case of a single generator, solid time. At worst, the harmonic loading may exceed the very
neutral grounding produces dangerously high fault current and limited continuous capability of the resistor, thus destroying
should be avoided. Any of the several grounding methods can it. Further problems can arise if the third-order current is high
be applied if they limit the maximum ground fault current in enough to operate ground fault relaying, which depends
each generator to less than its maximum three-phase fault on detection of zero-sequence current or voltage. Relays may
current EL N/Xd have to be desensitized to prevent false operation.
Most low-voltage power systems (208Y/120V and 480Y/ Circulating current is directly proportional to the vector
277V) are solidly grounded. Generators intended for emer- resultant of all voltage sources of a given harmonic in the
gency and standby service on these systems have additional closed loop, and inversely proportional to the sum of har-
winding bracing to allow their neutrals to be solidly grounded. monic-frequency impedances around the loop. If the zero-
However, there is still a chance of trouble if several generators sequence loop comprises two or more identical generators
are connected in parallel with only one grounded, as in the loaded the same, the voltage waveforms of the machines will
case above. be similar enough to nmake the resultant driving voltage very
McFADDEN: GROUNDING OF GENERATORS 555
small, and very little current will circulate. On the other hand,
significant currents are possible when different generators, or
generators combined with purchased-power transformers, are
connected in a loop.
The component derating required by circulating harmonic
current is easy to estimate. The thermal load is proportional
to the root-mean-square (rms) current, which is given by
'rms 22 h = 1, 2, 3,---,
'rm = 12 +0.1762=1.015pu.
GI and G2 are subjected to thermal overloads of 1.5 percent
and 0.6 percent, respectively, at full power-frequency load, Fig. 3. Two parallel generators with neutral grounding resistors.
and accordingly, might have to be derated. More importantly,
the zero-sequence third-harmonic current circulating through loops entirely, or by providing enough impedance in the zero-
the loop would tend to pick up the ground relays of both sequence circuit to limit circulating currents to tolerable
generators, causing mysterious false tripping of the generator levels.
breakers. (In a 13.8-kV system, for instance, the circulating
current is 36.9 A, versus a typical ground relay pickup current INTERNAL GROUND FAULTS IN GENERATORS
of 25 A for the 5000-kVA generator.) Generators differ from passive components of a power
For a more complicated example, assume the same genera- system in that they are sources of electric energy. Thus, a
tors operate at 13.8 kV and each is grounded through a fault inside a generator is supplied with current not only from
separate 19.92-Ql 400-A 10-s resistor (Fig. 3). Since the loop the power system beyond the machine terminals, but also
now contains two resistors, at 0.833-pu resistance apiece internally. This poses an interesting dilemma when a generator
(7500-kVA base), the magnitude of the loop impedance is is operated with a resistance-grounded neutral, especially
when the machine has no neutral circuit breaker (as is usually
i ZL I = N/1 .67 ±+0.5 1 2 = I .75 pu. the case in industrial installations).
Differential or neutral overcurrent relays normally detect
The circulating current is 0.0343 pu (7500-kVA base) or ground faults in generators and trip the generator stator and
only 10.8 A. The rms current the 5000-kVA
in G1 is only field breakers. This leaves the neutral end of the faulted wind-
1.001 pu; this presents no overload threat to the generators. ing still grounded. Since the fault current is severely limited
However, it amounts to 2.7 percent of the 10-s resistor rating, by the grounding resistor, the internal voltage of the machine
which is high enough to justify checking the continuous decays relatively slowly (approximately with the open-circuit
capacity of the resistor with the manufacturer. It might also time constant T'do), and fault current continues to flow for
be enough to cause misoperation in very sensitive ground quite some time after the breakers trip. Considerable damage
relaying and produces a continuous I2R loss of 4.6 kW in the can be done in this interval.
resistors. For instance, consider a 13.8-kV generator with a 400-A
As should be apparent, third-order harmonic current prob- grounding resistor (Fig. 4). If one phase suffers a ground
lems can be prevented by either avoiding zero-sequence fault at the midpoint of the winding, the driving voltage of
556 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-17, NO. 6, NOVEMBER/DECEMBER 1981
GROUNDING RECOMMENDATIONS
Considering the issues discussed above and general good
system grounding practice, we can offer some recommenda-
tions for neutral grounding on industrial and commercial Richard H. McFadden (S'67-M'67-SM'77)
systems with generators at distribution voltage. received the B.S.E.E. degree from Lehigh
1) Avoid solidly grounding a distribution-voltage generator University, Bethlehem, PA, in 1967, and the
J.D. degree from Duquesne University, Pitts-
neutral, unless the generator is known to be designed for burgh, PA, in 1976.
this service. Although reactance grounding is usually recom- In 1967 he joined Westinghouse Electric
mended as the alternative to solid grounding for generators, Corporation as an Industrial District Engineer,
and since then has held a number of engineering,
it is expensive, allows destructively high fault currents, and is marketing, and management positions with
rarely the best choice for units operated at distribution vol- Westinghouse. He is currently Advisory
tage. Either low- or high-resistance grounding will usually Engineer for Product Development Engineering
be the best approach. at the Westinghouse Marine Division, Sunnyvale, CA.
Mr. McFadden is currently Publications Chairman of the Industrial
2) To minimize circulating harmonic current problems Power Systems Department of the Industry Applications Society. He is a
(not to mention potential safety hazards and relay coordina- Registered Professional Engineer in the Commonwealth of Pennsylvania.