Sunteți pe pagina 1din 47

“RCC DESIGN AND DETAILING AS PER

REVISED
SEISMIC CODES”

presented by
Sangeeta Wij,
Managing Partner,
SD Engineering Consultants LLP
VP North, IAStructE
Important provisions of revised Seismic
Codes affecting RCC design and detailing
• Planning of building Configuration as per definition of Regular
Geometry in BIS:1893 has been revised
• Load Combinations have been revised as Vertical Earthquake
Force(with Sa/g=2.5) is now mandatory for all Zone 4 and 5 buildings.
• Stiffness modifiers have been incorporated (Attn: Software Vendors)
• Flat Slabs, Precast, PT systems to be used only after performing Non
Linear Analysis and adequate experimentation
• Floating/Stub Columns have been completely prohibited
• Open Storeys need to incorporate bracings/RC Shear Walls
• Design eccentricity at every floor has been revised and must be
checked accordingly(Attn: Software vendors)
• Importance Factors have been revised to 1.2 min.for >200 occupancy
buildings and minimum Earthquake Shear specified for all zones
Important provisions of revised
Codes…continued
• Foundations: No Isolated footings to be provided if Nc< 10
• Columns: minimum size to be 20dia(beam reinforcement
passing through the column) or 300mm
• Strong Columns only allowed to participate in resisting
Lateral Loads(check if Column strength >1.4 times Beam
Strength at every joint)
• All other columns to be designed as Gravity columns and
checked for bending/shear induced by R times
displacement.(Attn: Software Vendors)
• Beams: Ductility provisions to be similar to that of columns
and spacing governed by the same formula, maximum
ductile spacing is now 100mm
(Attn: Software Vendors)
Queries for BIS
• Way forward to be mandated for existing/under
construction buildings not conforming to current
provisions, especially Flat Slabs and PT buildings
without Adequate Shear Walls to carry 100% Base
Shear
• Way forward for Irregular Geometries under various
clauses to be clarified as 3D analysis is always carried
out these days for all important Projects, and referring
to specialist literature to correct irregularity cannot be
a Way Forward.
• Non Tower Area Columns’ and retaining Walls’ design
in large high rise developments may be covered in
more detail
S.No IS:13920;1993 IS:13920;2016

1. GENERAL As per 1.1.2 As per 1.1.2


SPECIFIC
ATION • The provisions for RC
• The provisions for RC construction given
construction given
herein apply specifically to monolithic
herein apply
reinforced concrete construction.
specifically to
• Precast and/or prestressed concrete
monolithic
members may be used only if they can
reinforced concrete
provide the same level of ductility as that
construction.
of a monolithic reinforced concrete
construction during or after an
earthquake.
• Precast and/or
• Likewise, flat slab structures must have a
prestressed concrete
lateral load resisting systems capable of
members may be used
providing similar level of performance as
only if they can
envisioned in this standard and must be
provide the same level
designed for drift compatibility as per 11.
of ductility as that of a
• Specialist literature must be referred to for
monolithic reinforced
design and construction of such structures.
concrete construction
The adequacy of such designs shall be
during or after an
demonstrated by adequate, appropriate
earthquake.
experimentation and non-linear dynamic
structural analyses.
As per 1.1.3 of IS:13920;2016

 All RC frames, RC walls:

• need not be designed to resists lateral loads.


• The designer can identify the lateral load resisting system based on relative
stiffness and locations in the building and design those members for full lateral
force.

 RC monolithic members are assumed:

• not to participate in the lateral force resisting system


• their effect on the seismic response of the system is accounted for:

 Consequence of failure of structural and non-structural members, not part of the


lateral force resisting system shall also be considered in design.
IS:13920;1993 IS:13920;2016

A) As per clause 5.2 A) As per clause 5.2:


• For all buildings that are more than 3 • Minimum grade of structural
story's in height, minimum grade of concrete shall be M20, but M25
concrete shall be M20 (fck = 20 MPa). for buildings more than 15m in
height in Seismic Zones III, IV,
V; and
• But not less than that required
by IS 456 based on exposure
conditions.
• However, CPWD Specs of 2009
clause 5.1.2.1 (ii) states that
structural concrete shall be of
minimum grade M25.
2. FLEXURAL IS 13920;1993 IS 13920;2016
MEMBERS/BEA
MS
As per clause 6.1.1: As per clause 6.1:
a) The factored axial compressive
• The factored axial stress does not exceed 0.08 fck.
stress on the member
under earthquake
loading shall not
exceed 0.1 fck.

As per clause 6.1.3

a) Beams shall not have depth D more


than 1/4th of clear span.
b) This may not apply to the floor
beam of the frame staging of
elevated RC water tank.
IS:13920;2016 FIG-1: BEAM-COLUMN JUNCTION

As per clause 6.1.4:


 Width of the beam bw
shall not exceed the
width of supporting
member c2 plus
distance on either side
of supporting member
equal to the smaller of
a) Width of supporting
member, c2
b) 0.75 times breadth of
supporting member,
c1
3. i) LONGITUDINAL IS:13920;1993 IS:13920;2016
REINFORCEMENT

As per clause 6.2.1 As per clause 6.2.1


a) The top as well as
bottom reinforcement a) Beams shall have at
shall consist of at least 12mm diameter
least two bars bars each at the top and
throughout the bottom faces.
member length.

b) The tension steel ratio b) Minimum longitudinal


on any face, at any steel ρmin required on any
section, shall not be less
than:
face at any section is:
ρmin=0.24√fck/f y
Where, ρmin=0.24√fck/f y
fck and fy are in MPA.
II) SPLICING OF IS: 13920;2016
LONGITUDINAL
BARS
As per 6.2.6.1 .
• Not more than
50% of area of
steel bars on
either top or
bottom face shall
be spliced at any
one section

III) TRANSVERSE As per 6.3.4


REINFORCEMENT  In the calculation
of design shear
force capacity of
RC beams,
contribution of
the following
shall not be
considered:
 Concrete in RC
section.
4. COLUMNS AND
INCLINED IS 13920;2016
MEMBERS

i) Geometry As per 7.1


 For various shapes of columns like “T”shaped,”X”
shaped etc., appropriate designs and detailing shall be
carried out.

As per 7.1.1
The minimum dimension of a column shall not be less
than,
a) 20db,, or
b) 300mm
BUT FIG. SHOWS 15 Dia bar
 AS SHOWN ON NEXT SLIDE
IS:13920;1993 IS: 13920;2016
As per 7.1.3 As per 7.1.2

• The ratio of the shortest 1. The cross-section aspect ratio (shall not
cross sectional dimension be less than ) 0.45.
to the perpendicular
dimension shall preferably • E.g. let us assume (200x400)mm section,
not be less than 0.4. then we have, b/d=0.5, i.e. >0.45
• E.g. let us assume • Hence ok
(300x400)mm section,
then we have, 1. Vertical members of RC buildings whose
b/d=0.66 , i.e. >0.45 cross-section aspect ratio is less than 0.4
Hence ok shall be designed as per requirements of9.
5. IS 13920;2016
AS PER 7.2
Relative Strengths of Beam and
Column at a Joint

As per 7.2.1
 At each beam-column joint of a
moment-resisting frame, the sum
of nominal design strength of
columns meeting at that joint (with
nominal strength calculated for the
factored axial load in the direction of
the lateral force under consideration
so as to give least column nominal
design strength) along each principal
plane shall be at least 1.4 times the
sum of nominal design strength of
beams meeting at that joint in the
same plane.
6. Longitudinal IS 13920:1993
Reinforcement

As per 7.2.1
1. Lap splices shall be provided only in the central half of
the member length. It should be proportioned as a
tension splice.

1. Hoops shall be provided over the entire splice length at


spacing not exceeding 150 mm center to center. Not
more than 50 percent of the bars shall be spliced at one
section.
IS 13920;2016 As Per 7.3.2.1
Lap Splices

As per 7.3.2 1. When adopted, closed links shall be provided over the
entire length over which the longitudinal bars are
Splicing of
spliced. Further:
Longitudinal a) The spacing of these links shall not exceed
Reinforcement 100mm.
b) The lap length shall not be less than the
developmental length of the largest longitudinal
reinforcement bar in tension.
c) Lap splices shall be provided only in the central
half of clear column height, and ????????
1) Within a joint, or
2) Within a distance of 2d from face of the beam.
d) Not more than 50 % of area of steel bars shall be
spliced at any one section.
Suggest laps in alternate bars , not consecutive
bars.
a) Lap splices shall not be used for bars of diameter
larger than 32mm for which mechanical splicing
shall be adopted.
IS 13920;1993 IS 13920;2016
As Per 7.2.2
• Any area of a column that extends more
than 100 mm beyond the confined core
due to architectural requirements shall be
detailed in the following manner.
• In case the contribution of this area to
strength has been considered, then it will
have the minimum longitudinal and
transverse reinforcement as per this code.
Transverse As per 7.4.1
 In either case, the
Reinforcement As per 7.3.1 closed link shall
 A rectangular hoop is a closed have 135° hook
stirrup, having a 135° hook with a ends with an
10 diameter extension (but not < 75 extension of 6
mm) at each end, that is embedded in times its diameter
the confined core (see Fig 7A). (but not <65mm)
at end, which are
embedded in the
confined core of
the column (see
Fig. 10A).
IS 13920:2016

AS PER 7.4.2
1. When rectangular links are used:

a) the minimum diameter permitted of


transverse reinforcement bars is 8mm,
when diameter of longitudinal bar is
less than or equal to 32mm, and
10mm, when diameter of longitudinal
bar is more than 32mm,

2. A cross- tie shall be provided, if length of


any side of the link exceeds 300mm (see
fig 10B); the cross-section shall be placed
perpendicular to this link exceeds whose
length exceeds 300mm. Alternatively, a pair
of overlapping links may be provided
within the column (see Fig.10C). In either
case, the hook ends of the link and cross –
ties engaging the same longitudinal bars
shall have 90° hooks on opposite sides of
the column. Crossties of the same or
smaller bar.
7. Special Confining
Reinforcement IS 13920;1993 IS 13920;2016

. As per 7.4.5 As per 8.1


1. Special confining
reinforcement shall be provided
over the full height of a column, 1. Flexural Yielding is likely in
which has significant variation in beams during strong
stiffness along its height. earthquake shaking and in
2. This variation in stiffness may columns when the shaking
result due to the presence of intensity exceeds the expected
bracing, a mezzanine floor or a intensity of earthquake
R.C.C. wall on either side of the shaking (see fig 12).
column that extends only over a
part of the column height (see
Fig. 12).
As per 7.4.6
• The spacing of hoops used as
special confining reinforcement
shall not exceed 1/4 of
minimum member dimension
but need not be less than 75
mm nor more than 100 mm.
IS:13920;2016

• The area of cross-section, Ash, 1. This special reinforcement shall,


of the bar forming circular a) Have a spacing not more than,
hoops or spiral, to be used as 1) 1/4 of minimum member
special confining dimension of the beam and
reinforcement, shall not be less column,
than :- 2) 6 times diameter of the smallest
longitudinal reinforcement bars;
Ash=0.09 SDkfck⁄fy (Ag⁄Ak- and
1) 3) 100mm link
b) Have area Ash of cross section of the
bar forming links or spiral of at least:
1) in circular links or spirals:

Ash=Max of {0.09 Sv DKfck⁄fy Ag⁄Ak-1


{0.024 Sv Dkfckfy
IS 13920;1993 IS 13920;2016

As per 7.4.8 2) In rectangular links:


 The area of cross section,
Ash, of the bar forming Ash=Max of {0.18 Svh fck⁄fy (Ag⁄Ak-1)
rectangular hoop, to be used {0.05 Svhfckfy
as special confining
reinforcement shall not be
less than:

Ash = 0.18 Sh
fck⁄fy[Ag⁄Ak]
7. SPECIAL
CONFINING IS 13920;1993 IS 13920;2016
REINFORCEMENT
As per 8.4
 Special Confining Reinforcement shall
be provided over the full height of a
column, which has significant variation
in stiffness along its height.
 This variation in stiffness may result
due to abrupt changes in cross-section
size, or unintended restraint to the
column provided by stair-slab,
mezzanine floor, plinth or lintel beams
framing into the columns, RC walls or
masonry wall adjoining column and
extending only for partial column height.
As per8.1

 The special confining


reinforcement as required
at the end of column shall
be provided through the
joint as well, unless the
joint is confined as
specified by 8.2.
SOECIAL CONFINING IS 13920:1993
REINFORCEMENT
As per 8.2
 A joint, which has
beams framing into all
vertical faces of it and
where each beam width
is at least 3/4 of the
column width, may be
provided with half the
special confining
reinforcement required
at the end of the
column.
 The spacing of hoops
shall not exceed 150
mm.
IS13920;2016

8. BEAM Design of Beam As per 9.1.1


Shear Strength of Concrete in a joint
COLUMN Column Joint for
JOINTS OF Distortional
τje=1)1.5 Aej √fck
MOMENT Shear
2)1.2 Aej √fck
RESISITING
3)1.0 Aej √fck
FRAMES
NOTE: 1) for joints confined by beams on all four
faces
2) for joints confined by beams on three faces
3) for other joints
Aej, is effective shear area of joint given by bjwj, in
which bj is the effective breadth of joint
perpendicular to the direction of shear force and wj
the effective width of joint bj (see Fig.15) shall be
obtained from following:
Min [bb; bc+0.5hc] if bc<bb
Where
bb=width of beam and bc = width of column
hc= depth of column in considered direction.
As per 9.1.2
Design Shear Stress Demand on a Joint
a) Design shear stress demand acting horizontally along each of the two principal
plan directions of the joint shall be estimated from earthquake shaking
considered along each of these directions, using:

τjdX=VdjX⁄bjwj

for shaking along plan direction X of Earthquake shaking

τ VdjY⁄bjwj
jdY=

for shaking along plan direction Y of earthquake shaking


It shall be ensured that the joint shear capacity of joint concrete estimated using 9.1.1
exceeds both .
τjdX and τjdY.

b)Design shear force demand VjdX and VjdY acting horizontally on the joint in principal plan
directions X and Y shall be estimated considering that the longitudinal beam bars in tension
reach a stress of 1.25 fy (when over strength plastic moment hinges are formed at beam
ends).
IS 13920;2016

As per 9.1.3
Width of Beam Column
Joint
When beam
reinforcement extends
through beam – column
joint, the minimum
width of the column
parallel to beam shall be
20 ???? or 15 ??? times
of the largest
longitudinal beam bar.
Is 13920;2016

As per 9.2
As Per 9.2.1
 Confining reinforcements in Joints
a) When all four vertical faces of the joint are having beams framing into them
covering at least 75 percent of the width on each face,
b) At least half the special confining reinforcement required as per 8 at the two ends of
columns, shall:
be provided through the joint within the depth of the shallowest beam framing
into it; and
2)When all four vertical faces of the joint are not having beams framing into
them or when all four vertical faces have beams framing into them but do not
cover at least 75 percent of the width on any face,

1) Special Confining reinforcement required as per 8 at the two ends of columns shall be
provided through the joint within the depth of the shallowest beam framing into it, and
2) Spacing of these transverse links shall not exceed 150mm.
As per 9.2.2
 In the exterior and corner joints, all 135-degreehooks of crossties should be along the
outer face of columns.
9. SHEAR IS 13920;1993 IS 13920;2016
WALLS

As per 9.1.2 As per 10.1.2


• The thickness • The thickness of any part of the wall shall
of any part of preferably, not be less than:
the wall shall • 150 mm; and
preferably, not • 300mm for buildings with coupled shear
be less than walls in any seismic zone.
150 mm. • The minimum thickness provided must
confirm to the fire resistance requirements
based on occupancy as laid down in IS 456.

As per 10.1.4
• Special shear walls shall be classified as
squat, intermediate or slender depending on
the overall height hw to length Lw ratio as
• Squat walls: hw/Lw<l,
• Intermediate walls: l<=hw/Lw<=2,and

• Slender wall: hw/Lw>2


IS 13920;1993 IS 13920;2016

As per 9.1.3 As per 10.1.5


• The effective flange width, to be used • In the design of flanged wall sections,
in the design of flanged wall sections, only that part of the flange shall be
shall be assumed to extend beyond considered which extends beyond the
the face of the web for a distance face of the web of the structural wall
which shall be the smaller of (a) half at least for a distance equal to smaller
the distance to an adjacent shear wall of,
web, and (b) 1/10 th of the total wall • actual width available
height. • half the distance to the adjacent
structural wall web; and
• 1/10th of the total wall height.
IS 13920;1993 IS 13920;2016

As per 9.1.4 As per 10.1.7

• Shear walls shall be provided with Special shear walls shall be


reinforcement in the longitudinal and provided with uniformly spaced
transverse directions in the plane of the reinforcement in its cross-section
wall. The minimum reinforcement ratio along vertical and horizontal
shall be 0.002 5 of the gross area in each directions. At least a minimum area
direction. This reinforcement shall be of reinforcement bars as indicated
distributed uniformly across the cross in Table1 shall be provided along
section of the wall. vertical and horizontal directions.
IS 13920;1993

As per 9.2.2
The design shear strength of concrete, Ţc, shall be calculated as per Table
13 of IS 456: 1978.

As per 9.2.4
When 𝜏v is less than Ţc shear reinforcement shall be provided in
accordance with 9.1.4, 9.1.5 and 9.1.7.
IS 13920;1993 IS 13920;2016

As per 9.2.5
When Ţv is greater than Ţc , the area of
horizontal shear reinforcement, Ah, to be
provided within a vertical spacing, Sv, is given by:

Vus = 0.87fyAhDwSv

Where Vus= (Vu– c tw dw ), is the shear force to


be resisted by the horizontal reinforcement.
However, the amount of horizontal
reinforcement provided shall not be less than
the minimum, as per 9.1.4.

As per 9.2.6 As per 9.2.2


The vertical reinforcement that is uniformly The design shear strength of concrete, c,
distributed in the wall shall not be less than shall be calculated as per Table 19 of IS
the horizontal reinforcement calculated as 456.
per 9.2.5.
IS 13920;2016

As per 10.2.3
𝜏
When nominal shear stress demand v on a wall is:
a) more than 𝜏vmax of concrete (given in Table 20 of IS 456), the wall section shall
be re-designed;
b)less than maximum design shear strength 𝜏cmaxof concrete and more than
design shear strength c of concrete, design horizontal shear reinforcement shall
be provided of area Ah given by:

Ah = Vus⁄0.87 f {d⁄S }
y v integral Vu- τc twdw0.87 fy{d⁄Sv}integral

Which shall not be less than the minimum area of horizontal steel as per
10.1.5;and
c) less than design shear strength of concrete, horizontal shear reinforcement
shall be the minimum area of horizontal steel as per 10.1.5
IS 13920;1993 IS 13920;2016

FLEXURAL As per 9.3 As per 10.3


STRENGTH/DESIG • Flexural Strength • Design for Axial Force and Bending
Moment
N FOR AXIAL •
• As per 9.3.1 As per 10.3.1
FORCE AND • The moment of resistance, Muv, • Design moment of resistance Mu
BENDING of the wall section may be of the wall section subjected to
MOMENT calculated as for columns combined bending moment and
subjected to combined bending compressive axial load shall be
and axial load as per IS 456: 1978. estimated in accordance with
requirements of limit state design
• The moment of resistance of method given in IS 456, using the
slender rectangular shear wall principles of mechanics involving
section with uniformly distributed equilibrium equations, strain
vertical reinforcement is given in compatibility conditions and
Annex A. consecutive laws.
• The moment of resistance of
slender rectangular structural wall
section with uniformly distributed
vertical reinforcement may be
estimated using expressions given
in Annex A.
• Expressions given in Annex A are
not applicable for structural walls
with boundary elements.
IS 13920;1993 IS 13920;2016

As per9.3.3 As per 10.3.3


• In walls that do not have • In structural walls that do
boundary elements, not have boundary
vertical reinforcement shall elements, at least a
be concentrated at the minimum of 4 bars of
ends of the wall. Each 12mm diameter arranged
concentration shall consist in 2 layers, shall be
of a minimum of 4 bars of concentrated as vertical
12 mm diameter arranged reinforcement at the ends
in at least 2 layers of the wall over a length
not exceeding twice the
thickness of RC wall.
IS 13920;1993 IS 13920;2016

As per 10.4.2
• A boundary element shall have adequate axial
load carrying capacity, assuming short column
action, so as to enable it to carry axial
compression arising from factored gravity load
and lateral seismic shaking effects.

As per 9.4.2 As per 10.4.2.1


• A boundary element shall have adequate axial
load carrying capacity, assuming short column • The load factored for gravity load shall be taken
action, so as to enable it to carry an axial as 0.8, if gravity load gives higher axial
compression equal to the sum of factored compressive strength of the boundary.
gravity load on it and the additional
compressive load induced by the seismic force. As per 10.4.3
The latter may be calculated as: • The vertical reinforcement in the boundary
elements shall not be less than 0.8 percent and
(Mu-Muv)⁄Cw not greater than 6 percent; the practical upper
limit would be 4 percent to avoid congestion.
Where,
Mu = factored design moment on the entire wall section,
Muv = moment of resistance provided by distributed vertical
reinforcement across the wall section, and
Cw = center-to-center distance between the boundary
elements along the two vertical edges of the wall.
IS 13920;1993 IS 13920;2016
COUPLED As per 9.5 As per 10.5
SHEAR Coupled Shear walls • Coupling Beams
WALLS/COUP As per 9.5.1 • As per 10.5.1
• Coupled shear walls shall be • Coplanar special structural walls may be
LING BEAMS connected by means of coupling beams.
connected by ductile coupling
beams. If the earthquake • As per 10.5.2
induced shear stress in the • If earthquake induced shear stress Ţve in
coupling beam exceeds coupling beam exceeds

Ls √fck ⁄ D τve >0.1√fck(Ls⁄D)

• ls is the clear span of the coupling • Where Ls is clear span of coupling beam
beam and and
• D is its overall depth, • D overall depth,
• the entire earthquake induced • the entire earthquake –induced shear,
shear and flexure shall, preferably, bending moment and axial compression
be resisted by diagonal shall be resisted by diagonal
reinforcement. reinforcement alone.
IS 13920;1993 IS 13920;2016

As per 9.7 As per 10.5.3


Discontinuous Walls • The diagonal of a coupling beam
shall be anchored in the adjacent
• Columns supporting walls with an anchorage length of
discontinuous walls shall be 1.5 times the development length
provided with special confining in tension
reinforcement, as per 7.4.4
IS 13920;1993 IS 13920;2016

11. Development, As per 9.92 As per 10.8.3


splice and Splices
Anchorage • Splices in adjacent As per 10.8.3.1
Requirement bars should be Lap splices
staggered by a • Closed links shall be provided over the entire
length over which the longitudinal bars are
minimum of 600 spliced.
mm. • Further,
• a) The spacing of these links shall not exceed
150mm.

• b) The lap length shall not be less than the


development length of the largest longitudinal
reinforcement bar in tension.

• c) Lap splices shall be provided only in the


central half of clear wall height, and not,
• 1) Within a joint; or
• 2) Within a distance of 2d from location where
yielding of reinforcement is likely to take place.

• d) Not more than 50 percent of area of steel


bars shall be spliced at any one section.
IS 13920;1993

As per9.9.3
shall be provided around lapped spliced bars
that are larger than 16 mm in diameter.
• The diameter of the tie shall not be less than one fourth
that of the spliced bar nor less than 6 mm.
• The spacing of ties shall not exceed 150 mm center to
center.
GRAVITY COLUMNS
AS PER IS 13920;2016
GRAVITY COLUMNS IN BUILDINGS

• Gravity columns shall be detailed according to and for Bending moments


when subjected to “R” times the design lateral displacement under the factored
equivalent static design seismic loads given by IS 1893(Part-1).

• As Per 11.1
• The provisions in and shall be satisfied, when induced bending
moments and horizontal shear forces under the said lateral displacement
combined with factored gravity bending moment and shear force do nor exceed
the design moment of resistance and design lateral shear capacity of the columns.

• As per 11.1.1

• Gravity columns shall satisfy , and .


• But, spacing of links along the full column height shall not exceed 6 times diameter
of smallest longitudinal bar or 150mm.
• As per 11.1.2

• Gravity columns with factored gravity axial stress exceeding 0.4 fck
shall satisfy and shall have transverse reinforcements at least
one half of special confining reinforcement required by 8.

• As per 11.2

• When induced bending moments and shear forces under said lateral
displacements combined with factored gravity bending moment and
shear force, exceed design moment and shear strength of the frame,
and shall be satisfied.

• As per Mechanical and Welded splices shall satisfy and

• As per Gravity columns shall satisfy and .

S-ar putea să vă placă și