Sunteți pe pagina 1din 16

Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Fig. 1
7SA513 line protection relay

Application Design Serial interfaces


The 7SA513 numerical line protection The compact 7SA513 line protection relay The unit is equipped with 2 serial inter-
relay provides selective and fast clear- contains all the components required for faces.
ance of faults on overhead lines and analog value acquisition and evaluation, The operating interface on the front is
cables with single and multiple end in- the operating and display panel, indica- suitable for connecting PCs. The DIGSI
feed in high voltage networks with any tion and command outputs, binary input operating program running under WIN-
type of meshing. The neutral point can be options, serial interfaces and auxiliary DOWS, provides user-friendly settings,
earthed, compensated or isolated. The voltage converters. The use of a powerful evaluation of fault recordings and faults,
main function is a fast 6-system distance 32-bit signal processor combined with a and commissioning.
protection with a polygon fault detection 16-bit standard processor permits in-
and tripping characteristic. A fault detec- tegration of numerous protection func- The system interface is available as a
tion program with a V/ /  characteristic tions into a compact device. fibre optics interface for connection to
is also available instead of the polygon the SINAUT LSA 678 substation control
Three housing versions can be supplied. and protection or a relay data concentra-
fault detection characteristic. The unit The version for surface-mounting on a
also incorporates all functions usually re- tor.
switchboard is fitted with double-tier ter-
quired for line protection. It can also be minals accessible from the front. The ver- The communication protocol used con-
used as backup overcurrent and distance sions for flush-mounting in a switchboard forms to the recommendations of VDEW/
protection for all types of differential or cubicle have connecting elements at ZVEI based on IEC 870–5–103.
protection equipment. The unit can be the rear and are available with or without The Siemens-specific protocol conform-
integrated both into conventional installa- a glass cover. ing to DIN 19 244 is still available for ex-
tions and into SINAUT LSA 678 substa- isting installations.
tion control and protection. Method of operation
All data processing within the 7SA513 Setting
line protection relay is digital, from the All parameters can be set by the operator
measurement and digitization of voltages using the integrated keypad and display
and currents to the tripping decision panel or a PC. The parameters are stored
logic. Computer-bound, digital measuring in non-volatile memory so that they are
methods largely suppress the influence retained even after the supply voltage
of inrush currents, transient DC compo- has been switched off.
nents, higher frequency transients and
harmonics. In the distance protection Self-monitoring
function measuring errors due to load The hardware and software components
currents and currents on the parallel line are constantly monitored and any irregu-
can be compensated. larities are immediately detected and sig-
nalled. This ensures a high degree of
safety, reliability and availability.

Siemens LSA 2.1.12 . April 1996  Siemens AG 19961


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Distance protection
X
The main function of the 7SA513 line
protection relay is a six-system distance X+A
protection. By parallel calculation and
monitoring of all six impedance loops a
high degree of sensitivity and selectivity fA
is achieved for all types of fault. The
shortest command time is less than one
network cycle. fAE
The fault detection characteristic used is

R A1E
R A2E
R A1

R A2
the polygon impedance fault detection Z<
(see Fig. 2). The shape of the fault detec-
tion polygon permits optimum adaptation R
to the load conditions on the protected
line. Starting of unfaulted loops is elimi-
nated to prevent the adverse influence of
currents and voltages in the fault free
loops. Overcurrent fault detection can be X–A
activated in parallel to the polygon imped-
Fault detection area
ance fault detection.
Phase – phase fault
As an option to the polygon impedance
fault detection, voltage and angle-depen- Phase – earth fault
dent overcurrent fault detection may also
Fig. 2
be used (see Fig. 3). Fault detection polygon for polygon impedance (Z<)
This V/ I/ ö characteristic uses the phase
voltages Vph–E or the line voltages Vph–ph
Characteristic Characteristic
depending on the phase angle ö and the
phase current Iph according to the se- for ö fault without
detection ö fault detection X
lected mode of starting.
V PH–E
The polygon tripping characteristic per-
mits separate setting of the reactance X Fault detection area
and the resistance R (see Fig. 4). The Load area
fault detection ö
reactance section R can be set sepa-
rately for faults with and without earth
involvement. Earth faults are detected by V PH–E ( I>>)
monitoring the earth current IE, the nega- V PH–E ( I>) Load area
< >
tive phase sequence current I2 and/or the R
displacement voltage VE. V PH–E ( I>)
Fault detection area
Five distance zones can be set forward,
reverse or non-directionally, two of them
as overreach zones for automatic reclo-
sure and permissible tripping schemes. I> I> I>> IāPH
For each distance zone a time stage is Fig. 3
available for the directional and non-direc- Characteristics of the voltage and angle-dependent overcurrent fault detection V / I / ö
tional characteristic (A total of 10 inde-
pendent time stages).
X X3
Compensation for load current and paral-
lel lines is included. X2
Digital filtering of the measured values X 1L
makes the unit insensitive to distur-
bances in the measured quantities. In X 1B
particular the influence of DC compo-
nents, capacitive voltage transformers, X1
series compensated lines and frequency
changes are reduced.
Sound phase polarization and voltage me-
mories provides dynamically unlimited
R 1B
R 1E

R 1L
R1

R2
R3

directional sensitivity. Phase selective


approx.
1-pole or 3-pole tripping is possible when R
45°
used with 1-pole or 1 and 3-pole rapid or
delayed auto reclosing scheme.

Fig. 4
Tripping characteristics of the distance protection

2 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Distance protection (continued)


Following the loss of V.T. voltage inputs, PPOL X
the distance protection can be blocked
automatically to prevent incorrect opera- APOL X+A
tion.
The distance protection has an instanta-
neous tripping level >>>. If this level is
exceeded tripping is immediate. This Network power swing
level can be used on very long lines if a
large short-circuit current is expected
from close in faults while the short-circuit
current for reverse faults will definitely

R A1

R A2
be reduced to a level below the setting ffAA
value. The function can be deactivated R
(default setting).

Fault location
The fault location function calculates the
fault impedance and the distance-to-fault. X–A
The result can be displayed in ohms, kilo-
PPOL–APOL
meters or percent of the line length. Par-
allel line and load current compensation
is also available for fault location func-
Fig. 5
tion. Polygon for power swing detection

Signal transmission
For fast selective clearance of faults up Network power swings Overcurrent protection as a backup
to 100 % of the line length a signal trans- During network power swings large cur- function and emergency function dur-
mission function is available. The follow- rents can occur alone with small volt- ing measured voltage failure
ing modes may be selected: ages. Small voltages and large currents The 7SA513 line protection relay includes
D Permissible underreach transfer trip imply small impedances which can cause overcurrent protection. It can be used as
with fault detection distance protection tripping. To avoid un- a backup function and as an emergency
controlled tripping by the distance protec- function in the event of a short-circuit or
D Zone acceleration with Z1B
tion and to achieve controlled tripping in interruption in the voltage transformer
D Permissible overreach with overreach the event of loss of synchronism (pole circuit or if the circuit-breaker of the volt-
zone Z1B slip), a power swing supplement is avail- age transformer trips. The settings for
D Direction comparison with directional able for the 7SA513 line protection relay. the emergency function may differ from
fault detection The following operating modes for net- those of the backup protection function.
work power swings can be set: The overcurrent protection can be set as
D Unblocking mode with overreach zone
two-stage definite-time overcurrent
Z1B D Power swing blocking to prevent the
protection or as inverse-time overcurrent
D Unblocking mode with directional fault distance protection from tripping protection.
detection D Power swing tripping for controlled
D Blocking mode tripping in the event of unstable power
swings (out-of-step protection).
D Overreach zone comparison via pilot Switch-on-to-fault protection
wires Weak infeed protection Instantaneous tripping is possible when
D Reverse interlocking. energizing a short-circuited line. Initiation
To prevent delayed tripping of permissible
The transient blocking function is pro- schemes during weak or zero infeed situ- of the binary input “Manual Close” will,
vided with overreaching schemes to tran- ations, an echo function is provided. If no depending on the setting, result in instan-
sient or current reversals resulting from fault detector picks up at one end of the taneous tripping in Z1, Z1B or fault detec-
the clearance of short circuits on parallel line, the signal received here is returned tion.
lines. as echo to allow accelerated tripping at On definite, large current faults the high
the other end of the line. current instantaneous stage can initiate
It is also possible to initiate tripping dur- very fast 3-pole tripping even if the binary
ing a weak infeed. At the end of the line input “Manual Close” is not initiated.
where the fault detector does not pick
up, a phase selective 1-pole or 3-pole trip
is issued if a corresponding drop in the
PhE voltage is present.

Siemens LSA 2.1.12 . April 1996 3


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Automatic reclosure Synchronism check Fault value recording


The 7SA513 relay is equipped with auto- When connecting two network sections The digitized measured values of the
matic reclosure (ARC). The range of func- by control command or following a 3-pole phase currents, earth currents, phase
tions includes: auto-reclosure, it must be ensured that voltages as well as displacement voltage
D 3-pole RAR/DAR1) for all types of the two network sections are in synchro- and several binary channels are stored
faults nism. For this purpose a synchronism with a set pre- and post fault time. The
check function is provided. After verifica- fault value recording can be transferred
D 1-pole RAR for 1-phase faults, no re-
tion of network synchronism, the func- to a PC and the SINAUT LSA 678 substa-
close for polyphase faults tion enables the CLOSE command. Alter- tion control and protection for evaluation.
D 1-pole RAR for 1-phase and 2-phase natively reclosure can be enabled after a Parallel use of a PC and the substation
faults without earth, no reclose for checking that the busbar or line is not control and protection is possible. If the
poly-phase faults carrying a voltage (dead line or dead bus). VDEW/ZVEI interface is used, up to 8
D 1-pole RAR for 1-phase and 3-pole fault value recordings can be stored. The
RAR/DAR for poly-phase faults Overvoltage protection data memory is a ring buffer with a maxi-
On very long EHV lines that carry no or mum length of 10 s (at fN = 50 Hz). The
D 1-pole RAR for 1-phase and 2-phase
light load impermissible overvoltages can oldest fault value recording is overwritten
faults without earth and 3-pole RAR/ by the latest data. Fault value recording
DAR for other faults occur due to the Ferranti effect. For
protection against these overvoltages the can be started via a binary input or, as an
D Multiple-shot DAR aid to commissioning, via the integrated
7SA513 line protection relay contains a
D Interaction with an external device for two stage overvoltage protection. Com- operator panel or PC. The recording dura-
automatic reclosure via binary inputs pounding can be set for the V> stage that tion can then be parameterized.
and outputs calculates the voltages at the remote end The fault value recording memory is pro-
D Control of the integrated ARC function of the line. Tripping can be performed at tected against failure of the supply volt-
by external protection the local circuit-breaker or at the remote age.
end of the line by transmission of an in-
D ARC blocking for faults on the cable
tertripping signal. Marshalled command and alarm re-
portion of mixed cable/overhead lines
lays, LEDs, binary inputs
D Interaction with an internal or external Circuit-breaker failure protection The device is equipped with several com-
synchro check
The 7SA513 line protection incorporates a mand relays with trip duty contacts. They
D Monitoring of the circuit-breaker auxil- single stage circuit-breaker failure protec- can be assigned both to the commands
iary contacts. tion function to detect failure of trip com- of the integrated protection functions as
mands, for example due to a defective well as to all other alarm outputs or
High resistance earth–fault protection circuit-breaker. The current detection binary signals.
in an earthed network logic is phase selective and can therefore Alarm relays and LEDs can be freely as-
In earthed networks where high resis- also be used in single pole tripping signed for user-specific output and dis-
tance earth faults can occur, the fault schemes. If the fault current has not play of alarms and events. Several single
detection of the distance protection may been interrupted after a set time delay indications can be grouped together to
not be sensitive enough. The 7SA513 line has elapsed, the busbar trip command is form a group indication. The retentive
protection relay has protection functions generated. LED displays are protected against failure
for high-resistance earth faults of this na- of the supply voltage. All binary inputs
ture. Only one of these functions can be Parameter set switchover can also be freely marshalled.
active at any one time: It is possible to switch between four dif-
D Directional or non-directional earth ferent parameter sets via the binary in- Measuring and test functions
fault protection with definite-time over- puts, the integrated operating panel or Numerous measuring and test functions
current characteristic the serial operating interface. In this way are integrated in the 7SA513 line protec-
D Directional or non-directional earth
it is possible to adapt the protection relay tion for commissioning and operational
fault protection with inverse-time over- settings if the network configuration has measurement:
current characteristic been changed by switching actions.
D Measurement of the in-service imped-
D Directional or non-directional earth
Parameter set switchover is also pos- ance of all 6 loops and display of direc-
fault protection with voltage-depen- sible via the compatible VDEW/ZVEI in- tion, reactance and resistance
dent characteristic (V0 inverse charac- terface protocol.
D Monitoring of the phase sequence
teristic).
D In-service measurement
To implement a directional comparison ph1, ph2, ph3
scheme, the directional earth-fault func-
D In-service measurement
tion can be supplemented with a signal
Vph1-ph2,
transmission logic.
Vph2-ph3,
Earth-fault direction detection is per- Vph3-ph1,
formed with residual current and residual Vph1, Vph2, Vph3
voltage. In addition or as an alternative to
D Active and reactive power measure-
the residual voltage, the start point cur-
ment (W and VAR)
rent (Y) of an earthed transformer may
be used for polarization of the directional D Frequency measurement
earth-fault function. A phase selector per- 1) RAR – Rapid auto-reclosure
D Trip circuit test with circuit-breaker, 1
DAR – Delayed auto-reclosure
mits single pole tripping by the earth-fault ARC – Automatic reclosure and 3-pole
protection in the event of single phase D Test ARC, 1 and 3-pole.
earth-faults in conjunction with uni-polar
automatic reclosing.

4 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Non-volatile storage of operational re- User-definable binary inputs and time


cords delays, external trip signals
The 7SA513 unit provides detailed data To register binary signals that could for
for the analysis of faults and for checking instance be generated by other protec-
states during operation. All the event me- tion devices, 4 binary inputs are provided.
mories listed below are backed up They are stored in the operational event
against failure of the supply voltage. buffer and can be signalled via alarm re-
D Time lays, LEDs and SINAUT LSA substation
As a standard a battery backed up control.
clock is available which can be syn- The unit is also equipped with 2 settable
chronized via a binary input. The clock time stages. The start and reset signals
can be set via the PC and VDEW/ZVEI can be marshalled to binary inputs, the
interface. The time and date are as- time stage output to alarm relays and
signed to all events. LEDs. A wide range of pick-up and drop-
D Fault records off times can be set. In future the use of
The events of the last 3 network faults external time relays for special applica-
can be retrieved at any time via the tions will no longer be necessary.
integrated operator panels. The events Phase selective remote tripping with and
of the last 8 network faults are avail- without automatic reclosure can be
able via the PC interface. achieved by coupling external signals via
D Operational events binary input.
All events that are not immediately
associated by the fault are stored in
the operational event memory.
D Tripping statistics
For each pole of the circuit-breaker the
trip and close cycles as well as the
disconnected current are summated
separately.
D Automatic display on the LCD
An operating mode can be activated in
which up to 2 operational measured
values are display in the integrated
LCD. When a fault occurs the display
automatically indicates 2 selected
items of fault information.

Siemens LSA 2.1.12 . April 1996 5


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Technical data
Input circuits Rated current N 1 or 5 A
Rated voltage VN 80 to 125 V AC
Rated frequency fN 50 or 60 Hz
Thermal overload capacity in V.T. circuits, continuous 140 V AC
in C.T. circuits, continuous 4 x N
for 1 s 100 x N
Maximum dynamic overload 250 x N
Power consumption, voltage inputs approx. 0.5 VA
current inputs at N = 1 A approx. 0.1 VA
at N = 5 A approx. 0.2 VA

Power supply Rated auxiliary voltage Vaux (working range) 48, 60 V DC


via integrated converter 110, 125 V DC
220, 250 V DC
Permitted tolerance of the rated auxiliary voltage Vaux –20 to +15%
Max. ripple at Vauxnom 12%
Power consumption, quiescent approx. 15 W
energized approx. 40 W
Max. bridging time during auxiliary voltage failure 50 ms at Vaux 110 V

Input/output modules Quantity 2 or 3

Binary inputs Number per input/output module 8 (marshallable)


Voltage range, can be set with jumpers 24, 60 V DC
110, 125 V DC
220, 250 V DC
Current consumption approx. 3 mA

Alarm contacts Number of relays per input/output module each with 1 change- 9 standard relays or
over contact 6 standard relays and
1 Reed relay;
all relays can be marshalled

Switching capacity of the standard relays make/break 20 W/ VA


Permissible current for standard relays, continuous 1A
Switching voltage for standard relays 250 V AC/ DC
Switching power of the Reed relays make/break 15 W/ VA
Permissible current for Reed relays, continous 0.3 A
Switching voltage for Reed relays 220 V AC/ DC
Permissible load circuit capacitance for Reed relays max. 5 nF

Command contacts Number of relays per input/output module with 2 NO contacts 2 (marshallable)
each 1 000 W/ VA
Switching power make 30 W/ VA
break 250 V AC/ DC
Switching voltage 5A
Permissible current continuous 30 A
0.5 s

LED displays Ready green 1


Faulty red 1
Converter healthy green 3
Marshallable displays per input/output module red 8

Serial interfaces Operating interface On the front, not isolated, suitable for con-
necting a personal computer
Baud rate 1 200 to 19 200 bd
System interface isolated, suitable for linking to a central
Baud rate unit
Fibre-optic connection 1 200 to 19 200 bd
Integrated FSMA plug connector for FO
Optical wavelength connection with ceramic connector
Permissible line attenuation 820 nm
Distance up to 8 dB per glass fibre 62.5/125 mm
up to 2 km

6 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Technical data (continued)


Mechanical design Housing, dimensions 7XP20, see dimension drawing
Degree of protection to EN 60529 Housing IP 51
Terminals IP 21
CE conformity, regulations The product meets the stipulations of the guideline of the council This conformity is the result of a test that
of the European Commities for harmonization of the legal require- was performed by Siemens AG in accor-
ments of the member states on electro-magnetic compatibility dance with article 10 of the guideline and
(EMC guideline 89/336/EEC). the EN 50081–2 and EN 50082–2 basic
The product conforms with the international standard of the specifications.
IEC 255 series and the German national standard DIN VDE 57
435 / Part 303.
The unit has been developed and manufactured for use in indus-
trial areas in accordance with the EMC standard. The unit has not
been designed for use in living quarters as defined in standard
EN 50081.

Insulation tests Voltage test (100% test), all circuits except for auxiliary voltage 2 kV (RMS value), 50 Hz
IEC 255–5, DIN VDE 0435 Part 303 Voltage test (100% test), only auxiliary voltage 2.8 kV DC
Surge voltage test (type test), all circuits, Class III 5 kV (peak value), 1.2/50 ms, 0.5 J,
3 positive and 3 negative surges at inter-
vals of 5 s
EMC tests for noise immunity High frequency test 2.5 kV (peak value), 1 MHz, t = 15 ms,
(type tests IEC 255–22–1, Class III and DIN VDE 0435 Part 303, Class III 400 pulses per s, test duration 2 s
Standards: IEC 255–22 (product standard) Static discharge test 4 kV / 6 kV contact discharge, 8 kV air dis-
EN 50082–2 (basic specification) IEC 255–22–2, Class III and EN 61000–4–2, Class III charge, both polarities, 150 pF, Rl=330 W
DIN VDE 0435 Part 303 Irradiation with high frequency field, unmodulated, 10 V/m, 27 to 500 MHz
IEC 255–22–3 (report), Class III
Irradiation with high frequency field, amplitude-modulated 10 V/m, 80 to 1000 MHz, 80 %, 1 kHz, AM
ENV 50140, Class III
Irradiation with high frequency field, pulse-modulated 10 V/m, 900 MHz, repetition rate 2000 Hz,
ENV 5014 / ENV 50204, Class III ED 50 %
Rapid burst 2 kV, 5/50 ns, 5 kHz, burst length = 15 ms,
IEC 255–22–4 and EN 61000–4–4, Class III repetition rate 300 ms, both polarities,
Rl=50 W, test duration 1 min
Line-bound high frequency, amplitude-modulated 10 V, 150 kHz to 80 MHz, 80 %, 1 kHz, AM
ENV 50141, Class III 30 A /m, continuous, 300 A /m for 3 s,
Magnetic field with power system frequency 50 Hz
EN 61000–4–8, Class IV
EMC tests for interference emission Radio interference voltages, only auxiliary voltage 150 kHz to 30 MHz
(type tests) CISPR 11, EN 55011, limit value A and
Standards: EN 50081–2 (basic specifications) DIN VDE 0875 Part 11, limit value A
Radio interference field strength 30 to 1000 MHz
CISPR 11, EN 55011, limit value A and
DIN VDE 0875 Part 11, limit value A
Climatic stress Permissible ambient temperature during operation –5 to +55 °C
during storage –25 to +55 °C
during transport –25 to +70 °C
Humidity stress Average annual relative humidity v75 %,
on 30 days in the year up to 95 % relative
humidity, condensation not permissible
Mechanical test stress Permissible mechanical stress during operation 10 to 60 Hz, 0.035 mm amplitude
IEC 255–21–1, IEC 68–2 60 to 500 Hz, 0.5 g acceleration
during transport 5 to 8 Hz, 7.5 mm amplitude
8 to 500 Hz, 2 g acceleration
Distance protection Setting ranges
Earth fault detection
Earth current E /N in steps of 0.01 0.1 to 1
Displacement voltage
Ǹ
V E u (+ 3 x V 0, earthed networks) 1V 2 to 100 V
V E u (+ Ǹ3 x V 0, unearthed networks) 1V 10 to 100 V
Impedence start (Z<)
Characteristic polygon
Range forward X+ 0.01 W 0.1 to 200 W1)
Range backward X– 0.01 W 0.1 to 200 W1)
Resistance tolerance 0.01 W 0.1 to 200 W1)
Limit angle between load and
short-circuit range 0.1_ 30 to 80_
Minimum current ph> / N 0.01 0.1 to 4
Overcurrent ph>> / N 0.01 1 to 20

1) Impedance settings refer to N = 1 A; at N = 5 A


these values are 5 times the secondary values

Siemens LSA 2.1.12 . April 1996 7


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Technical data (continued)


Distance protection (continued) Setting values (continued)
Voltage and angle-dependent overcurrent
start (V / / )
Phase-to-earth voltage Vph–E ( >) in steps of 1V 20 to 70 V
Phase-to-earth voltage Vph–E ( ơ) 1V 20 to 70 V
Phase-to-phase voltage Vph–ph ( >) 1V 40 to 130 V
Phase-to-phase voltage Vph–ph ( ơ) 1V 40 to 130 V
Minimum current ph> / N 0.01 0.1 to 1
Overcurrent ph>> / N 0.01 0.25 to 4
Limit angle between load and short-
circuit range  1_ 30 to 60_ or 90 to 120_
Distance measurement
Characteristic polygon
Distance zones 5, 2 of these as overreach zones and all
can be set forward, backward or non-direc-
tional
Range X 0.01 W 0.05 to 130 W
Resistance tolerance R
for phase-to-phase fault 0.01 W 0.05 to 65 W
for phase-to-earth fault 0.01 W 0.05 to 130 W
Time stages 7 for multi-phase faults
3 for single-phase faults
Ranges 0.01 s 0 to 32 s or deactivated
Earth impedance matching
X E RE 0.01 –7 to 7
,
X L RL
Parallel line matching
X M RM 0.01 –7 to 7
,
X L RL
Distance protection instantaneous tripping level >>> (non-direc-
tional)
Smallest setting value 3 x N
Greatest setting value 20 x N
Default ∞ (no tripping with >>> level)
Load current compensation
Direction detection for all types of error with externally generated short-circuit trip-
ping voltages and voltage memory
Directional sensitivity dynamically unlimited
Times
Shortest command time
approx. 18 ms at fN = 50 Hz
Shortest command time (distance protection instantaneous approx. 16.5 ms at fN = 60 Hz
Tripping level >>>) approx. 11 ms
Releast time after OPEN command approx. 25 ms
after start release without OPEN command approx. 30 ms
Tolerances
Measuring tolerances to DIN VDE 0435 Part 303
(for sinusoidal measured quantities)
For impedence start DX v 5 % for 30o v  v 90 o
X k
DR v 10 % for 0o v  v 60 o
R k
For distance measurement DX v 5 % for 30o v  v 90 o
X k
DR
v 5 % for 0 o v  v 60 o
R k
For amplitude measurement "5 %
Timer accuracy v1 % of setting value or 10 ms

Instantaneous disconnection High current start k> / N 1 to 25


on connection to short-circuit Shortest command time approx. 11 ms

Fault location Output of the distance to fault in W secondary, W primary, km, %


Start signal Trip, start release, binary input
Setting reactance per unit in steps of 0.01 W/km 0.01 to 5 W/km
Parallel line compensation can be set as an option
Load current compensation can be set as an option
Measuring tolerances to DIN VDE 0435 Part 303 v2.5 % line length
(for sinusoidal measured quantities) at 30° vk v90 ° and Vk/VN w0.1

1) Impedance settings refer to N = 1 A; at N = 5 A


these values are 5 times the secondary values

8 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Technical data (continued)


Signal transmission Modes
Permissible schemes PUR transfer trip with fault detector
ZOne acceleration with Z1B
Comparison methods POR
Direction comparison
Unblock with fault detector
Unblock with Z1B
Blocking procedure
Overreach zone comparison via pilot wire –
Reverse interlocking –

Power swing add-on module Principle of power swing protection Measurement of the rate of change of the
(for impedance start Z<) impedance vector
Modes Power swing blocking
Power swing tripping
Difference power swing and fault detector
polygon in steps of 0.01 W 0.1 to 50 W
Rate of change dR/dT 1 Wā/s 0 to 200 Wā/s
Operating time 0.01 s 0.01 to 32 s or until the end of power
swing

Weak infeed protection Mode Echo function and/or trip


with comparison and blocking schemes:
active during signal reception without fault
detection

Overcurrent time protection Characteristic Definite-time overcurrent protection, in-


verse time overcurrent protection
Applications as backup protection function,
as emergency function with automatic ac-
tivation following measured voltage failure
or voltage transformer mcb trip
Setting range of definite time overcurrent protection
High set Phase Iph>>/IN in steps of 0.01 0.1 to 9.99
Earth IE>>/IN 0.01 0.1 to 4
Overcurrent Phase Iph>/IN 0.01 0.1 to 9.99
Earth IE>/IN 0.01 0.1 to 4
Times tI>, tIE>, tI>> 0.01 s 0 to 32 s or deactivated
Shortest command time approx. 30 ms
Setting range of inverse time overcurrent protection
High set (DT) Phase Iph>>/IN 0.01 0.1 to 9.99
Earth IE>>/IN 0.01 0.1 to 4
Overcurrent (IDMT) Phase IP/IN 0.01 0.1 to 4
Earth IEP/IN 0.01 0.1 to 4
Time multiplier tp 0.05 to 32
Pick–up threshold 1.1 x Ip
Characteristic according to IEC 255–4, Section 3.5.2 or BS 142 normally, very, extremely inverse
Measuring tolerance according to DIN VDE 0435 Part 303
Pick-up level DT v"5 %
IDMT Pick-up at 1.05 <I/IP <1.15
Time delay DT 1 % of setting value or 10 ms
IDMT v5 % "15 ms for 2 vI/IP v20 and
1 s vtP v20 s

Earth–fault protection Directional earth fault definite time protection with non-direc-
for high–resistance earth faults in an earthed tional backup protection
network
Pick–up with earth current IE>/IN in steps of 0.01 0.1 to 4
Displacement voltage V E u (+ Ǹ3 x V 0) 1V 0.1 to 10 V

Direction detection with with IE and VE and Y


Signal transmission method Direction comparison
Times
Shortest command time approx. 30 ms
Current reversal time approx. 30 ms
Trip delay 0.01 s 0 to 32 s or deactivated
Time tolerance v1 % of setting value or 10 ms
Directional earth IDMTL protection
Characteristics according to IEC 255–4, Section 3.5.2 Normal, very, extremely inverse
or BS 142
Pick-up value IE>/IN 0.01 0.1 to 4
Time multiplier t IE> 0.01 s 0 to 32 s
Tolerances
Current pick-up level Pick-up at 1.05 < I/IEP < 1.15
Operating times v5 % for 2 v( I/IE>) v20 and
1 s vt IE v20 s

Siemens LSA 2.1.12 . April 1996 9


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Technical data (continued)


Automatic reclosure Number of automatic reclosures Up to 10
Program Only 1-pole
Only 3 -pole
1 or 3-pole
Action times for RAR and DAR cycle
in steps of 0.01 s 0.01 to 320 s
Dead times in the RAR cycle 0.01 s 0.01 to 320 s
Dead times in DAR cycles 0.01 s 0.01 to 1 800 s
Reclaim times 0.01 s 0.5 to 320 s
CLOSE command duration 0.01 s 0.01 to 32 s

Synchronism check Modes for connection


Line dead/busbar dead V1</V2<
Line dead/busbar live V1</V2>
Line live/busbar dead V1>/V2<
Synchronism V1>/V2>
Permissible voltage difference DV in steps of 1V 1 to 50 V
Permissible frequence difference Df 0.01 Hz 0.01 to 1 Hz
Permissible angle difference Dö 1° 1 to 60°

Overvoltage protection Function


Voltage measurement, local
Voltage calculation, for the opposite end
(compounding)
Voltage selection 3 x Phase-to-earth voltages or
3 x Phase-to-phase voltages
Pick–up of the V>> level by ANDing the phase selective start signals
or
by ORing the phase selective start signals
Setting ranges
Voltage threshold V>/VN in steps of 0.01 1 to 1.9
Release ratio Vrel/V> 0.01 0.5 to 0.99
Voltage threshold V>>/VN 0.01 1 to 1.9
Release ratio Vrel/V>> 0.01 0.5 to 0.99
Times
t V> 0 to 32 s
t V>> with circuit-breaker closed 0.01 0 to 32 s
t V>> with circuit-breaker open 0.01 0 to 32 s
Command timer approx. 45 ms
Measuring tolerance according to DIN VDE 0435 Part 303 "5 %
(for sinusoidal measured quantities)

Circuit-breaker failure protection Setting ranges


Current start ISVS /IN in steps of 0.01 0.1 to 4
Delay time 0.01 s 0.05 to 1 s
Shortest release time approx. 10 ms
Time tolerance v1 % of setting value or 10 ms
Measuring tolerance according to DIN VDE 0435 Part 303 "5 %
(for sinusoidal meausred quantities)

Fault recording Measured quantities iph1, iph2, iph3, iE, Vph1, Vph2, Vph3, VE
Start signal for fault recording Trip, start, binary input, operator panel, PC
Memory management dynamic ring buffer
Maximum number of recordings available at one time 8
Sampling interval 20 value samples per network cycle
Maximum storage time (sum of all recordings)
at 50 Hz 10 s
at 60 Hz 8.3 s
Pre fault time in steps of 0.01 s 0.05 to 0.5 s
Post fault time 0.01 s 0.05 to 0.5 s
Maximum time for one recording 0.01 s 0.3 to 5 s

Additional functions Operational measured values:


Currents Iph1, Iph2, Iph3
Voltages Vph1–ph2, Vph2–ph3, Vph3–ph1, Vph1, Vph2,
Vph3
Power P/Q
Frequency f
Effective range 0 to 240 % x IN
0 to 120 %.x VN
0 to 120 % x PN
96 to 104 % x fN
Tolerance v2 % of the nominal value

10 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Selection and ordering data


Order No.
7SA513 line protection relay 7SA513 j – j j A j j – 0 C j j
Rated current at 50/60 Hz AC
1A 1
5A 5
Rated auxiliary voltage
48, 60 V DC 2
110, 125 V DC 4
220, 250 V DC 5
Construction
for switchboard surface-mounting B
for switchboard flush-mounting or cubicle flush-mounting C
for switchboard flush-mounting or cubicle flush-mounting without glass cover E
Functionality
V2 with impedance start, for earth networks 1
V3 with impedance start or V–/–/f start, for earthed or compensated networks, with VDEW interface 2
Input/output modules ( EAH )
2 EAH: 18 AR, 4 CR, 16 BI 0
3 EAH: 27 AR, 6 CR, 24 BI 1
2 EAH: 12 AR, 2 RR, 4 CR, 16 BI 2
3 EAH: 18 AR, 3 RR, 6 CR, 24 BI 3
Options A
without auto-reclosure, without synchro-check E
with auto-reclosure 1/ 3-pole, without synchro-check1) G
with auto-reclosure 1/ 3-pole, with synchro-check H
Options B
without earth fault backup protection for earth networks1) 0
with earth fault backup protection for earth networks 1

AR Alarm relay, switching power 20 W, 1A


RR Reed relay, switching power 15 W, 0.3 A
CR Command relay, switching power 1 000 W, 5 A
BI Binary input, voltage range 24 to 250 V DC settable

Documentation
Catalog LSA. 2.1.12 7SA513 line protection relay (V3) E50001–K5712–A221–A1
Manual 7SA513 feeder protection (V2.2) C53000–G1100–C86–2
Manual 7SA513 feeder protection (V3.1) C53000–G1100–C103–1

1) As of functionality V3 (11th position in the order number = 2).

Siemens LSA 2.1.12 . April 1996 11


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Housing for switchboard surface-mounting


L1 L2 L3
 L1 1 4B1
Version for switchboard flush-mounting/cubicle flush-mounting
1J1 47
E Command 1J3 97
5 4B2 1J4 98
2 3B1 relay 1
L2 1J2 48
6 3B2 1K1 49
L1 1K3 99
L2 3 2B1 Command
L3 1K4 100
L3 2B2 relay 2

7 1K2 50
E 4 1B1 7SA513 2J2 140
8 1B2 2J3 141
VL1 Signal relay 1
VL2 9 1A1 2J4 142
3J2 137
VL3 1) 10 1A2
VN 3J3 138
VL1 11 3A1 Signal relay 2
3J4 139
VL1 4J2 134
VL2 12 3A2 4J3 135
VL2 Signal relay 3
 VL3 4J4 136
VL3 13 3A3 2J1 131
VN
VN 14 3A4 3J1 132
Signal relay 4
4J1 133
5J2 128
5J3 129
Signal relay 5
5J4 130
6J2 187
L1 Signal relay 6 6J3 188
V2 15 2A1 6J4 189
L2 2A2 7J2 184
16
V2N Signal relay 7 2) 7J3 185
L3 147 2K3
Binary 7J4 186
148 2K4
input 1 5J1 190
149 2K1 2) 6J1 191
Binary Signal relay 8
150 2K2 7J1 192
input 2
143 3K3 8J2 181
Binary
144 3K4 Signal relay 9 3) 8J3 182
input 3 8J4 183
145 3K1
3K2
Binary EAH 0
146 1G1 43
input 4 1G3 93
197 4K3 Command
4K4 Binary 1G4 94
198 relay 3
input 5 1G2 44
199 4K1
4K2 Binary 1H1 45
200 1H3 95
input 6 Command
193 5K3 1H4 96
5K4 Binary relay 4
194 1H2 46
input 7
195 5K1 2G2 22
5K2 Binary
196 2G3 23
input 8 Signal relay 10
2G4 24
120 2H3 3G2 25
2H4 Binary
121 3G3 26
input 9 Signal relay 11
122 2H1 3G4 27
2H2 Binary 4G2 28
123
input 10 4G3 29
124 3H3 Signal relay 12
3H4 Binary 4G4 30
125
input 11 2G1 31
126 3H1
Binary 3G1 32
127 3H2 Signal relay 13
input 12 4G1 33
173 4H3 5G2 34
Binary
174 4H4 5G3 35
input 13 Signal relay 14
175 4H1 5G4 36
Binary 6G2 74
176 4H2
input 14 6G3 75
177 5H3 Signal relay 15
Binary 6G4 76
178 5H4
input 15 7G2 77
Binary inputs, signal relays, command relays 179 5H1
Binary Signal relay 16 2) 7G3 78
and LEDs can be freely marshalled 180 5H2
input 16 7G4 79
1) EP – Earth current of the parallel line or 5G1 80
Y – Neutral point current 88 1L4 6G1 81
1L3 Signal relay 17 2)
87 7G1 82
86 1L2 8G2 83
2) For 7SA513*–**** . Not available
2 L+ 37 1M1 8G3 84
1M2 Signal relay 18 3)
3 L – 38 PSH
8G4 85
EAH 1
3) For 7SA513*–**** . Reed relay 4D Fibre-optic interface link with 4D
2 central equipment
3

Fig. 6
Connection diagram for the 7SA513 line protection relay, version DD, with 2 input/output modules (for 7SA513 with 3 input/output modules see Fig. 7)

12 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

7SA513 line protection relay (Version V3)

Housing for switchboard surface-mounting


Version for switchboard flush-mounting/cubicle flush-mounting
112 2F3 1E1 39
Binary 1E3 89
113 2F4 Command
input 17 1E4 90
114 2F1 relay 5
Binary 1E2 40
115 2F2
input 18 1F1 41
116 3F3 1F3 91
Binary Command
117 3F4 1F4 92
input 19 relay 6
118 3F1 1F2 42
Binary
119 3F2 2E2 19
input 20
165 4F3 Signal relay 19 2E3 20
Binary
166 4F4 2E4 21
input 21 3E2 71
167 4F1
Binary 3E3 72
168 4F2 Signal relay 20
input 22 3E4 73
169 5F3
Binary 4E2 103
170 5F4
input 23 Signal relay 21 4E3 104
171 5F1 4E4 105
Binary
172 5F2 2E1 106
input 24
Signal relay 22 3E1 107
4E1 108
5E2 109
Signal relay 23 5E3 110
5E4 111
6E2 153
Signal relay 24 6E3 154
6E4 155
7E2 156
Signal relay 25 1) 7E3 157
7E4 158
Binary inputs, signal relays, command relays and
5E1 162
LEDs can be freely marshalled
Signal relay 26 1) 6E1 163
1) For 7SA513*–**** . Not available 7E1 164
2
8E2 159
3
Signal relay 27 2) 8E3 160
8E4 161
2) For 7SA513*–**** . Reed relay EAH 2
2
3

Fig. 7 (To be read together with Fig. 6)


Input/output module EAH2 in the 7SA513 line protection relay, with 3 input/output modules, version DD.

Siemens LSA 2.1.12 . April 1996 13


Overcurrent and Distance Relays

Dimension drawings in mm

450 30 172 29.5


445

Fibre optic

244

266
connection

266
1.5
10

Front view Side view

7.3 431.5
13.2 405
5.4

Diam. 5 or M4
255.8
245

Diam. 6

446
Panel cutout

Fig. 8
7SA513 with housing 7XP2050–2 (for panel flush mounting or cubicle mounting)

260
459 27 29.5
10 150
115 200
1

Cutout 20 x 60
(without paint)
40
280
344

266

1.5
39

1 50
51 100 71
206 31.7 7.5
444 149 20.3

Front view Side view

Fig. 9
7SA513 with housing 7XP2050–1 (for panel surface mounting)

14 Siemens LSA 2.1.12 . April 1996


Overcurrent and Distance Relays

Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions

Conditions of Sale and Delivery


Subject to the J
General Conditions of Supply and Delivery The technical data, dimensions and We reserve the right to adjust the prices
for Products and Services of the weights are subject to change unless and shall charge the price applying on
Electrical and Electronic Industry otherwise stated on the individual pages the date of delivery.
and to any other conditions agreed upon of this catalog.
with the recipients of catalogs.
The illustrations are for reference only.
A 9.91 a

Export Regulations
In accordance with present German and permissible without the approval of the Subject to change.
US export regulations export licences (da- relevant authorities except where current Relevant are the criteria stated in the
ted 02.95) are not required for the prod- German export regulations contain coun- delivery note and in the invoice.
ucts listed in this catalog. try–specific restrictions. An export licence may be required due
Export and re–export are therefore to country–specific application of the
product.

Trademarks Dimensions
All product designations used are trade- All dimensions in this catalog are given in
marks or product names of Siemens AG mm.
or of other suppliers.

Responsible for
Technical contents: Norbert Schuster,
Siemens AG, EV S T11, Nürnberg
General editing: Fr. Steffen/Hr. Reichel,
Siemens AG, EV S SUP22, Nürnberg

Siemens LSA 2.1.12 . April 1996 15


Overcurrent and Distance Relays

Bereich
Energieübertragung und -verteilung Power
Geschäftsgebiet Sekundärtechnik
P. O. Box 48 06 Transmission
D-90026 Nürnberg and Distribution
16
Siemens Aktiengesellschaft Order No.: E50001-K5712–A221-A1–7600
Siemens LSA 2.1.12 . April 1996
Printed in the Federal Republic of Germany
KG K 0496 3.0 SC 16 En 36Z420 6101/U277

S-ar putea să vă placă și