Sunteți pe pagina 1din 4

Fixed systems for gas and fire monitoring

Gasmonitor Plus
Gasmonitor Plus
Gasmonitor Plus is our flexible microprocessor controlled
system designed with a modular approach, so you get exactly
what you want.
Used throughout the world, both on and offshore, Gasmonitor Plus
provides the cost effective solution to your system requirements.
Gasmonitor Plus, the gas and fire control system you can trust.

Simple to use Ground breaking design

Gasmonitor Plus offers flexibility whilst still providing Gasmonitor Plus is a microprocessor based expandable
simple operation. All the day to day functions control system, which can be multiplied to offer
are accessible via push buttons on the unlimited channels and outputs.
front panel.
Its modular construction provides ultimate
As well as a rolling display, indicating the channel customisation capacity with minimal wiring.
currently monitored, each channel has a bar graph
Gasmonitor Plus has industry standard analogue
display. This unique bar graph format is ranged
outputs, and the mechanical design is based on 19”
to indicate readings below the first alarm setting,
Eurorack. This means that the Gasmonitor Plus
providing an instantaneous representation
will integrate fully with existing rack
of the gas concentration on every detector.
mounted protection systems on site.
Common alarm LEDs on the display card and
The alochrome finish and rack screening plates
individual alarms on the panel only light when a
ensure that the Gasmonitor Plus is impervious to
hazard or fault is detected. This means the whole
radio frequency interferance.
rack status can be checked at a glance.

Flexible architecture Easy maintenance

Each channel has three levels of alarm as well Gasmonitor Plus has been designed with
as a dedicated analogue output, set as 4-20 easy servicing and maintenance in mind.
mA as standard.
Each channel is inhibited separately so that
Optional relay modules can interface to the panel to plant safety is not compromised during
provide up to a total of 84 output relays per maintenance checks.
rack. Sixteen of these relays can be configured/
Routine calibration can be achieved from the front
voted from a combination of the three levels of alarm
panel. The one man calibration feature reduces the
per channel.
service overhead by half.
The RS232 digital interface provides connectivity
One universal gas card architecture controls all gas
with PC for configuration, monitoring and datalog
detectors. This reduces the spares holding
upload. Each rack is uniquely addressable, making
required for Gasmonitor Plus maintenance. Each
multi-drop architectures possible. This cuts down on
control card is fitted with its own
configuration and monitoring cabling.
dedicated micro-controller so it can
function independently in the event of a single
point failure.
Large, clear display Individual channel Channel alarm
alarm inhibits indication

Unique
bargraph
reading per
channel

Universal gas
Common alarm indicators input cards

Industry-standard Remote reset switch Dedicated external audio/ Up to 20 smoke/heat


gas detectors visual alarm drive detectors per zone

Optional
Battery
Backup

AC/DC
Power
Options

Analogue outputs per Common and individual


channel channel relays for levels 1, 2,
4-20mA or 1-5Vdc 3 and Fault

Optional voted relays


Gasmonitor Plus

Size 483 x 133 x 294 mm


(19.0 x 5.25 x 11.5 ins)
Weight 9.5 kg (21 lbs)
Enclosure material Aluminium alloy
Mounting Rack mounted (3u format)1
Channels 16 per rack
Inputs Gas 2 or 3 wire, 4-20 mA
(sink or source), or mV bridge
Fire - Smoke detectors, heat Maximum of 32 loops per rack
detectors and manual call points, (i.e. 16 twin zone fire modules)
up to 20 per loop
Outputs Analogue 16 x 4-20mA,
max. load 960 Ohms
or 1-5 V, min. load 100 Ohms
External audio/visual alarm drive Powered 24 V dc, max load
up to 200mA for each alarm level
Relays Type Up to 84 DPCO
contacts rated 5 A @ 250 V ac,
non-inductive load
Assignment - common Alarm 1, Alarm 2, Alarm 3, Fault
- per channel Gas alarms 1, 2 & 3, fire & fault
- voting Up to 16, configurable
Relay modes energised, de-energised & latching, non-latching
Digital Communications DCS/PLC/PC/Local configuration link RS232
Logging Built-in datalogger
- data available via
communication links
Panel indication Channel number 4 lines x 20 characters back-lit LCD display
Gas reading as above plus green LED bar-graph
Measurement units ppm, %LEL, %vol, fire
System fault yellow LED
Alarm indication Audible-internal sounder •
Visual - alarm 3 individual & 3 common alarms (red LED)
- fault individual & common fault (yellow LED)
- inhibit individual inhibit (yellow LED)
Power AC mains 100 - 260 V ac 50/60 Hz external
DC 27.6 V dc,
Battery backup External
Remote Accept/Reset •
Lamp test •
Approvals Low voltage directive Meets BS EN 61010-1
RF immunity Meets EN 50082-1
RF emissions Meets EN 50081-1
Operating Temperature 0 to +50oC (32 to 122oF)
Humidity 0 - 95% non-condensing •

1. Wall mounted and floor standing cabinets are optional, dimensions on request.

P05003 Issue 7 05/07


UK Office USA Office Rotterdam Office Singapore Office
Crowcon Detection Instruments Ltd Crowcon Detection Instruments Ltd Crowcon Detection Instruments Ltd Crowcon Detection Instruments Ltd
2 Blacklands Way 21 Kenton Lands Road Vlambloem 129 Block 194 Pandan Loop
Abingdon Business Park Erlanger 3068JG, Rotterdam #06-20 Pantech Industrial Complex
Abingdon Kentucky 41018-1845 Netherlands Singapore 128383
Oxfordshire  OX14 1DY USA Tel: +31 10 421 1232 Tel: +65 6745 2936
United Kingdom Tel: +1 859 957 1039 or Fax: +31 10 421 0542 Fax: +65 6745 0467
Tel: +44 (0) 1235 557700 1-800-5-CROWCON Email: eu@crowcon.com Email: sales@crowcon.com.sg
Fax: +44 (0) 1235 557749 Fax: +1 859 957 1044 Web Site: www.crowcon.com Web Site: www.crowcon.com
Email: sales@crowcon.com Email: salesusa@crowcon.com
Web Site: www.crowcon.com Web Site: www.crowcon.com
Crowcon reserves the right to change the design or specification of this product without notice

S-ar putea să vă placă și