Description: Contract No :: Record no. :


LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 1 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
1. RELAY IDENTIFICATION:

Bay No. : Aux. Voltage : 125VDC

Bay Name : Serial No. :

Manufacturer : AREVA Type : MICOM P54331AE6M0540K

C.T Ratio : 3000/1 Amp VT Ratio : 380/0.115kV

Frequency : 50/60 Hz Function : 87L1

Rated Current : 1/5 Amp IP/OP Voltage : 110/125 VDC

Soft Ware : P543____6__540_C Drawing No : 10P54302

Fiber Optic Converter:

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED

1 Inspect for physical damage / defects.


2 Verify connection as per approved drawings.
3 Check tightness of all connections.
4 Check Ferrules.
5 Check apparatus lists.

3. ELECTRICAL TESTS:

1 Case earthing checked


2 Test switch checked for correct function.
3 Human Machine Interface (HMI) checked
4 Indications Checked
5 Reset of indications checked.

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 2 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

4. OPTO I/P STATUS CHECKED:


Apply DC Voltage (125 V) at each terminals of each OPTO I/P.
Check at HMI; System Data Menu; Opto I/P Status; each I/P should change from (0) state (1) state.

5.
OPTO RELAY No TERMINAL FUNCTION STATUS CHECKED L

1 D1 – D2 SPARE
2 D3 – D4 CB CLOSED
3 D5 – D6 CB OPEN
4 D7 – D8 SPARE
5 D9 – D10 SPARE
6 D11 – D12 VT FAIL
7 D13– D14 SPARE
8 D15– D16 SPARE
9 F1 – F2 SPARE
10 F3 – F4 SPARE
11 F5 – F6 SPARE
12 F7 – F8 SPARE
13 F9 – F10 SPARE
14 F11 – F12 SPARE
15 F13 – F14 SPARE
16 F15 – F16 SPARE
ED STATUS CHECKED:

Note: From the Local HMI Go to Commissioning Test, Test LEDS (Apply Test).

LED No FUNCTION COLOUR STATUS CHECKED

1 DIFF TRIP A R
2 DIFF TRIP B R 6.
3 DIFF TRIP C R O
4 DIFF START Y
5 DIFF INTER TRIP R
6 TEST LOOP BACK Y
7 COMM FAIL Y
8 VT FAIL Y
UTPUT CONTACTS FUNCTION CHECKED:

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 3 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
Note: From the Local HMI Go to Commissioning Test, Test mode (blocked), Test Pattern mode and select
each relay to be tested and Apply Contact Test, after test; apply remove test to de-energized the relay.

OUTPUT RELAY No TERMINALS FUNCTION STATUS CHECKED

1 H1 – H2 86C1 DIFF TRIP


2 H3 – H4 SPARE
3 H5 – H6 DIFF TRIP CP,FR,FMK
4 H8 – H9 DIFF START FR
5 H11 – H12 DIFF TRIP A SOE
6 H14 – H15 DIFF TRIP B SOE
7 H17 – H18 DIFF TRIP C SOE
8 G1 – G2 DIFF COMM FAIL SOE
9 G3 – G4 SPARE
10 G5 – G6 SPARE
11 G8 – G9 BATTERY FAIL
12 G11 – G12 V,T FAIL
13 G14 – G15 DIFF. START SOE
14 G17 – G18 SPARE

7. RELAY BURDEN:

ITEM DESCRIPTION DC Voltage Current (mA) Watts Limits W


(V)
1 Normal Condition <11

2 Fault Condition <13


Limits according to the Catalogue for Technical Data – P543/en TD/ H53 – Page : 32
SUPPLY OFF
TERMINALS (CLOSED) - (J11, J12) :

TERMINALS (OPEN) - (J13, J14) :

SUPPLY ON
TERMINALS (CLOSED) - (J13, J14) :

TERMINALS (OPEN) - (J11, J12) :

8. CURRENT TRANSFORMER SHORTING CONTACTS:

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 4 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

Current Input Terminals Shorting Checked


IR C3 – C2 – C1
IB C6 – C5 – C4
IY C9 – C8 – C7
IN C15 – C14 – C13 *
IM C12 – C11 – C10 *

* Not be checked because it is not used in the scheme.


This table according to the Catalogue for Commissioning and Maintenance – P54x/EN CM/G53 – Page No; 11

9. TIME AND DATE CHECK:

If the time and date is not being maintained by an IRIG-B signal, so in the event of the auxiliary
supply failing, with a battery fitted in the relay, the time and date will be maintained.

To test this, remove the auxiliary supply from the relay for approximately 30 seconds, on restoring
the auxiliary supply the time and date should be correct.

Result: ____________

A. SECONDARY INJECTION TEST IN CLOSE LOOP MODE INTERNAL

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 5 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

10. MEASUREMENTS:
- To check secondary values go to measurement 1.
- To check primary values go to measurement setup, set local values to: primary values, then Go to
Measurement 1.
CURRENT INPUTS CHECK:
CT RATIO DISPLAYED DISPLAYED
APPLIED VALUE
INPUT CT APPLIED SECONDARY PRIMARY VALUE
(A)
(A) VALUE (A) (A)
IA
IB
IC
IN **
Limit: Current Measurement Accuracy = 10mA or ± 10% .As per the manual P543/en TD/ H53 – Page: 24
VOLTAGE INPUTS CHECK:
VT RATIO DISPLAYED DISPLAYED
APPLIED VALUE
INPUT VT APPLIED SECONDARY PRIMARY VALUE
(V)
(V) VALUE (V) (KV)
VAB
VBC
VCA
VA
VB
VC
VN**
Limit: Voltage Measurement Accuracy = ±1%. As per the manual P543/en TD/ H53 – Page: 24
ACTIVE, REACTIVE AND APPARENT POWER CHECK:
- Injected 66.4V and 1.0A with 45º lagging. Measurement prints out attached.
- To check the values go to measurement 2.
- Line angle (ӨL) = 45 degree.
- P = V * I * COS (ӨL) and Q = V * I * SIN (ӨL)
Calculated Measured Calculated Measured Calculated Measured
PHASE
(MW) (MW) (MVAR) (MVAR) (MVA) (MVA)
A
B
C
11. PICK UP & DROP OFF TEST FOR DIFFERENTIAL CURRENT (Id):
TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 6 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

To avoid absence of fiber optic communication then blocking of differential protection element;
At Commission Tests menu, Set '' Test Loop back '' is '' Internal ''. Through HMI only.

Pick Up Value = 0.5 x (Is1 + K1 x I bias ) A

Where; K1 = 30 % = 0.3 P.U

Drop Out Value = 0.75 x (Pick Up Value) A

Expected Measured Expected Measured


Injected
SETTING Pick Up Pick Up Drop Out Drop Out
PHASE Current
Is1 (A) Value (A) Value (A) Value (A) Value (A)
I bias A

0.2 0.1 0.115 0.08625


R-N 0.4 0.2 0.23 0.1725
0.6 0.3 0.345 0.2587
0.2 0.1 0.115 0.08625
Y-N 0.4 0.2 0.23 0.1725
0.6 0.3 0.345 0.2587
0.2 0.1 0.115 0.08625
B-N 0.4 0.2 0.23 0.1725
0.6 0.3 0.345 0.2587
R-Y 0.4 0.2 0.23 0.1725
Y-B 0.4 0.2 0.23 0.1725
B-R 0.4 0.2 0.23 0.1725
R-Y-B 0.4 __ 0.23 0.1725

Limits: Pick up & Drop Out ±10%

According to the Catalogue for Technical Data – P543/en TD/ H53 – Page: 10

12. OPERATING TIME TEST FOR DIFFERENTIAL CURRENT (Id):

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 7 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
Set; DT Mode & Is1 = 0.4 In & K1 = 30 % & Is2 = 4 In & K2 = 150 %

Operating Time
Phase Inject current (A) Delay Time (ms)
(ms)
0.8 Zero (Inst)
R 0.8 250
0.8 500
0.8 Zero (Inst)
Y 0.8 250
0.8 500
0.8 Zero (Inst)
B 0.8 250
0.8 500
R-Y 0.8 250
Y-B 0.8 250
B-R 0.8 250
R-Y-B 0.8 250

Accuracy:
Instantaneous Operation: <30 ms.
Definite Time Operation: ± 2 % or 20 ms whichever is greater.
According to the Catalogue for Technical Data – P543/en TD/ H53 – Page: 10
According to the Catalogue for Twice time current injected – P54X/ENCM- Page: 174 Sec 6.3.3.2

13. BIAS CHARACTERISTIC TESTING:

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 8 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

For local testing of the relay put in the Loop back mode, At Commission Tests menu, Set '' Test Loop
back '' is '' Internal ''. Through HMI only.

І – LOWER SLOPE

Connect the test circuit as shown figure.

Current is injected into the R phase which is used as the bias current and another current is injected
into the Y phase which is used as differential current.
Inject a bias current of 1A in the R phase. The relay will trip and any LED associated with the R
phase will operate.
Slowly increase the current in the Y phase until phase Y trips . Record the phase Y current
magnitude and check that it corresponds to the following equation;
Id Calculated = 0.5 * (Is1 +I bias K1) A
Where; IS1; The Basic Diff Current Setting.
K1; The Lower Percentage Bias Setting.

Set; IS2 = 4 In

To check more than one point at the same slope, Change the bias current value and the equation
above can be used, and also for other differential settings '' Different slopes, I s1 ''.
Apply the above procedure for each phase.

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 9 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
K1 IS1 I bias Id calculated Id Measured Errors %
A R Y B R Y B
1 0.25
0.2 2 0.4
3 0.55
1 0.35
30 % 0.4 2 0.5
3 0.65
1 0.45
0.6 2 0.6
3 0.75
1 0.3
0.2 2 0.5
3 0.7
1 0.4
40 % 0.4 2 0.6
3 0.8
1 0.5
0.6 2 0.7
3 0.9
1 0.35
0.2 2 0.6
3 0.85
1 0.45
50 % 0.4 2 0.7
3 0.95
1 0.55
0.6 2 0.8
3 1.05
Limits; ± 10 % According to the Catalogue for Commissioning and Maintenance – P54x/EN CM/G53 –
Pages No; 30 & 31

П– UPPER SLOPE
TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 10 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

Repeat the test and check the result with the following equation;
Id Calculated = 0.5 X [(6 X K2) – {(K2 – K1) X IS2} + IS1] A
Is2; The Bias Current Threshold Setting.
K2; The High Percentage Bias Setting.
IS1 & K1 are Fixed; IS1 = 0.2 A , K1 = 30 %

Id Id Measured Errors %
K2 Is2 I bias A
calculated R Y B R Y B
5 1.15
2 6 1.4
7 1.65
5 1.05
50% 3 6 1.3
7 1.55
5 0.95
4 6 1.2
7 1.45
5 1.9
2 6 2.4
7 2.9
5 1.55
100 % 3 6 2.05
7 2.55
5 1.2
4 6 1.7
7 2.2
5 2.65
2 6 3.4
7 4.15
5 2.05
150% 3 6 2.8
7 3.55
5 1.45
4 6 2.2
7 2.95
Limits; ± 10 % According to the Catalogue for Commissioning and Maintenance – P54x/EN CM/G53 –
Pages No ; 30 & 31

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 11 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
14. VTS FUNCTION TEST:

LOSS OF ONE OR TWO PHASE TEST:

FIXED SETTING Negative sequence threshold used by the elements are V2= 10V.
(As per Catalogue P54x/EN OP/B74 Page No:05)
Note: Inject three phase (66.4) balance voltage during test of particular phase to reduce that phase
voltage until the fuse failure operates.
Phase Under Measure Voltage Measure Neg Seq
Set Time (Sec) Measured Time (Sec)
Test (Vo) Volts Voltage (V2)
A
B

LOSS OF THREE PHASE VOLTAGE TEST:

FIXED SETTING Phase voltage level detector is fixed and will drop off at 10V and pick up at 30V.
(As per Catalogue P54x/EN OP/B74 Page No: 05)
Note: Inject three phase (66.4) balance voltage during testing all phase voltage decrease until the fuse
failures operate.

Measure Voltage Volts Drop out Voltage Volts Set Time (Sec) Measured Time (Sec)

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 12 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
15. FINAL SETTING:

CT Ratio 2000/1 Amp

PT Ratio ; 380/0.115 kV

General Configuration:

Setting Group ; Group 1

Phase Differential: Enabled

Differential Prot Comm IM64

Scheme Set:
Address:
Baud Rate:
Clock Source:
Communication Delay Tolerance:
Communication Fail Timer:
Char Mode Time:

Differential Characteristics Configuration


Phase Is1:
Phase Is2:
Phase K1:
Phase K2:
Phase Characteristic:
Phase Time Delay:
Phase TMS:
Phase Time Dial:
P I T Time:
Compensation:
Susceptance:
Inrush Restraint:
Vector compensation:
Phase CT Correction:
E.F CT Correction:

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 13 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
Pick Up & Drop Off Test for Differential Current (id):

Expected Measured Expected Measured


Injected
SETTING Pick Up Pick Up Drop Out Drop Out
PHASE Current
Is1 (A) Value (A) Value (A) Value (A) Value (A)
Ibais A

R-N 0.4 0.2 0.23 0.1725


Y-N 0.4 0.2 0.23 0.1725
B-N 0.4 0.2 0.23 0.1725
R-Y 0.4 0.2 0.23 0.1725
Y-B 0.4 0.2 0.23 0.1725
B-R 0.4 0.2 0.23 0.1725
R-Y-B 0.4 0.2 0.23 0.1725

Limits: Pick up & Drop Out ±10%


According to the Catalogue for Technical Data – P543/en TD/ H53 – Page: 10

Operating Time Test for Differential Current (id):

Injection Current = Is1 = 0.4 A


PHASE Delay Time (ms) Operating Time (ms)

R
Y
B
R-Y
Y-B
R-B
R-Y-B
Accuracy: Definite Time Operation; ± 2 % or 20 ms whichever is greater.

BIAS CHARACTRISTIC:
TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 14 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
І – LOWER SLOPE
IS1; the Basic Diff Current Setting.
K1; the Lower Percentage Bias Setting.

Id Id Measured Errors %
K1 IS1 I bias A
calculated R B Y R B Y
1 0.35
30 % 0.4 2 0.5
3 0.65
Limits; ±10 % According to ''Catalogue: Commissioning and Maintenance – P54x/EN CM/G53 – Pages No 30 & 31''
П– UPPER SLOPE
Is2; The Bias Current Threshold Setting.
K2; The High Percentage Bias Setting.

Id Id Measured Errors %
K2 IS2 I bias A
calculated R B Y R B Y

5 1.45
4
150 % 6 2.2

7 2.95

Final Setting Issue No. : ________________

Final Setting Issue Date : ________________

B. END TO END TEST (Final Setting)


TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 15 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

P591 INTERFACE UNIT CHECK:

Sr. No P591 Interface Units Checks Result

Visual Inspection - Channel 1 Unit


1 - Channel 2 Unit
Rating information - Channel 1 Unit
2 - Channel 2 Unit
Case Earthing - Channel 1 Unit
3 - Channel 2 Unit
Wiring against Diagram - Channel 1 Unit
4 - Channel 2 Unit
Measured Aux. Supply - Channel 1 Unit
5 - Channel 2 Unit
LED Working - Channel 1 Unit
6 - Channel 2 Unit

LOOPBACK TEST:

Test Method: At P593 unit REMOVE EXTERNAL WIRING FROM TBs 3,4,7 & 8 AND JUMPER TB 3 to
7 AND TB 4 to 8

Sr. No Description Result

Signal strength received by P593 -Channel 1 Unit (-16.8dBm to -25.4dBm)


1 . - Channel 2 Unit (-16.8dBm to -25.4dBm)

Signal strength transmitted by P593 -Channel 1 Unit (-16.8dBm to -28.8dBm)


2 . - Channel 2 Unit (-16.8dBm to -28.8dBm)
o Normalize Tx and Rx cables b/w P543 and P593 and put P543 in Test
loopback ‘External’ mode.
o Reset alarm indications.
o Check loopback alarm is still active and not reset.
3 o Check communication working (Channel status, propagation delay
etc.)

Prop. Delay Channel Status


- Channel 1 Unit
- Channel 2 Unit

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 16 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
COMMINUCATION FAILURE CHECK.

Checked
Function Remote
Local Relay
Relay
Disconnect a fiber optic channel '' Alarm should appeared''

Reconnect a fiber optic channel '' Alarm should disappeared''

Communication equipment

SECONDARY INJECTION CHECK.

SINGLE PHASE INJECTION AT LOCAL RELAY

Phase Injection Current ( A ) Remote End Checked

R 1
Y 1
B 1

SINGLE PHASE INJECTION AT REMOTE END RELAY

Phase Injection Current ( A ) Local Checked

R 1
Y 1
B 1
PICK UP AND DROP OUT TEST FOR DIFFERENTIAL CURRENT (Id):
Pick up value = (Is1 + K1 * Ibias) Ampere.
Ibias = 0.5 (IL + IR)
Drop out value = 0.75 * (pick up value) Ampere.
Phase Setting Is1 (A) Expected Value Measured Pickup Measured
(A) Value (A) Dropout Value (A)
R 0.4 0.46
Y 0.4 0.46
B 0.4 0.46
Limits :Pick up = Setting 10% and Drop out = (0.75 x Setting) 10%. According to Catalogue for technical data –
P543/en TD/J74- Page no 2-6.
OPERATING TIME TEST FOR DIFFERENTIAL CURRENT (Id):
TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 17 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
Phase Injected Current (A) Setting Delay Time Measured Operating
(ms) Time (ms)
R 0.8 0
Y 0.8 0
B 0.8 0
Limits : Definite time operation :  2% or 20ms which ever is greater.
According to catalogue for technical data – P543 /en TD /J74 – page no 2-8.
LOWER SLOP CHECK:
SETTING, IS1 = 0.4 Amp and K1 = 30%
Where Is1 = the basic differential setting.
K1 = the lower percentage bias setting.
Id calculated = (Is1 + Ibias K1) Ampere.
Ibias = 0.5 (IL + IR)
Note: Inject the both ends bias current same, adjust the differential current zero by current angle then
increase the local current until the relay operates. Record the differential and Bias current.

Limits:  10% According to catalogue for CM –P54x/EN CM/I 74 - page no 10-36.

UPPER SLOP CHECK:


TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 18 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV
SETTING, IS1 = 0.4 Amp, IS2 = 4.0 Amp, K1 = 30% and K2 = 150%.
Id calculated = K2* Ibias – (K2 - K1)IS2 + IS1 Ampere.
Ibias = 0.5 (IL + IR)
Note: Inject the both ends bias current same, adjust the differential current zero by current angle then
increase the local current until the relay operates. Record the differential and Bias current.

Limits :  10% According to catalogue for CM –P54x/EN CM/ I 74- page no 10-37.

MEASURED DIFFERENTIAL CURRENT:


Injected CURRENT 1Amp From one side.
Go to Measurement 3 and record the Differential Current.

DIFFERENTIAL CURRENT
Phase
CT REVERSE CT NORMAL
R
Y
B

INTERTRIP CHECK

Put a jumper between terminals ''H1 & H2'' intertrip output contact, the remote end CB should
tripped, and repeat this from remote end.

Inter trip Function CB Trip Checked

From Local Relay


From Remote Relay

C. ONLOAD CHECKS
TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 19 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

CONFIRM CURRENT TRANSFORMER WIRING

Phase Secondary Current Values Secondary Current Values With The Errors
Using a Multimeter Relay's Measured

Limits; 1 % According to the Catalogue for Commissioning and Maintenance – P54x/EN CM/G53 –
Page No ; 40

MEASURE CAPACITIVE CHARGING CURRENT

With the feeder energized from one end only, Compare local and remote measured currents in the
MEASUREMENT 3 menus at HMI to confirm that the feeder capacitive charging current is similar to
that expected on all three phases.
Check that the setting of ( Is1 ) is higher than 2.5 times the capacitive charging current.

Phase Local Current Remote Current Check Is1 > 2.5 Icap

According Catalogue for Commissioning and Maintenance – P54x/EN CM/G53 – Page No; 40

CHECK DIFFERENTIAL CURRENT


TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :


SSSS SSSSSSSSSS SSS SSSS SSSSSS
Description: Contract No :: Record no. :
LINE DIFFERENTIAL MICOM P543 10631156/00

CONTRACTOR: End Client: Sheet:


SIEMENS CO. LTD SEC-COA 20 of 20
Site: Panel / Designation / Location no.: Project no.:
S/S 9019 380 kV

With the feeder supplying load current check that the relay measurements in the MEASUREMENTS 3
menu at HMI are as expected and that the differential current is similar to the value of capacitive
charging current previously measured for all three phases.

Phase Current Differential Measured Check Id ≈ Icap

18. REMARKS:

ATTACHMENTS;

1- Final setting file is downloading from the relay and printed.

2- PSL '' Programmable Logic Scheme'' files which include a configuration of I/P & O/P
contacts and Leds, is downloading from the relay and printed.
3- An example of one disturbance viewed by WINWAVE program is retrieved and printed.

TESTED BY : Thyssenkrupp Xervon COUNTER SIGNED BY : SIEMENS WITNESSED BY : SEC-COA

NAME : Ghulam Murtaza NAME : TAHIR MAHMOUD NAME :WALI MUHAMMAD

SIGNATURE : SIGNATURE : SIGNATURE :