Modelling Parameters Input


1. Crack Section Properties

NSCP 2016
Structural Components
Stiffness Modifiers
Columns 0.70
Shearwalls (Cracked) 0.35
Shearwalls (Un-Cracked) 0.70
Gravity Beams 0.35
Frame Beam (girders) 0.40
Slab (Conventional) n/a, 0.25
Flat Slabs 0.25

2. Defining Mass Source

NSCP 2016
Loads
Factors
Self-Weight 1.0
Superimposed DL 1.0
Live Load < 100psf 0
Storage Live Load ≥ 125psf 0.25
Permanent equipment
1.0
operating weight

3. Diaphragm Definition and Assignment (Rigid/Semi-Rigid)


4. Define Load Cases
Load Cases Designation
Self-Weight DEAD
Superimposed DL SDL
Live Load < 100psf LL
Storage Live Load ≥ 125psf LL1
Permanent equipment
LL2
operating weight
Static Quake Along X EQX
Static Quake Along Y EQY
NSCP 2016
Lateral Load Parameters
Factors
Distance to Fault 5.0km
Fault Type A
Na , Nv 1.0 , 1.2
Ct, R 0.02 , 8.5
Ca, Cv, Z 0.4 , 0.672 , 0.4
Seismic Zone 4
STRUCTURE INSTITUTE
Lecture and Hands-On Series 1 Batch 2
July 22-23 & 29-30, 2017
Ground Floor Function Hall, South Tower,
LA VERTI Residences, Donada St., Pasay City

5. Define Special Seismic Load Effects


6. Review Support Conditions
7. Define/Assign Rigid Zone Factor and End Offsets
8. Define Dynamic Analysis Parameters (Set Number of Modes)

Set P-Delta Parameters

NSCP 2016
Loads
Factors
Self-Weight 1.2
Superimposed DL 1.2
Live Load < 100psf 0.50
Storage Live Load ≥ 125psf 0.50
Permanent equipment
1.2
operating weight
Number of Iterations 3

Useful Links:
https://www.youtube.com/watch?v=E12x8nulJiI
http://www.nzsee.org.nz/db/Bulletin/Archive/27%282%290129.pdf

9. Check load assignments for SDL, Live and Perimeter Line loads.
10. Run Modal Analysis and Check for Basic Response Indicators
a) Check/Open Analysis Log File for Errors and Instability
b) Check for 90% Mass Participation Ratios*
Useful Links:
https://www.youtube.com/watch?v=NRV779N2IYg
https://www.youtube.com/watch?v=ilQuptmUJq0
http://www.nzsee.org.nz/db/Bulletin/Archive/27%282%290129.pdf
c) Check for the response in Mode 1, Mode 2, and Mode 3*
* If desired response is not meet re-adjust model geometry and/or dynamic analysis parameters – then
repeat Step 9a to Step 9c.
11. Define Response Spectrum Function/s (Min. Eccentricity = 5%)
12. Define Orthogonal Load Combination/s
STRUCTURE INSTITUTE
Lecture and Hands-On Series 1 Batch 2
July 22-23 & 29-30, 2017
Ground Floor Function Hall, South Tower,
LA VERTI Residences, Donada St., Pasay City

13. Define Wall Group and Wall + Column Group for Section Cuts
14. Define Section Cuts for Walls and Walls + Columns for Checking of 25% Back-Up Frame Check
Useful Links:
https://www.youtube.com/watch?v=POMegXlcs5k
https://www.youtube.com/watch?v=Agi4nCXmiPM
15. Define Pier Label for Computation of Reliability Factor (Rho) and Shearwall Design
Useful Links:
https://www.youtube.com/watch?v=UhkJq4tcHHE
https://wiki.csiamerica.com/display/etabs/Pier+and+Spandrel+Labeling+and+Design
16. PERFORM ANALYSIS
17. Check/Open Analysis Log File
18. Check Column Gravity Loads. How?
Estimate Total LL Reaction = Ave. Live Load x Tributary Area x Number of Floors
Estimate Total SDL Reaction = Ave. SDL x Tributary Area x Number of Floors
Estimate Total SW Reaction = (6.6kPa – 7.3kPa) x Tributary Area x A x B
A = Approximation only = 1.4-1.6 for corner column, 1.1-1.2 for corner column, 1.0 for Interior column
B = 1.0 for 10F, 1.1 for 20F, 1.2 for 30F, 1.3 for 40F (interpolate is needed)
19. Check Static Base Shear and compare with manual calculations, Manual Calculations Based on Static
Force Procedure from NSCP’15/UBC’97.
STRUCTURE INSTITUTE
Lecture and Hands-On Series 1 Batch 2
July 22-23 & 29-30, 2017
Ground Floor Function Hall, South Tower,
LA VERTI Residences, Donada St., Pasay City

20. Check for Torsional Irregularity


Useful Links:
https://www.youtube.com/watch?v=wIjfDdeEKBs
https://www.youtube.com/watch?v=H6COaEEGbM8
21. If Necessary Adjust the Eccentricity for Torsion Amplification and Re-Run analysis
22. Check for Diaphragm Displacements/Total Drift per Floor
23. Check for Inter-Storey Drift Ratio
Useful Links:
https://www.youtube.com/watch?v=rkqcy214Wyk
https://www.youtube.com/watch?v=FFeQfceEWSU
24. Check for Reliability/Redundancy Factor (Rho) Values
25. Check Base Shear Distribution per Floor for 25% Back-up Frame Requirement.
26. If you’re satisfied with results of Item 24 and 25 proceed with step 27 otherwise revised model then
perform check from Step 13 to 25. Note, (a) If you alter wall and column locations re-assign group for
walls and (walls+columns) as well as pier labels assignments before checking step 25 and 26 (b) Set
eccentricity back to 5% for Response Spectrum Case.
27. Reduce the Response Spectrum Base-shear to Match Static Base Shear from Etabs or from Manual
Calculations.
28. Now you have a code compliant P R E L I M I N A R Y Structural Analysis Model

NOTE:
Before running the modal analysis, it is important that you check carefully the
consistency of the units on the structural model. This includes material definition,
properties, and loads.

story drift limit = 1/50 or 0.02