Sunteți pe pagina 1din 4

ENGLISH Quick Start Guide - ATV312

S1A1094203
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product
documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive
system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable
regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically
insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to
prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that
can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.

Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV312 installation manual (BBV46391) and programming manual (BBV46385) on www.schneider-electric.com.

1 Check the delivery of the drive


• Remove ATV312 from the packaging and check that it has not been damaged.

WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.

Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

2 Check the line voltage compatibility


• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts / Drive voltage range _______ Volts
8B0917121134
Drive range: ATV312ppppM2 = 200/240 V single phase / ATV312ppppM3=200/240 V three-phase
ATV312ppppN4 = 380/500 V three-phase / ATV312ppppS6 = 525/600 V three-phase

3 Mount the drive vertically


For a surrounding air temperature up to 50 °C (122 °F)
(a)

(a) (a)

(b)
(a)

(a) 50 mm (2 in.)
(b) 10 mm (0.4 in.)
See installation manual (BBV46391) on www.schneider-electric.com for other thermal conditions.

www.schneider-electric.com 1/4 S1A10942 - 04/2014


4 Connect power wiring 5 Connect control wiring and
• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating (see SCCR annex) select control configuration:
• Check that the motor voltage is compatible with the drive voltage.
Motor voltage ______Volts. 5.1 or 5.2
• Wire the drive to the motor.
• Wire the drive to the line supply. [REMOTE configuration]
5.1 (Control by external reference)
Source
• Ensure SW1 = ‘’SOURCE’’ CLI
SINK

• Wire the speed reference:


RUN
REF

200/240 V MON
CONF
CAN
ERR

+10 v
ATV312 M2

AI 1

COM
or
2.2 KΩ
See
SCCR annex
200/240 V • Wire the command:
ATV312 M3 Control command 2-wire: Control command 3-wire:
ATV 312 ATV 312
OR
24 V LI1 LI2 24 V LI1 LI2 LIx
380/500 V
ATV312 N4

LI1: forward LI1: stop


LI2: reverse LI2: forward
LIx: reverse
525/600 V • Next steps, do: 6 + 7 + 8 + 9.1
ATV312 S6

[LOCAL configuration]
5.2 (control by internal reference).

RUN
REF
MON CAN

6 + 7 + 8 + 9.2
CONF ERR

Do:

6 Apply power to the drive


• Ensure that Logic Inputs are not active (see Li1, Li2, Lix ).
• Apply power to the drive. ENT
• At first power up, the drive displays nSt (3-wire control) or rdY (2 -wire control), after pushed drive displays bFr.
• On next start-ups, the drive displays nSt or rdY .

7 Set motor parameters


• Refer to the motor nameplate for the following parameter settings.
Customer
Menu Code Description Factory setting
setting
[Standard mot. freq]:
bFr 50.0
Standard motor frequency (Hz)
[Rated motor volt.]:
UnS drive rating
Nominal motor voltage on motor nameplate (V)
[Rated motor freq.]:
drC- FrS 50.0
Nominal motor frequency on motor nameplate (Hz)
[MOTOR CONTROL]
[Rated mot. current.]:
nCr drive rating
Nominal motor current on motor nameplate (A)
[Rated motor speed]:
nSP drive rating
Nominal motor speed on motor nameplate (rpm)
[Motor 1 Cosinus Phi.]:
COS drive rating
Nominal motor cos ϕ on motor nameplate

www.schneider-electric.com 2/4 S1A10942 - 04/2014


7 Set motor parameters (continued)
• Set tUn parameter to YES.
Customer
Menu Code Description Factory setting
setting
drC- [Auto Tunning]:
tUn nO
[MOTOR CONTROL] Auto-Tunning for UnS, FrS, nCr, nSP and COS

DANGER DANGER
HAZARD OF ELECTRIC SHOCK OR ARC FLASH UNINTENDED EQUIPMENT OPERATION
• The Nominal Motor Parameters UnS, FrS, nCr, nSP and COS
• During auto-tuning, the motor operates at rated must be correctly configured before starting auto-tuning.
current. • If one or more of these parameters is modified after auto-tuning has
• Do not service the motor during auto-tuning. been performed, tUn will return to nO and the procedure must be
repeated.
Failure to follow these instructions will result in death
or serious injury. Failure to follow these instructions will result in death or serious injury.

8 Set basic parameters


Customer
Menu Code Description Factory setting
setting
[Acceleration]:
ACC 3.0
Acceleration time (s)
[Deceleration]:
dEC 3.0
Deceleration time (s)
SEt- [Low speed]:
LSP 0.0
[SETTINGS] Motor frequency at minimum reference (Hz)
[High speed]:
HSP 50.0
Motor frequency at maximum reference (Hz)
[Mot. therm. current]:
ItH drive rating
Nominal current on motor nameplate (A)
I-O- [Reverse assign.]:
rrS LI2
[INPUTS / OUTPUTS CFG] Reverse assignment
[2 preset speeds]:
PS2 LI3
Fun-> PSS- Preset speeds
[PRESET SPEEDS] [4 preset speeds]:
PS4 LI4
Preset speeds
Fun-> SAI- [Summing ref. 2]
SA2 AI2
[SUMMING INPUTS] Analog input

9 Set control choice


Menu Code Description 5.1 [REMOTE configuration] 5.2 [LOCAL configuration] Customer Setting
CtL- [Ref.1 channel]: Al1 (factory setting),
Fr1 AlU1
[COMMAND] Reference control Al2, Al3
I-O- [2/3 wire control]: 2C: 2-wire (factory setting)
tCC LOC
[INPUTS / OUTPUTS CFG] Command control 3C: 3-wire

9.1 [REMOTE configuration] 9.2 [LOCAL configuration]


(Factory setting)
MODE

Factory settings of parameters: 3s


LOC rdY
Fr1 = AI1
tCC = 2C
Factory settings of parameters:
Fr1 = AIU1
tCC = LOC
rrS = LI2
PS2 = LI3 35.
1
PS4 = LI4
[Output frequency] (Hz)

10 Start the motor


www.schneider-electric.com 3/4 S1A10942 - 04/2014
Menus structure

= ENT MODE
ESC

3s LOC 2s
rdY rdY
These 3 parameters are rEN
MODE
only visible at first power up ESC ENT
of the drive.
bFr 3s
Settings can be changed
subsequently in menu:
drC- for bFr Fr1 35. [Output frequency] (Hz)
CtL- for Fr1
I-O- for tCC.
tCC

MODE
[SPEED REFERENCE] rEF-

[SETTINGS] SEt-

[MOTOR CONTROL] drC-

[INPUTS / OUTPUTS CFG] I-O-

[COMMAND] CtL-

[APPLICATION FUNCT.] FUn-

[FAULT MANAGEMENT] FLt-

[COMMUNICATION] COM-

[MONITORING] SUP-

Parameter selection

= ENT

ESC ESC

SEt- ACC 15. Refer to the programming manual (BBV46385) for comprehensive menu descriptions.
ENT ENT

ESC A dash appears after menu codes to differentiate them from parameter codes.
dEC 26.
Example:
ENT
[SETTINGS] (SEt-), ACC parameter.

26.
SFr 1 flash
(save)

www.schneider-electric.com 4/4 S1A10942 - 04/2014

S-ar putea să vă placă și