Tasnee Identification Code

AA-BBBBBB-CC-DD-EEEFF
RELAY COORDINATION STUDY
Tecnimont Identification Code

3276-NN-VD-011079
HDPE 400 KT/Y
Plants :
LDPE 400 KT/Y
Client Ref.: TASNEE Location: AL JUBAIL – KSA Sheet 1/1 Issue 02

RELAY COORDINATION STUDY


Q1-A4D-01

02 REVISION AS PER CUSTOMER COMMENTS Ubiali Gambirasio Ghilardi 19-06-2007


Issue Description Prepared Checked Approved Date
This document is Tecnimont’s property, and cannot be used by others for any purpose, without prior written consent
PT S.p.A.

TASNEE

HDPE/LDPE PROJECT

SWITCHBOARDS

5-SW-600 – 6-SW-600
5-SW-601 – 6-SW-601

RELAY COORDINATION STUDY

Job: 8606001370

Dwg.: 1VCC006007T0601

REV. DATE DRAWN CHECKED APPROVED

0 13/04/07 FIRST ISSUE UBIALI GAMBIRASIO GHILARDI

1 11/06/07 Revision as per customer comments UBIALI GAMBIRASIO GHILARDI

2 19/06/07 Revision as per customer comments UBIALI GAMBIRASIO GHILARDI


Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 2
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

INDEX
1. INTRODUCTION..................................................................................................................... 3

2. SELECTIVITY STUDY ORGANIZATION ............................................................................... 4

3. HYPOTHESIS FOR THE SELECTIVITY STUDY ................................................................... 5

4. RESULTS OF THE SELECTIVITY STUDY ............................................................................ 7

ATTACHMENT “A” 5-SW-600

ATTACHMENT “B” 6-SW-600

ATTACHMENT “C” 6-SW-601

ATTACHMENT “D” 5-SW-601


Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 3
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

1. INTRODUCTION

Scope of the work is the calculation of the protective relays setting value in order to obtain
selectivity in case of faults into the electrical network for the 13.8 & 4.16 kV Tasnee hdpe/ldpe
Project.

Basically, the protective philosophy is based on the knowledge that the faults or abnormal
operating conditions can be lead to:
- overloads;
- phase to phase and three phase faults (phase faults);
- phase to ground faults (ground faults).

The detection of the above conditions is undertaken by the protective relays, whose task is
mainly to shut down the faulted part from operation and separate it from the electrical distribution
system. The setting of the relays has been selected in order to allow a reliable operation of the
system, keeping as long and as much as possible the feeders or the system in service without risk
of damage.

Settings are fairly above any transient current, voltage, frequency etc. conditions, and
intervention times allow for the recovery of these electrical parameters within their normal
operating values.
Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 4
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

2. SELECTIVITY STUDY ORGANIZATION

In order to facilitate the consultation, this document is divided into attachments (one for
each switchgear) that contains data and results that have been used and obtained during the
development of the whole job.

In order to facilitate the consultation, this document contains data and results that have
been used and obtained during the development of the whole job.

The topics are:

- ONE LINE PROTECTIONS DIAGRAM: is drawn in a simplified manner the electrical


network as well as the point of installation of the main relays forming the protective system.

- TRANSFORMERS and MOTORS RATING: schedules of the machine data used for the
relay coordination.

- RELAY SETTING TABLE: characteristics of the relays (manufacturer, type, setting range);
the ratio of measurement transformers (current or voltage) and the setting values at the
primary and secondary side of the measurement transformers. The pages where the
coordination curves are drawn as well as the labels of the relevant curves are indicated into
the columns "curve, page, label".

- SELECTIVITY CURVES: selectivity drawing together with the curves that are significant for
the relay coordination. The relays are identified with a code (where applicable) to allow an
easy identification on the setting tables and coordination sheets. The code is evidenced,
into the one line diagram, with a circle for phase relays and with an ellipse for ground
relays.
Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 5
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

3. HYPOTHESIS FOR THE SELECTIVITY STUDY


3a) Selectivity study is based on short circuit current calculation (estimated), and has been
studied for both with maximum and minimum short circuit currents. The fault current
indicated into the selectivity drawings is the maximum short circuit current of the switchgear
in subject as per short circuit current calculation, including motors fault contribution. Vice
versa, the selectivity curves for each individual user or feeder are drawn up the maximum
short circuit let through fault current.
The maximum phase to ground fault current on 13.8 & 4.16 kV electrical network is equal to
400 A (limited by resistors).

3b) Attention shall be paid to the following when reading the selectivity drawings. In fact, for
ground fault selectivity drawings, the current scale has been divided by 10. Into the left
down corner of the drawings are, in any case, clearly evidenced (if different from one) the
multiplying coefficient of the current in axis.

3c) Into the machine data schedules are listed all the machines data, transformers and motors
used for the study. Where data are up to now not yet defined, an asterisk indicates the
estimated value.

3d) Transformer withstand limit capability (evidenced into selectivity drawings with a point) has
been estimated equal to the maximum short circuit current with upstream infinite power;
time duration equal to two seconds.

3e) Inrush current of the transformers, calculated with equation Imagn = In x k x exp(-t/T)/√2,
has been drawn into the selectivity sheet in order to verify that protections do not operate at
the transformer breaker closing (parameters k and T are reported into transformer
schedule). The RMS value of the magnetising current has been drawn, in order to be
verified with relay measuring criteria.

3f) Into selectivity drawings are evidenced the short circuit current withstand capability of the
cables calculated according with equation I2t = k2S2. The coefficient k for copper cables
(G7) is assumed equal to k=143.
Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 6
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

3g) The motor protection relay group together in a single case all the necessary functions to
protect satisfactory motors. Into the selectivity drawings, are shown the motor operating
curves and the protection curves as per following: 49-51-50-51LR-48-64

The M.V. motors thermal time constant has been set to allow a new start in case of preload
equal to 90% (typical situation in case of automatic transfer). The too long starting
protection has been chosen of inverse time type (I2t), with current and time equal to the
starting condition.

3h) The fault current indicated into the selectivity drawings is the maximum short circuit current
of the bus in subject as per short circuit current calculation, including motors fault
contribution. Consequently the fault contribution through the transformer is lower than this
value. High set settings, of the overcurrent protection at the primary side of the transformer
is based on maximum transformer let through fault current taking into account the source
power and the transformer impedance.
Job: 8606001370
Dwg: 1VCC006007T0601

PT S.p.A. Pag.: 7
Rev.: 2 Date: 19/06/07
TASNEE - HDPE/LDPE PROJECT
SWITCHBOARDS
5-SW-600 – 6-SW-600 – 5-SW-601 – 6-SW-601
RELAY COORDINATION STUDY

4. RESULTS OF THE SELECTIVITY STUDY

4a) The general criteria used for the protection settings are the mixed amperometrical and
chronometrical selectivity. The main point is in any case to assure a complete and sure
protection for the concerned feeder and after, selectivity with upstream and downstream
protections.

4b) Selectivity is assured for phase faults and ground faults into the complete 13.8 & 4.16 kV
electrical distribution network.

4c) MV ground fault selectivity (fault current limited to 400 A):


- motor and transformer feeders: ground overcurrent relays are fed from ring C.T. and
consequently settings can be very low. Settings are assumed equal to 10-40 A (primary
value).
- incomings and bustie ground overcurrent relays are fed in residual connection from
phase C.T.'s. To avoid false trip during transient phenomena (inrush or phase fault
mainly in case of presence of current with DC component), a definite time type
characteristic has been selected with a setting of 6-10% of the C.T. rated current.

4e) ABB REF 542 relays have two independent alternative settings that can be changed via
communication channel. The characteristics of the plant do not require different settings
and consequently primary and secondary settings are identical.

4f) Settings of 13.8 kV incoming relays must be verified with upstream relays in order to
guaranteed selectivity between protections.
JOB.: 8606001370
DWG.: 1VCC006007T0601
PT S.p.A.

TASNEE - HDPE/LDPE PROJECT


SWITCHBOARDS
5-SW-600 – 6-SW600 – 5-SW601 – 6-SW-601 REV.: 2 DATA: 19/06/2007
RELAY COORDINATION STUDY

ATTACHMENT 'A'

SWITCHBOARD 13.8 kV
5-SW-600

ONE LINE DIAGRAM A01

TRANSFORMERS DATA A02

MOTORS DATA A03

RELAY SETTING TABLE A04-A15

SELECTIVITY CURVES A16-A22


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
TRANSFORMERS RATING DWG.: 1VCC006007T0601
VOLTAGE: 13.8 kV PAGE: A02
SWGR: 5-SW-600 REV.: 2 DATE: 19/06/2007

RATED RATED VOLTAGE RATED CURRENT Uk VECTOR IN-RUSH CURRENT NOTE


ITEM
POWER PRIMARY SECOND. PRIMARY SECOND. GROUP K (*) T (*)

[kVA] [V] [V] [A] [A] [%] [x In] [s]

ONAN 50000 34500 14400 837 2005 12.50 Dyn11 5.50 1.00
5-TR-600A / B
ONAF 65000 34500 14400 1088 2606

10650 13800 446 9.40 D 6.40 0.70

5-TR-602A /603A 5325 1725 1782 d11:45

5325 1725 1782 y10:45

10650 13800 446 9.40 D 6.40 0.70

5-TR-602B /603B 5325 1725 1782 d0:15

5325 1725 1782 y11:15

56-TR-611 -612A / B 2500 13800 420 105 3437 9.00 Dyn11 7.50 0.45

5-TR-611 -612 -613 -614A / B 2500 13800 420 105 3437 9.00 Dyn11 7.50 0.45

5-TR-601A / B 15000 13800 4350 628 1991 12.00 Dyn11 6.00 0.80

(*) ESTEEMED VALUE

IN-RUSH CURRENT IS CALCULATED WITH THE FOLLOWING FORMULA: Iin-rush = In x K x exp(-t/T)/√2


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
MOTORS RATING DWG.: 1VCC006007T0601
VOLTAGE: 13.8 kV PAGE: A03
SWGR: 5-SW-600 REV.: 2 DATE: 19/06/2007

LOCKED- THERM.
NUMBER OF STARTING STARTING STARTING
RATED RATED RATED ILR/In ILR/In ROTOR CONST.
/HOUR TIME TIME
ITEM TIME (Un) TIME
at 100%
POWER VOLTAGE CURRENT COLD HOT at 100% Un at 100% Un at Umin at Umin
Un

[kW] [V] [A] [% di In] [s] [% di In] [s] [s] [min]

5KM-6101A /B 1880 13800 94 3 2 500 5.00 400 11.00 8.00 6.00

(*) ESTEEMED VALUE


JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A04 #### A
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 125 / 1 A16 A3
2 5KM-6101A /B PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110
2
3 Cable= 1x(3x150) mm G 1 RING C.T. ratio: 100 / 1 A22 A3g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 97.5 0.78 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 1880 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 13.8 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 94.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 5.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 5.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.00 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 11.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 25 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 98 0.78 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 415 4.26 11.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 237 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 189 1.51 15.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 98 0.78 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 261 2.68 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 650 5.20 0.08 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A05 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 125 / 1
3 5KM-6101A /B PLUS 1 Star point C.T. ratio 125 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 0 SPABUS CH.: 79
6 I1n [A] = 94 In1= 10-10000 A 94 94 SENSOR: 1,2,3
7 I2n [A] = 94 In2= 10-10000 A 94 94 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO NO
9 threshold current Id1= 0.1-0.5 Ir 0.15
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 In 0.50
14 trip by Id> Id>= 0.5-40 In 7.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A06 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 150 / 1 A17 A4
2 56-TR-611 -612A /B PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 A22 A4g
4 49 θ> Sn [kVA] = 2500 49 THERMAL IMn= 0.1 .. 5.0 In 108 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 105 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 9.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 128 0.85 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 315 2.10 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1425 9.5 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A07 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 150 / 1 A18 A5
2 5-TR-611 -612 -613 -614A /B PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 A22 A5g
4 49 θ> Sn [kVA] = 2500 49 THERMAL IMn= 0.1 .. 5.0 In 108 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 105 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 9.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 128 0.85 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 315 2.10 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1425 9.5 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A08 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 800 / 1 A19 A6
2 5-TR-601A /B PLUS
2
3 Cable= 9x(1x400) mm N 1 RING C.T. ratio: 100 / 1 A22 A6g
4 49 θ> Sn [kVA] = 15000 49 THERMAL IMn= 0.1 .. 5.0 In 648 0.81 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 628 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 12.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 760 0.95 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 2520 3.15 0.75 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 6400 8.0 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 40.00 0.40 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A09 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 1100 / 1 A20 A7
2 5-TR-602 -603A /B PLUS
2
3 Cable= 2x 6x(1x400) mm N 1 RING C.T. ratio: 100 / 1 A22 A7g
4 49 θ> Sn [kVA] = 21300 49 THERMAL IMn= 0.1 .. 5.0 In 924 0.84 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 891 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 9.4 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = D… T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 1100 1.00 0.05 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 2695 2.45 0.25 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 6600 6.0 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 40.00 0.40 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A10 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO 1-2-3 ABB REF 542 1 C.T. ratio: 3150 / 1 A21 A8
2 6-SW-600A PLUS
3 N 1 RING C.T. ratio: 3150 / 1 A22 A8g
4 49 θ> Sn [kVA] = 65000 49 THERMAL IMn= 0.1 .. 5.0 In 2615 0.83 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 14.4 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 In [A] = 2606 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1200
7 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1200
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT VERY INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2678 0.85 0.50 SENSOR: 1,2,3 SPABUS CH.: 57
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 7875 2.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 7875 2.5 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
14 51N Io>> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 189.0 0.06 0.40 SENSOR: 1,2,3 SPABUS CH.: 67
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A11 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 METERING BUSBARS 1-2-3 ABB REF 542 110:√3 110 Busbar A V.T. ratio: 13800:√3 / 110:√3 13800 110 110
2 5-SW-600 PLUS 110:√3 110 Busbar B V.T. ratio: 13800:√3 / 110:√3 13800 110 110
3
4 27A U< UNDERVOLTAGE BUSBAR "A" 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.04 motor shedding SENSOR: 1,2,3 SPABUS CH.: 65
5 59A U> OVERVOLTAGE BUSBAR "A" 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 5.00 alarm SENSOR: 1,2,3 SPABUS CH.: 62
6 27B U< UNDERVOLTAGE BUSBAR "B" 27HIGH DEF. TIME U<<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.05 motor shedding SENSOR: 4,5,6 SPABUS CH.: 64
7 59B U> OVERVOLTAGE BUSBAR "B" 59HIGH DEF. TIME U>>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 5.00 alarm SENSOR: 4,5,6 SPABUS CH.: 61
8
9 BUSBARS 1-2-3 ABB REM 543 1 C.T. ratio: 3150 / 1
10 GEN. SETTINGS: Meas - Measuring mode Fundamental frequency
11 - Drop-off time of the operate time counter 0-1000 ms 100 ms
12 - FOR ALL THE RELAY FUNCTION NOT DESCRIBED INTO THE SETTING TABLE SHALL BE SET 'NOT IN USE' FOR THE OPERATION MODE
13 87 Id> HIGH IMPEDANCE DIFFERENTIAL INSTANT. Id>= 0.5-50 %In t= 0.03 .. 0.50 s 1575 50% 0.03 Diff3 3ΔI>
14 A/B CT's Vk > 660 V
15 Stab. Res. = 544 Ohm - Vs = 272 V
16
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A12 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 BUS TIE 1-2-3 ABB REF 542 1 C.T. ratio: 3150 / 1 (*) A2
2 In [A] = 2606 PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110 110
3 N A22 A2g
4 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT VERY INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2678 0.85 0.50 SENSOR: 1,2,3 SPABUS CH.: 57
5 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 7875 2.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 52
6 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 7875 2.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
7 51N Io>> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 189.0 0.06 0.40 SENSOR: 1,2,3 SPABUS CH.: 67
8 25 ΔU/Δf SYNCHRO-CHECK 25 DEF. TIME ΔU= 0.02-0.4 Un tΔ= 0.2-1000 s 2070 0.15 2.00 SENSOR: 4-5 / 8 SPABUS CH.: 85
9 Δϕ Δϕ= 5-50° 10° 00' 10.0
10 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A13 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 INCOMERS FROM: 1-2-3 ABB REF 542 1 C.T. ratio: 3150 / 1 (*) A1
2 5-TR-600A /B PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110 110
3 N A22 A1g
4 1 Star Point C.T. ratio: 400 / 1 A22 A1gg
5 49 θ> Sn [kVA] = 65000 49 THERMAL IMn= 0.1 .. 5.0 In 2678 0.85 SENSOR: 1,2,3 SPABUS CH.: 74
6 Un [kV] = 14.4 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
7 In [A] = 2606 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
9 T Warn= 50 .. 400 °C 116 ° 116
10 T env= 10 .. 50 °C 50 ° 50.0
11 T rst= 10 .. 400 °C 90 ° 90
12 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT VERY INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2898 0.92 1.00 SENSOR: 1,2,3 SPABUS CH.: 57
13 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 9450 3.00 0.60 SENSOR: 1,2,3 SPABUS CH.: 52
14 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 9450 3.00 0.60 SENSOR: 1,2,3 SPABUS CH.: 51
15 51N Io> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 189 0.06 2.00 SENSOR: 1,2,3 SPABUS CH.: 67
16 51G Io> GROUND FAULT OVERCURRENT DEF. TIME 50GHIGH DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 40 0.10 2.50 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 5.00 Trip SENSOR: 4,5,6 SPABUS CH.: 65
18 59 U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 30.00 Trip SENSOR: 4,5,6 SPABUS CH.: 62
19 67 I> --> DIRECTIONAL PHASE OVERCURRENT 67HIGH DEF. TIME I>>= 0.05-40 In t>>= 0.08-300 s 315.0 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 54
20 REV. DIRECT.
21 67N Io>-> DIRECTIONAL GROUND FAULT OVERCURRENT67NHIGH DEF. TIME IE>>= 0.05-40 In t= 0.04-30 s 315.00 0.10 0.10 SENSOR: I7-U4,5,6 SPABUS CH.: 72
22 Uo= 0.02-0.7 Un 0.10 DIRECTION LINE
23 NETTYPE: GROUNDED (COS PHI)
24 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A14 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 INCOMERS FROM: 1-2-3 ABB REF 542 1 34.5 kV C.T. ratio 1250 / 1
3 5-TR-600A /B PLUS 1 13.8 kV C.T. ratio 3150 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 11 SPABUS CH.: 79
6 I1n [A] = 1088 In1= 10-100000 A 1088 1088 SENSOR: 1,2,3
7 I2n [A] = 2606 In2= 10-100000 A 2606 2606 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO YES
9 threshold current Id1= 0.1-0.5 Ir 0.30
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 0.50
14 trip by Id> Id>= 0.5-40 In 9.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17 87N Iod RESTRICTED EARTH FAULT DIFFERENTIAL 87N INSTANT. SPABUS CH.: 95
18 In [A] = 2606 Ir= 1-100000 A 2606 2606 SENSOR: 4,5,6
19 threshold current Id= 0.1-0.5 Ir 261 0.10 SENSOR: 7
20 unbiased region limit Ib1= 0.01-1 Ir 1303 0.50
21 slighly biased region slope slope= 0.01-2 0.70
22 slighly biased region limit Ib2= 0.01-2 Ir 3258 1.25
23 heavily biased slope slope= 0.1-1 1.00
24 Relay operate angle ROA= 60-180° 75
25 Time t= 0.040 … 100 s 0.05
26
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-600
VOLTAGE: 13.8 kV
PAGE: A15 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
1 INCOMERS FROM: 1-2-3 SIEM 7SD6001 1 LINE CT --> 1250 / 1 Cod. 7816= Existing
2 5-TR-600A /B -…-2DA0 FREQUENCY --> 60 [Hz] Cod. 1101= 60
3 Cod. 1102= 1250 Cod. 1103=1250
4 Pilo wire resist.=0-2000 Ohm Min Trip Comm.=0.01-60 s 0.00 0.20 Cod. 1131= 0.00 Cod.1134= 0.20
5 87L Id> LINE DIFFERENTIAL: INSTANT Id>= 0.5-2.5 In tId>=0-60 s 1.00 0.00 Cod 1501=ON Cod.1503= 1.00 Cod.1525= 0.00
6 Imin 0-1.5 In 0.00 Cod.1523= 0.00
7 Intertrip= ON-OFF Send Prol.trip = 0-5 s ON 0.10 Cod.1541= ON Cod.1542= 0.10
8 Id for spill 0.1-1 In time for spill=5-60 s 0.4 5 Cod.1550= 0.40 Cod.1551= 5
9 Pilot Wire Monitoring Station Identification slave Cod 1601=ON Cod.1602= slave
10 Block diff during failure time for blocking=0.2-60 s on 5.0 Cod.1603= on Cod.1604= 5.0
11 Emergency Overcurrent I>= 0.1-15 In tI>=0-60 s 2.0 0.10 Cod 1701=OFF Cod.1702= 2.0 Cod.1703= 0.10
12 Direct Remote Trip Send Prol.transfer = 0-60 s 0.00 Cod.2203= 0.00
13 Trip Receiver Receive signal.transfer = 0-60 s 0.03 Cod 2301=ON Cod.2303= 0.03
14 Receive Prol.transfer = 0-60 s 0.20 Cod.2303= 0.20
15
JOB.: 8606001370
DWG.: 1VCC006007T0601
PT S.p.A.

TASNEE - HDPE/LDPE PROJECT


SWITCHBOARDS
5-SW-600 – 6-SW600 – 5-SW601 – 6-SW-601 REV.: 2 DATA: 19/06/2007
RELAY COORDINATION STUDY

ATTACHMENT 'B'

SWITCHBOARD 13.8 kV
6-SW-600

ONE LINE DIAGRAM B01

TRANSFORMERS DATA B02

MOTORS DATA B03

RELAY SETTING TABLE B04-B16

SELECTIVITY CURVES B17-B23


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
TRANSFORMERS RATING DWG.: 1VCC006007T0601
VOLTAGE: 13.8 kV PAGE: B02
SWGR: 6-SW-600 REV.: 2 DATE: 19/06/2007

RATED RATED VOLTAGE RATED CURRENT Uk VECTOR IN-RUSH CURRENT NOTE


ITEM
POWER PRIMARY SECOND. PRIMARY SECOND. GROUP K (*) T (*)

[kVA] [V] [V] [A] [A] [%] [x In] [s]

ONAN 50000 34500 14400 837 2005 12.50 Dyn11 5.50 1.00
6-TR-600A
ONAF 65000 34500 14400 1088 2606

56-TR-614A / B 2500 13800 420 105 3437 9.00 Dyn11 7.50 0.45

6-TR-611 -612 -613A / B 2500 13800 420 105 3437 9.00 Dyn11 7.50 0.45

6-TR-601A / B 6300 13800 4350 264 836 6.00 Dyn11 7.00 0.60

5200 13800 218 8.80 D 7.00 0.55

6-TR-602 2600 1725 870 d0

2600 1725 870 y11

(*) ESTEEMED VALUE

IN-RUSH CURRENT IS CALCULATED WITH THE FOLLOWING FORMULA: Iin-rush = In x K x exp(-t/T)/√2


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
MOTORS RATING DWG.: 1VCC006007T0601
VOLTAGE: 13.8 kV PAGE: B03
SWGR: 6-SW-600 REV.: 2 DATE: 19/06/2007

LOCKED- THERM.
NUMBER OF STARTING STARTING STARTING
RATED RATED RATED ILR/In ILR/In ROTOR CONST.
/HOUR TIME TIME
ITEM TIME (Un) TIME
at 100%
POWER VOLTAGE CURRENT COLD HOT at 100% Un at 100% Un at Umin at Umin
Un

[kW] [V] [A] [% di In] [s] [% di In] [s] [s] [min]

6PM-1801A /S 1500 13800 74 3 2 600 3.00 480 5.50 6.00 7.00

6PM-1802A /S 1200 13800 59 3 2 600 3.50 480 6.00 7.00 7.00

(*) ESTEEMED VALUE


JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B04 #### B
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1 B17 B3
2 6PM-1801A /S PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110
2
3 Cable= 1x(3x150) mm G 1 RING C.T. ratio: 100 / 1 B23 B3g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 76.5 0.51 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 1500 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 13.8 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 74.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 5.50 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 30 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 77 0.51 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 386 5.04 8.5 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 224 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 179 1.19 8.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 77 0.51 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 246 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 615 4.10 0.08 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B05 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1
3 6PM-1801A /S PLUS 1 Star point C.T. ratio 150 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 0 SPABUS CH.: 79
6 I1n [A] = 74 In1= 10-10000 A 74 74 SENSOR: 1,2,3
7 I2n [A] = 74 In2= 10-10000 A 74 74 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO NO
9 threshold current Id1= 0.1-0.5 Ir 0.15
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 In 0.50
14 trip by Id> Id>= 0.5-40 In 7.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B06 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1 B18 B4
2 6PM-1802A /S PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110
2
3 Cable= 1x(3x150) mm G 1 RING C.T. ratio: 100 / 1 B23 B4g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 61.5 0.41 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 1200 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 13.8 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 59.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.50 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 6.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 30 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 62 0.41 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 312 5.07 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 178 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 143 0.95 9.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 62 0.41 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 196 3.18 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 495 3.30 0.08 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B07 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1
3 6PM-1802A /S PLUS 1 Star point C.T. ratio 150 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 0 SPABUS CH.: 79
6 I1n [A] = 59 In1= 10-10000 A 59 59 SENSOR: 1,2,3
7 I2n [A] = 59 In2= 10-10000 A 59 59 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO NO
9 threshold current Id1= 0.1-0.5 Ir 0.15
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 In 0.50
14 trip by Id> Id>= 0.5-40 In 7.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B08 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 150 / 1 B19 B5
2 56-TR-614A /B PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 B23 B5g
4 49 θ> Sn [kVA] = 2500 49 THERMAL IMn= 0.1 .. 5.0 In 108 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 105 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 9.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 128 0.85 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 315 2.10 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1425 9.5 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B09 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 150 / 1 B20 B6
2 6-TR-611 -612 -613A /B PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 B23 B6g
4 49 θ> Sn [kVA] = 2500 49 THERMAL IMn= 0.1 .. 5.0 In 108 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 105 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 9.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 128 0.85 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 315 2.10 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1425 9.5 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B10 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 300 / 1 B21 B7
2 6-TR-601A /B PLUS
2
3 Cable= 9x(1x400) mm N 1 RING C.T. ratio: 100 / 1 B23 B7g
4 49 θ> Sn [kVA] = 6300 49 THERMAL IMn= 0.1 .. 5.0 In 273 0.91 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 264 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 6.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 330 1.10 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 1920 6.40 0.75 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 5400 18.0 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 20.00 0.20 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B11 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 300 / 1 B22 B8
2 6-TR-602 PLUS
2
3 Cable= 2x 6x(1x400) mm N 1 RING C.T. ratio: 100 / 1 B23 B8g
4 49 θ> Sn [kVA] = 5200 49 THERMAL IMn= 0.1 .. 5.0 In 225 0.75 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 13.8 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 218 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 8.8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dd0Y11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 270 0.90 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 765 2.55 0.25 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 3000 10.0 0.05 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 20.00 0.20 0.10 SENSOR: 7 SPABUS CH.: 66
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B12 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 METERING BUSBAR 1-2-3 ABB REF 542 110:√3 110 Busbar V.T. ratio: 13800:√3 / 110:√3 13800 110 110
2 6-SW-600 PLUS
3
4 27 U< UNDERVOLTAGE BUSBAR "A" 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 0.04 motor shedding SENSOR: 1,2,3 SPABUS CH.: 65
5 59 U> OVERVOLTAGE BUSBAR "A" 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 5.00 alarm SENSOR: 1,2,3 SPABUS CH.: 62
6
7 BUSBAR 1-2-3 ABB REM 543 1 C.T. ratio: 3150 / 1
8 GEN. SETTINGS: Meas - Measuring mode Fundamental frequency
9 - Drop-off time of the operate time counter 0-1000 ms 100 ms
10 - FOR ALL THE RELAY FUNCTION NOT DESCRIBED INTO THE SETTING TABLE SHALL BE SET 'NOT IN USE' FOR THE OPERATION MODE
11 87 Id> HIGH IMPEDANCE DIFFERENTIAL INSTANT. Id>= 0.5-50 %In t= 0.03 .. 0.50 s 1575 50% 0.03 Diff3 3ΔI>
12 CT's Vk > 660 V
13 Stab. Res. = 544 Ohm - Vs = 272 V
14
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B13 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 INCOMERS FROM: 1-2-3 ABB REF 542 1 C.T. ratio: 3150 / 1 (*) B1
2 6-TR-600A PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110 110
3 N B23 B1g
4 1 Star Point C.T. ratio: 400 / 1 B23 B1gg
5 49 θ> Sn [kVA] = 65000 49 THERMAL IMn= 0.1 .. 5.0 In 2678 0.85 SENSOR: 1,2,3 SPABUS CH.: 74
6 Un [kV] = 14.4 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
7 In [A] = 2606 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
9 T Warn= 50 .. 400 °C 116 ° 116
10 T env= 10 .. 50 °C 50 ° 50.0
11 T rst= 10 .. 400 °C 90 ° 90
12 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT VERY INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2898 0.92 1.00 SENSOR: 1,2,3 SPABUS CH.: 57
13 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 9450 3.00 0.60 SENSOR: 1,2,3 SPABUS CH.: 52
14 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 9450 3.00 0.60 SENSOR: 1,2,3 SPABUS CH.: 51
15 51N Io> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 189 0.06 2.00 SENSOR: 1,2,3 SPABUS CH.: 67
16 51G Io> GROUND FAULT OVERCURRENT DEF. TIME 50GHIGH DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 40 0.10 2.50 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 5.00 Trip SENSOR: 4,5,6 SPABUS CH.: 65
18 59 U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 30.00 Trip SENSOR: 4,5,6 SPABUS CH.: 62
19 67 I> --> DIRECTIONAL PHASE OVERCURRENT 67HIGH DEF. TIME I>>= 0.05-40 In t>>= 0.08-300 s 315.0 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 54
20 REV. DIRECT.
21 67N Io>-> DIRECTIONAL GROUND FAULT OVERCURRENT67NHIGH DEF. TIME IE>>= 0.05-40 In t= 0.04-30 s 315.00 0.10 0.10 SENSOR: I7-U4,5,6 SPABUS CH.: 72
22 Uo= 0.02-0.7 Un 0.10 DIRECTION LINE
23 NETTYPE: GROUNDED (COS PHI)
24 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B14 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 INCOMERS FROM: 1-2-3 ABB REF 542 1 34.5 kV C.T. ratio 1250 / 1
3 6-TR-600A PLUS 1 13.8 kV C.T. ratio 3150 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 11 SPABUS CH.: 79
6 I1n [A] = 1088 In1= 10-100000 A 1088 1088 SENSOR: 1,2,3
7 I2n [A] = 2606 In2= 10-100000 A 2606 2606 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO YES
9 threshold current Id1= 0.1-0.5 Ir 0.30
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 0.50
14 trip by Id> Id>= 0.5-40 In 9.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17 87N Iod RESTRICTED EARTH FAULT DIFFERENTIAL 87N INSTANT. SPABUS CH.: 95
18 In [A] = 2606 Ir= 1-100000 A 2606 2606 SENSOR: 4,5,6
19 threshold current Id= 0.1-0.5 Ir 261 0.10 SENSOR: 7
20 unbiased region limit Ib1= 0.01-1 Ir 1303 0.50
21 slighly biased region slope slope= 0.01-2 0.70
22 slighly biased region limit Ib2= 0.01-2 Ir 3258 1.25
23 heavily biased slope slope= 0.1-1 In 1.00
24 Relay operate angle ROA= 60-180° 75
25 Time t= 0.040 … 100 s 0.05
26
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B15 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
1 INCOMERS FROM: 1-2-3 SIEM 7SD6001 1 LINE CT --> 1250 / 1 Cod. 7816= Existing
2 6-TR-600A -…-2DA0 FREQUENCY --> 60 [Hz] Cod. 1101= 60
3 Cod. 1102= 1250 Cod. 1103=1250
4 Pilo wire resist.=0-2000 Ohm Min Trip Comm.=0.01-60 s 0.00 0.20 Cod. 1131= 0.00 Cod.1134= 0.20
5 87L Id> LINE DIFFERENTIAL: INSTANT Id>= 0.5-2.5 In tId>=0-60 s 1.00 0.00 Cod 1501=ON Cod.1503= 1.00 Cod.1525= 0.00
6 Imin 0-1.5 In 0.00 Cod.1523= 0.00
7 Intertrip= ON-OFF Send Prol.trip = 0-5 s ON 0.10 Cod.1541= ON Cod.1542= 0.10
8 Id for spill 0.1-1 In time for spill=5-60 s 0.4 5 Cod.1550= 0.40 Cod.1551= 5
9 Pilot Wire Monitoring Station Identification slave Cod 1601=ON Cod.1602= slave
10 Block diff during failure time for blocking=0.2-60 s on 5.0 Cod.1603= on Cod.1604= 5.0
11 Emergency Overcurrent I>= 0.1-15 In tI>=0-60 s 2.0 0.10 Cod 1701=OFF Cod.1702= 2.0 Cod.1703= 0.10
12 Direct Remote Trip Send Prol.transfer = 0-60 s 0.00 Cod.2203= 0.00
13 Trip Receiver Receive signal.transfer = 0-60 s 0.03 Cod 2301=ON Cod.2303= 0.03
14 Receive Prol.transfer = 0-60 s 0.20 Cod.2303= 0.20
15
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-600
VOLTAGE: 13.8 kV
PAGE: B16 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 INCOMING FROM 1-2-3 ABB REF 542 1 C.T. ratio: 3150 / 1 (*) B2
2 5-SW-600A PLUS 110:√3 110 V.T. ratio: 13800:√3 / 110:√3 13800 110 110
3 N 1 RING C.T. ratio: 3150 / 1 B23 B2g
4 49 θ> Sn [kVA] = 65000 49 THERMAL IMn= 0.1 .. 5.0 In 2615 0.83 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 14.4 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 In [A] = 2606 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1200
7 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1200
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT VERY INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2678 0.85 0.50 SENSOR: 1,2,3 SPABUS CH.: 57
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 7875 2.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 7875 2.5 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
14 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 9660 0.70 2.00 SENSOR: 4,5,6 SPABUS CH.: 65
15 59 U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 16560 1.20 2.00 SENSOR: 4,5,6 SPABUS CH.: 62
16 67 I> --> DIRECTIONAL PHASE OVERCURRENT 67HIGH DEF. TIME I>>= 0.05-40 In t>>= 0.08-300 s 315.0 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 54
17 REV. DIRECT.
18 67N Io>-> DIRECTIONAL GROUND FAULT OVERCURRENT67NHIGH DEF. TIME IE>>= 0.05-40 In t= 0.04-30 s 315.00 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 72
19 Uo= 0.02-0.7 Un 0.10 DIRECTION LINE
20 NETTYPE: GROUNDED (COS PHI)
21 25 ΔU/Δf SYNCHRO-CHECK 25 DEF. TIME ΔU= 0.02-0.4 Un tΔ= 0.2-1000 s 2070 0.15 2.00 SENSOR: 4-5 / 8 SPABUS CH.: 85
22 Δϕ Δϕ= 5-50° 10° 00' 10.0
23 (*) ALL PHASE FAULT DRWG's
JOB.: 8606001370
DWG.: 1VCC006007T0601
PT S.p.A.

TASNEE - HDPE/LDPE PROJECT


SWITCHBOARDS
5-SW-600 – 6-SW600 – 5-SW601 – 6-SW-601 REV.: 2 DATA: 19/06/2007
RELAY COORDINATION STUDY

ATTACHMENT 'C'

SWITCHBOARD 4.16 kV
6-SW-601

ONE LINE DIAGRAM C01

TRANSFORMERS DATA C02

MOTORS DATA C03

RELAY SETTING TABLE C04-C16

SELECTIVITY CURVES C17-C26


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
TRANSFORMERS RATING DWG.: 1VCC006007T0601
VOLTAGE: 4.16 kV PAGE: C02
SWGR: 6-SW-601 REV.: 2 DATE: 19/06/2007

RATED RATED VOLTAGE RATED CURRENT Uk VECTOR IN-RUSH CURRENT NOTE


ITEM
POWER PRIMARY SECOND. PRIMARY SECOND. GROUP K (*) T (*)

[kVA] [V] [V] [A] [A] [%] [x In] [s]

6-TR-614 630 4160 415 87.4 876 6.00 Dyn11 11.00 0.30

(*) ESTEEMED VALUE

IN-RUSH CURRENT IS CALCULATED WITH THE FOLLOWING FORMULA: Iin-rush = In x K x exp(-t/T)/√2


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
MOTORS RATING DWG.: 1VCC006007T0601
VOLTAGE: 4.16 kV PAGE: C03
SWGR: 6-SW-601 REV.: 2 DATE: 19/06/2007

LOCKED- THERM.
NUMBER OF STARTING STARTING STARTING
RATED RATED RATED ILR/In ILR/In ROTOR CONST.
/HOUR TIME TIME
ITEM TIME (Un) TIME
at 100%
POWER VOLTAGE CURRENT COLD HOT at 100% Un at 100% Un at Umin at Umin
Un

[kW] [V] [A] [% di In] [s] [% di In] [s] [s] [min]

6KM-9005A /S 522 4160 89.0 3 2 510 4 (*) 408 8 (*)

6KM-9001A /B 420 4160 62.3 3 2 600 4.00 480 7.90

6ABM-5104A /B 200 4160 35.0 3 2 600 4 (*) 480 8 (*)

6KM-5101A /S 260 4160 43.8 3 2 600 6.10 480 13.30

6ABM-1901A /S 200 4160 33.0 3 2 600 4 (*) 480 8 (*)

6PM-1804A /S 200 4160 35.0 3 2 600 1.90 480 4.80 7.40

(*) ESTEEMED VALUE


JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C04 #### C
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 125 / 1 C17 C3
2 6KM-9005A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x70) mm G 1 RING C.T. ratio: 100 / 1 C26 C3g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 91.3 0.73 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 522 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 89.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 5.10 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.08 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 25 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 91 0.73 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 401 4.39 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 228 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 183 1.46 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 91 0.73 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 252 2.76 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 625 5.00 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.30 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65

25
26 FUS. 1-2-3 ABB CMF INVERSE 250 250 250 C17 C3f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C05 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 100 / 1 C18 C4
2 6KM-9001A /B PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C4g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 64.0 0.64 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 420 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 62.3 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 7.90 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 20 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 64 0.64 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 328 5.12 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 190 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 150 1.50 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 64 0.64 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 209 3.27 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 520 5.20 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 160 160 160 C18 C4f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C06 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 C19 C5
2 6ABM-5104A /B PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C5g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 36.0 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 200 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 35.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 36 0.72 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 185 5.14 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 105 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 84 1.68 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 36 0.72 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 116 3.23 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 290 5.80 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 C19 C5f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C07 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 C20 C6
2 6KM-5101A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C6g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 45.0 0.60 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 260 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 2400
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1200
7 In [A] = 43.8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1200
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 6.10 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 13.30 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 15 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 45 0.60 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 244 5.42 10.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 132 0.54
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 106 1.41 18.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 45 0.60 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 145 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 368 4.90 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 160 160 160 C20 C6f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C08 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 C21 C7
2 6ABM-1901A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C7g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 34.0 0.68 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 200 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 33.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 34 0.68 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 174 5.13 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 99 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 80 1.59 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 34 0.68 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 109 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 275 5.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 C21 C7f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C09 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 C22 C8
2 6PM-1804A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C8g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 36.0 0.72 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 200 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 960
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 480
7 In [A] = 35.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 480
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 1.90 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 4.80 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 36 0.72 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 181 5.04 7.5 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 105 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 84 1.68 7.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 36 0.72 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 116 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 290 5.80 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 C22 C8f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C10 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMER 1-2-3 ABB REF 542 1 C.T. ratio: 100 / 1 C23 C9
2 6-TR-614 PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 C26 C9g
4 49 θ> Sn [kVA] = 630 49 THERMAL IMn= 0.1 .. 5.0 In 90 0.90 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 4.16 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 87.4 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 6.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 105 1.05 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 265 2.65 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1750 17.5 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15

16 FUS. 1-2-3 ABB CEF INVERSE 160 160 160 C23 C9f

17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C11 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CAPACITORS: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 C24 C10
2 6PF-601A /C PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C10g
4 49 θ> CAPACITOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 43.5 0.58 SENSOR: 1,2,3 SPABUS CH.: 74
5 Sn [kVAR] = 300 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 In [A] = 42.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 6.0 0.08 3.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 Reset time= 0 .. 2000 s 1.00
13 Timer decr= 0 .. 100% 0%
14 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 126 1.68 0.5 SENSOR: 1,2,3 SPABUS CH.: 53
15 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 420 5.60 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
16 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.50 SENSOR: 4,5,6 SPABUS CH.: 65
18 59A U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 1.50 SENSOR: 4,5,6 SPABUS CH.: 62
19
20 FUS. 1-2-3 ABB CEF INVERSE 160 160 160 C24 C10f

21
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C12 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CAPACITORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 C25 C11
2 6PF-601B /D PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 C26 C11g
4 49 θ> CAPACITOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 22.0 0.44 SENSOR: 1,2,3 SPABUS CH.: 74
5 Sn [kVAR] = 150 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 In [A] = 21.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 3.0 0.06 3.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 Reset time= 0 .. 2000 s 1.00
13 Timer decr= 0 .. 100% 0%
14 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 63 1.26 0.5 SENSOR: 1,2,3 SPABUS CH.: 53
15 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 210 4.20 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
16 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.50 SENSOR: 4,5,6 SPABUS CH.: 65
18 59A U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 1.50 SENSOR: 4,5,6 SPABUS CH.: 62
19
20 FUS. 1-2-3 ABB CEF INVERSE 63 63 63 C25 C11f

21
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C13 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 METERING BUSBARS 1-2-3 ABB REF 542 110:√3 110 Busbar A V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2 6-SW-601 PLUS 110:√3 110 Busbar B V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3
4 27A U< UNDERVOLTAGE BUSBAR "A" 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.04 motor shedding SENSOR: 1,2,3 SPABUS CH.: 65
5 59A U> OVERVOLTAGE BUSBAR "A" 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 5.00 alarm SENSOR: 1,2,3 SPABUS CH.: 62
6 27B U< UNDERVOLTAGE BUSBAR "B" 27HIGH DEF. TIME U<<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.04 motor shedding SENSOR: 4,5,6 SPABUS CH.: 64
7 59B U> OVERVOLTAGE BUSBAR "B" 59HIGH DEF. TIME U>>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 5.00 alarm SENSOR: 4,5,6 SPABUS CH.: 61
8
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C14 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 BUS TIE 1-2-3 ABB REF 542 1 C.T. ratio: 1250 / 1 (*) C2
2 In [A] = 836 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3 N C26 C2g
4 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 875 0.70 0.50 SENSOR: 1,2,3 SPABUS CH.: 58
5 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 5000 4.00 0.25 SENSOR: 1,2,3 SPABUS CH.: 52
6 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 5000 4.00 0.25 SENSOR: 1,2,3 SPABUS CH.: 51
7 51N Io>> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 125.0 0.10 0.80 SENSOR: 1,2,3 SPABUS CH.: 67
8 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C15 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 INCOMERS FROM: 1-2-3 ABB REF 542 1 C.T. ratio: 1250 / 1 (*) C1
2 6-TR-601A /B PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3 N C26 C1g
4 1 Star Point C.T. ratio: 400 / 1 C26 C1gg
5 49 θ> Sn [kVA] = 6300 49 THERMAL IMn= 0.1 .. 5.0 In 863 0.69 SENSOR: 1,2,3 SPABUS CH.: 74
6 Un [kV] = 4.35 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
7 In [A] = 836 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
9 T Warn= 50 .. 400 °C 116 ° 116
10 T env= 10 .. 50 °C 50 ° 50.0
11 T rst= 10 .. 400 °C 90 ° 90
12 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 925 0.74 1.00 SENSOR: 1,2,3 SPABUS CH.: 58
13 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 5500 4.40 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
14 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 5500 4.40 0.50 SENSOR: 1,2,3 SPABUS CH.: 51
15 51N Io> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 125 0.10 1.10 SENSOR: 1,2,3 SPABUS CH.: 67
16 51G Io> GROUND FAULT OVERCURRENT DEF. TIME 50GHIGH DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 40 0.10 1.50 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 5.00 Trip SENSOR: 4,5,6 SPABUS CH.: 65
18 59 U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 30.00 Trip SENSOR: 4,5,6 SPABUS CH.: 62
19 67 I> --> DIRECTIONAL PHASE OVERCURRENT 67HIGH DEF. TIME I>>= 0.05-40 In t>>= 0.08-300 s 125.0 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 54
20 REV. DIRECT.
21 67N Io>-> DIRECTIONAL GROUND FAULT OVERCURRENT67NHIGH DEF. TIME IE>>= 0.05-40 In t= 0.04-30 s 125.00 0.10 0.10 SENSOR: I7-U4,5,6 SPABUS CH.: 72
22 Uo= 0.02-0.7 Un 0.10 DIRECTION LINE
23 NETTYPE: GROUNDED (COS PHI)
24 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 6-SW-601
VOLTAGE: 4.16 kV
PAGE: C16 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 INCOMERS FROM: 1-2-3 ABB REF 542 1 13.8 kV C.T. ratio 350 / 1
3 6-TR-601A /B PLUS 1 4.16 kV C.T. ratio 1250 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 11 SPABUS CH.: 79
6 I1n [A] = 264 In1= 10-100000 A 264 264 SENSOR: 1,2,3
7 I2n [A] = 836 In2= 10-100000 A 836 836 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO YES
9 threshold current Id1= 0.1-0.5 Ir 0.30
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 0.50
14 trip by Id> Id>= 0.5-40 In 9.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17 87N Iod RESTRICTED EARTH FAULT DIFFERENTIAL 87N INSTANT. SPABUS CH.: 95
18 In [A] = 836 Ir= 1-100000 A 836 836 SENSOR: 4,5,6
19 threshold current Id= 0.1-0.5 Ir 167 0.20 SENSOR: 7
20 unbiased region limit Ib1= 0.01-1 Ir 418 0.50
21 slighly biased region slope slope= 0.01-2 0.70
22 slighly biased region limit Ib2= 0.01-2 Ir 1045 1.25
23 heavily biased slope slope= 0.1-1 In 1.00
24 Relay operate angle ROA= 60-180° 75
25 Time t= 0.040 … 100 s 0.05
26
JOB.: 8606001370
DWG.: 1VCC006007T0601
PT S.p.A.

TASNEE - HDPE/LDPE PROJECT


SWITCHBOARDS
5-SW-600 – 6-SW600 – 5-SW601 – 6-SW-601 REV.: 2 DATA: 19/06/2007
RELAY COORDINATION STUDY

ATTACHMENT 'D'

SWITCHBOARD 4.16 kV
5-SW-601

ONE LINE DIAGRAM D01

TRANSFORMERS DATA D02

MOTORS DATA D03

RELAY SETTING TABLE D04-D24

SELECTIVITY CURVES D25-D42


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
TRANSFORMERS RATING DWG.: 1VCC006007T0601
VOLTAGE: 4.16 kV PAGE: D02
SWGR: 5-SW-601 REV.: 2 DATE: 19/06/2007

RATED RATED VOLTAGE RATED CURRENT Uk VECTOR IN-RUSH CURRENT NOTE


ITEM
POWER PRIMARY SECOND. PRIMARY SECOND. GROUP K (*) T (*)

[kVA] [V] [V] [A] [A] [%] [x In] [s]

5-TR-617A /B /C 630 4160 415 87.4 876 6.00 Dyn11 11.00 0.30

5-TR-615 435 4160 401 60.4 626 3.00 Dyn11 12.00 0.25

5-TR-616 435 4160 401 60.4 626 3.00 Dyn11 12.00 0.25

(*) ESTEEMED VALUE

IN-RUSH CURRENT IS CALCULATED WITH THE FOLLOWING FORMULA: Iin-rush = In x K x exp(-t/T)/√2


TASNEE HDPE/LDPE PROJECT
PT S.p.A.
JOB: 8606001370
MOTORS RATING DWG.: 1VCC006007T0601
VOLTAGE: 4.16 kV PAGE: D03
SWGR: 5-SW-601 REV.: 2 DATE: 19/06/2007

LOCKED- THERM.
NUMBER OF STARTING STARTING STARTING
RATED RATED RATED ILR/In ILR/In ROTOR CONST.
/HOUR TIME TIME
ITEM TIME (Un) TIME
at 100%
POWER VOLTAGE CURRENT COLD HOT at 100% Un at 100% Un at Umin at Umin
Un

[kW] [V] [A] [% di In] [s] [% di In] [s] [s] [min]

5PM-6101A /S 185 4160 32.0 3 2 580 2.70 464 6.30 20.60

5PM-6102A /S 185 4160 32.0 3 2 580 2.70 464 6.30 20.60

5-KM-3501 160 4160 29.2 3 2 510 4 (*) 408 8 (*)

5-KM-5401B /C /S 460 4160 75.0 3 2 600 3.60 480 6.7

5-KM-5401A 220 4160 40.0 3 2 600 1.00 480 1.20

5-KM-5401D 300 4160 49.7 3 2 600 3.50 480 6.70

5-KM-2402A /S 400 4160 65.0 3 2 600 3.80 480 7.60

5-KM-3201 410 4160 73.0 3 2 600 4.00 480 8.05 38

5-KM-2310 265 4160 45.0 3 2 600 4 (*) 480 8 (*)

5-KM-2203A /S 220 4160 36.0 3 2 600 9.00 480 22.4

5-PM-2101A /S 315 4160 51.0 3 2 600 6.00 480 14.20 6.5

5-PM-1301A /S 230 4160 39.0 3 2 600 3.10 480 6.8 24.0 6.0

5-PM-1203A /B 655 4160 108.1 3 2 600 3.30 480 7.4 22.0 6.0

5-PM-1201A /B /C 655 4160 108.1 3 2 600 3.30 480 7.4 22.0 6.0

5-PM-1202A /B 655 4160 108.1 3 2 600 3.30 480 7.4 22.0 6.0

5-MXM-1201 400 4160 69.0 3 2 600 1.30 480 3.5 16.0

5-MXM-1202 400 4160 69.0 3 2 600 1.30 480 3.5 16.0

5-MXM-1203 400 4160 69.0 3 2 600 1.30 480 3.5 16.0

(*) ESTEEMED VALUE


JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D04 #### D
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 D25 D3
2 5PM-6101A /S 5PM-6102A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D3g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 33.0 0.66 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 185 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 32.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 5.80 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 2.70 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.64 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 6.30 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 33 0.66 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 163 4.95 9.5 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 93 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 75 1.49 9.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 33 0.66 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 103 3.11 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 255 5.10 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65

25
26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D25 D3f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D05 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTOR: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 D26 D4
2 5KM-3501 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D4g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 30.0 0.60 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 160 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 29.2 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 5.10 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.08 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 30 0.60 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 131 4.38 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 75 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 60 1.20 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 30 0.60 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 83 2.75 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 205 4.10 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D26 D4f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D06 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 100 / 1 D27 D5
2 5KM-5401B /C /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D5g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 77.0 0.77 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 460 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 75.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.60 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 6.70 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 20 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 77 0.77 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 388 5.04 8.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 225 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 180 1.80 10.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 77 0.77 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 248 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 630 6.30 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 200 200 200 D27 D5f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D07 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTOR: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 D28 D6
2 5KM-5401A PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D6g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 41.0 0.82 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 220 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 600
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 300
7 In [A] = 40.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 300
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 1.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 1.20 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 41 0.82 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 187 4.56 3.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 122 0.65
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 96 1.92 3.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 41 0.82 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 134 3.27 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 335 6.70 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D28 D6f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D08 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTOR: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 D29 D7
2 5KM-5401D PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D7g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 51.0 0.68 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 300 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1320
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 660
7 In [A] = 49.7 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 660
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.50 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 6.80 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 15 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 51 0.68 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 259 5.08 8.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 150 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 120 1.60 10.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 51 0.68 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 166 3.25 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 413 5.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 160 160 160 D29 D7f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D09 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 100 / 1 D30 D8
2 5KM-2402A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D8g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 67.0 0.67 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 400 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 65.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.80 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 7.60 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 20 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 67 0.67 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 342 5.11 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 195 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 156 1.56 11.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 67 0.67 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 215 3.21 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 540 5.40 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 200 200 200 D30 D8f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D10 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTOR: 1-2-3 ABB REF 542 1 C.T. ratio 100 / 1 D31 D9
2 5KM-3201 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x70) mm G 1 RING C.T. ratio: 100 / 1 D42 D9g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 75.0 0.75 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 410 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 73.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.05 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 20 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 75 0.75 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 380 5.06 12.5 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 220 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 176 1.76 12.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 75 0.75 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 242 3.23 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 610 6.10 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 200 200 200 D31 D9f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D11 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTOR: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 D32 D10
2 5KM-2310 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D10g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 46.5 0.62 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 265 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 45.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 4.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 8.00 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 15 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 47 0.62 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 238 5.12 9.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 136 0.57
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 108 1.44 12.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 47 0.62 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 150 3.22 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 375 5.00 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 160 160 160 D32 D10f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D12 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 D33 D11
2 5KM-2203A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D11g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 37.0 0.74 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 220 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 3600
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 In [A] = 36.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 9.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 22.40 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 37 0.74 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 202 5.45 17.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 109 0.54
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 87 1.73 30.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 37 0.74 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 120 3.24 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 300 6.00 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D33 D11f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D13 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 D34 D12
2 5PM-2101A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D12g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 52.5 0.70 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 315 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 2400
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1200
7 In [A] = 51.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1200
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 6.00 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 14.20 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 15 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 53 0.70 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 286 5.44 11.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 154 0.54
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 123 1.64 19.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 53 0.70 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 170 3.24 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 428 5.70 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D34 D12f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D14 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 50 / 1 D35 D13
2 5PM-1301A /S PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D13g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 40.0 0.80 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 230 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1200
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 600
7 In [A] = 39.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 600
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.10 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 6.80 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 10 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 40 0.80 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 203 5.08 8.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 118 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 94 1.88 10.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 40 0.80 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 130 3.25 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 325 6.50 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 100 100 100 D35 D13f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D15 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 5PM-1201A /B /C 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1 D36 D14
2 5PM-1202A /B 5PM-1203A /B PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x70) mm G 1 RING C.T. ratio: 100 / 1 D42 D14g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 111.0 0.74 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 655 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1440
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 720
7 In [A] = 108.1 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 720
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 3.30 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 7.40 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 30 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 111 0.74 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 562 5.06 11.5 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 326 0.58
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 260 1.73 11.5 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 111 0.74 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 359 3.23 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 900 6.00 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.30 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 250 250 250 D36 D14f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D16 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 MOTORS: 1-2-3 ABB REF 542 1 C.T. ratio 100 / 1 D37 D15
2 5MXM-1201 -1202 -1203 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D15g
4 49 θ> MOTOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 71.0 0.71 SENSOR: 1,2,3 SPABUS CH.: 74
5 Pn [kW] = 400 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 720
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 360
7 In [A] = 69.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 360
8 I str. [x In] a 100% Un = 6.00 T Warn= 50 .. 400 °C 116 ° 116
9 t str. [s] a 100% Un = 1.30 T env= 10 .. 50 °C 50 ° 50.0
10 I str. [x In] a Umin = 4.80 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 t str. [s] a Umin = 3.50 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 20 0.20 20.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 nr. str. from cold = 3 Reset time= 0 .. 2000 s 1.00
13 nr. str. from hot = 2 Timer decr= 0 .. 100% 0%
14 48 I> within hours = 1 51MS INVERSE IMn= 0.200 .. 2.000 In 71 0.71 SENSOR: 1,2,3 SPABUS CH.: 80
15 Is= 1.000 .. 20.000 IMn time= 0.040 .. 300 s 316 4.45 7.0 BLOCK 51LR (CH. 86)+TRIP
16 IMs= 0.200 .. 0.800 Is 209 0.66
17 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 166 1.66 7.0 SENSOR: 1,2,3 SPABUS CH.: 53
18 51LR I> t> 51LR DEF. TIME IMn= 0.200 .. 2.000 In 71 0.71 SENSOR: 1,2,3 SPABUS CH.: 86
19 Is= 1.000..20.000 IMn t= 0.040 .. 30 s 230 3.24 2.00
20 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 570 5.70 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
21 66 n> 66 DEF. TIME Nws (Warm)= 1 .. 10 Tws= 20 .. 200 °C 2.00 80.0 SPABUS CH.: 87
22 Ncs (Cold)= 1 .. 10 t rst=1.00 .. 7200.00 s 3.00 1200
23 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
24 27M U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.20 SENSOR: 4,5,6 SPABUS CH.: 65
25

26 FUS. 1-2-3 ABB CMF INVERSE 200 200 200 D37 D15f

27
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D17 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 100 / 1 D38 D16
2 5-TR-617A /B /C PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 D42 D16g
4 49 θ> Sn [kVA] = 630 49 THERMAL IMn= 0.1 .. 5.0 In 90 0.90 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 4.16 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 87.4 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 6.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 105 1.05 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 265 2.65 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1750 17.5 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15

16 FUS. 1-2-3 ABB CEF INVERSE 160 160 160 D38 D16f

17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D18 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 FEEDERS TO TRANSFORMERS 1-2-3 ABB REF 542 1 C.T. ratio: 100 / 1 D39 D17
2 5-TR-615 5-TR-616 PLUS
2
3 Cable= 1x(3x150) mm N 1 RING C.T. ratio: 100 / 1 D42 D17g
4 49 θ> Sn [kVA] = 435 49 THERMAL IMn= 0.1 .. 5.0 In 62 0.62 SENSOR: 1,2,3 SPABUS CH.: 74
5 Un [kV] = 4.16 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 In [A] = 60.4 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 Vcc [%] = 3.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 Vector Group = Dy11 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 75 0.75 1.50 SENSOR: 1,2,3 SPABUS CH.: 58
12 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 185 1.85 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
13 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 2450 24.5 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
14 64 Io>> GROUND FAULT OVERCURRENT 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
15

16 FUS. 1-2-3 ABB CEF INVERSE 100 100 100 D39 D17f

17
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D19 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CAPACITORS: 1-2-3 ABB REF 542 1 C.T. ratio 150 / 1 D40 D18
2 5PF-601A /C PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2
3 Cable= 1x(3x150) mm G 1 RING C.T. ratio: 100 / 1 D42 D18g
4 49 θ> CAPACITOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 123.0 0.82 SENSOR: 1,2,3 SPABUS CH.: 74
5 Sn [kVAR] = 800 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 In [A] = 120.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 18.0 0.12 3.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 Reset time= 0 .. 2000 s 1.00
13 Timer decr= 0 .. 100% 0%
14 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 360 2.40 0.5 SENSOR: 1,2,3 SPABUS CH.: 53
15 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 1200 8.00 0.50 SENSOR: 1,2,3 SPABUS CH.: 51
16 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.50 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.50 SENSOR: 4,5,6 SPABUS CH.: 65
18 59A U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 1.50 SENSOR: 4,5,6 SPABUS CH.: 62
19
20 FUS. 1-2-3 ABB CMF INVERSE 315 315 315 D40 D18f

21
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D20 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CAPACITORS: 1-2-3 ABB REF 542 1 C.T. ratio 75 / 1 D41 D19
2 5PF-601B /D PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2
3 Cable= 1x(3x35) mm G 1 RING C.T. ratio: 100 / 1 D42 D19g
4 49 θ> CAPACITOR PROTECTION 49 THERMAL IMn= 0.1 .. 5.0 In 61.5 0.82 SENSOR: 1,2,3 SPABUS CH.: 74
5 Sn [kVAR] = 400 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
6 Un [kV] = 4.16 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
7 In [A] = 60.0 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
8 T Warn= 50 .. 400 °C 116 ° 116
9 T env= 10 .. 50 °C 50 ° 50.0
10 T rst= 10 .. 400 °C 90 ° 90
11 46 m<3 46 INVERSE Is= 0.05 .. 0.30 In K= 2.0 … 30.0 9.0 0.12 3.0 SENSOR: 1,2,3 SPABUS CH.: 75
12 Reset time= 0 .. 2000 s 1.00
13 Timer decr= 0 .. 100% 0%
14 51 I> t> 50tLOW DEF. TIME I>= 0.05..40.00 In t= 0.020 .. 300 s 180 2.40 0.5 SENSOR: 1,2,3 SPABUS CH.: 53
15 50 I>> 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 600 8.00 0.30 SENSOR: 1,2,3 SPABUS CH.: 51
16 64 Io> 50GHIGH DEF. TIME IEF>>= 0.05 .. 40.00 Ion t= 0.040 .. 30 s 10.00 0.10 0.10 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.50 SENSOR: 4,5,6 SPABUS CH.: 65
18 59A U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 1.50 SENSOR: 4,5,6 SPABUS CH.: 62
19
20 FUS. 1-2-3 ABB CEF INVERSE 200 200 200 D41 D19f

21
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D21 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 METERING BUSBARS 1-2-3 ABB REF 542 110:√3 110 Busbar A V.T. ratio: 4160:√3 / 110:√3 4160 110 110
2 5-SW-601 PLUS 110:√3 110 Busbar B V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3
4 27A U< UNDERVOLTAGE BUSBAR "A" 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.04 motor shedding SENSOR: 1,2,3 SPABUS CH.: 65
5 59A U> OVERVOLTAGE BUSBAR "A" 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 5.00 alarm SENSOR: 1,2,3 SPABUS CH.: 62
6 27B U< UNDERVOLTAGE BUSBAR "B" 27HIGH DEF. TIME U<<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 0.05 motor shedding SENSOR: 4,5,6 SPABUS CH.: 64
7 59B U> OVERVOLTAGE BUSBAR "B" 59HIGH DEF. TIME U>>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 5.00 alarm SENSOR: 4,5,6 SPABUS CH.: 61
8
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D22 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 BUS TIE 1-2-3 ABB REF 542 1 C.T. ratio: 2500 / 1 (*) D2
2 In [A] = 1991 PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3 N D42 D2g
4 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2000 0.80 0.50 SENSOR: 1,2,3 SPABUS CH.: 58
5 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 6250 2.50 0.25 SENSOR: 1,2,3 SPABUS CH.: 52
6 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 6250 2.50 0.25 SENSOR: 1,2,3 SPABUS CH.: 51
7 51N Io>> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 250.0 0.10 0.80 SENSOR: 1,2,3 SPABUS CH.: 67
8 25 ΔU/Δf SYNCHRO-CHECK 25 DEF. TIME ΔU= 0.02-0.4 Un tΔ= 0.2-1000 s 624 0.15 2.00 SENSOR: 4-5 / 8 SPABUS CH.: 85
9 Δϕ Δϕ= 5-50° 10° 00' 10.0
10 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D23 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 INCOMERS FROM: 1-2-3 ABB REF 542 1 C.T. ratio: 2500 / 1 (*) D1
2 5-TR-601A /B PLUS 110:√3 110 V.T. ratio: 4160:√3 / 110:√3 4160 110 110
3 N D42 D1g
4 1 Star Point C.T. ratio: 400 / 1 D42 D1gg
5 49 θ> Sn [kVA] = 15000 49 THERMAL IMn= 0.1 .. 5.0 In 2050 0.82 SENSOR: 1,2,3 SPABUS CH.: 74
6 Un [kV] = 4.35 TMn= 50 .. 400 °C τ OFF= 10 .. 100000 s (I<0.1 IMn) 110 ° 110 1800
7 In [A] = 1991 Tini= 10 .. 400 °C τ NORMAL= 10 .. 20000 s 90 ° 90 1800
8 T Trip= 50 .. 400 °C τ OVERHEAT= 10 .. 20000 s 121 ° 121 1800
9 T Warn= 50 .. 400 °C 116 ° 116
10 T env= 10 .. 50 °C 50 ° 50.0
11 T rst= 10 .. 400 °C 90 ° 90
12 51 I> PHASE OVERCURRENT INVERSE TIME 51IDMT EXTR. INV. Ieb= 0.05 .. 40 In k= 0.05 .. 1.50 2200 0.88 1.00 SENSOR: 1,2,3 SPABUS CH.: 58
13 50t I>> PHASE OVERCURRENT DEFINITE TIME 50tHIGH DEF. TIME I>>= 0.05 .. 40.00 In t= 0.02 .. 300 s 7000 2.80 0.50 SENSOR: 1,2,3 SPABUS CH.: 52
14 50 I>> SHORT CIRCUIT OVERCURRENT 50IST DEF. TIME I>>>= 0.1 .. 40.00 In t= 0.015 .. 30 s 7000 2.80 0.50 SENSOR: 1,2,3 SPABUS CH.: 51
15 51N Io> GROUND FAULT OVERCURRENT DEF. TIME 50GLOW DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 250 0.10 1.10 SENSOR: 1,2,3 SPABUS CH.: 67
16 51G Io> GROUND FAULT OVERCURRENT DEF. TIME 50GHIGH DEF. TIME Io>>= 0.05-40 Ion to>>= 0.04..30 s 40 0.10 1.50 SENSOR: 7 SPABUS CH.: 66
17 27 U< UNDERVOLTAGE 27LOW DEF. TIME U<= 0.1 … 1.2 Un t= 0.040 … 30 s 2912 0.70 5.00 Trip SENSOR: 4,5,6 SPABUS CH.: 65
18 59 U> OVERVOLTAGE 59LOW DEF. TIME U>= 0.1 … 3.0 Un t= 0.040 … 30 s 4992 1.20 30.00 Trip SENSOR: 4,5,6 SPABUS CH.: 62
19 67 I> --> DIRECTIONAL PHASE OVERCURRENT 67HIGH DEF. TIME I>>= 0.05-40 In t>>= 0.08-300 s 250.0 0.10 0.10 SENSOR: I1,3-U4,6 SPABUS CH.: 54
20 REV. DIRECT.
21 67N Io>-> DIRECTIONAL GROUND FAULT OVERCURRENT67NHIGH DEF. TIME IE>>= 0.05-40 In t= 0.04-30 s 250.00 0.10 0.10 SENSOR: I7-U4,5,6 SPABUS CH.: 72
22 Uo= 0.02-0.7 Un 0.10 DIRECTION LINE
23 NETTYPE: GROUNDED (COS PHI)
24 (*) ALL PHASE FAULT DRWG's
JOB: 8606001370
TASNEE HDPE/LDPE PROJECT DWG: 1VCC00600T0601
RELAY SETTING TABLE REV.: 2 DATE 19/06/2007
PT S.p.A.
SWITCHBOARD: 5-SW-601
VOLTAGE: 4.16 kV
PAGE: D24 ####
RELAY OR FUNCTION RELAY CHARACTERISTICS C.T. SETTINGS CURVES
In SETTING and/or NOTES
PS ANSI IEC USER PH MNFR MODEL OPERATING and/or RANGE V.T. PRIMARY I/U TIME PAGE CODE
CODE CODE L.. CHARACT. Un I/U [A/V] TIME RATIO VALUE [pu/A/V] [s/..]
1 CONTINUATION FOR:
2 INCOMERS FROM: 1-2-3 ABB REF 542 1 13.8 kV C.T. ratio 750 / 1
3 5-TR-601A /B PLUS 1 4.16 kV C.T. ratio 2500 / 1
4 G
5 87 Id DIFFERENTIAL 87 INSTANT. group= 0-11 11 SPABUS CH.: 79
6 I1n [A] = 628 In1= 10-100000 A 628 628 SENSOR: 1,2,3
7 I2n [A] = 1991 In2= 10-100000 A 1991 1991 SENSOR: 4,5,6
8 transformer earthing Prim. Earth= YES/NO Sec. Earth= YES/NO NO YES
9 threshold current Id1= 0.1-0.5 Ir 0.30
10 unbiased region limit Ib1= 0.5-5 Ir 0.50
11 slighly biased region threshold Id2= 0.2-2 Ir 1.00
12 slighly biased region limit Ib2= 1-10 Ir 2.00
13 heavily biased slope slope= 0.4-1 0.50
14 trip by Id> Id>= 0.5-40 In 9.00
15 Second Harmonics 2HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
16 Fifth Harmonics 5HarThre 0.1-0.3 Id Enable= YES/NO 0.10 YES
17 87N Iod RESTRICTED EARTH FAULT DIFFERENTIAL 87N INSTANT. SPABUS CH.: 95
18 In [A] = 1991 Ir= 1-100000 A 1991 1991 SENSOR: 4,5,6
19 threshold current Id= 0.1-0.5 Ir 199 0.10 SENSOR: 7
20 unbiased region limit Ib1= 0.01-1 Ir 996 0.50
21 slighly biased region slope slope= 0.01-2 0.70
22 slighly biased region limit Ib2= 0.01-2 Ir 2489 1.25
23 heavily biased slope slope= 0.1-1 In 1.00
24 Relay operate angle ROA= 60-180° 75
25 Time t= 0.040 … 100 s 0.05
26