Sunteți pe pagina 1din 1

ANNEXURE II - BATTERY CHARGER SIZING CALCULATION

Ref: EXP – 458-13, R4 Date: 02/01/2014

BATTERY-CHARGER SIZING CALCULATION

CUSTOMER : ABB

PROJECT : Kenya Project

110V DC SYSTEM :-

SYSTEM VOLTAGE : 110V

BATTERY CAPACITY : 300 AH (Considered form battery details)

CONTINUOS LOAD CURRENT : 22.32 Amps (Considered form battery details)

BATTERY CHARGING CURRENT : 300 Ah X 0.2 = 60.0A

CHARGER RATING : Continuous current + Battery charging current


: 22.32 A + 60.0 = 82.32A

CHARGER RATING WITH FACTORS : 82.32 A x 1.1 = 90.55 AMPS (Rounded to 90A)

CHARGER OFFERED : 110 TP 90 Dual Float cum Boost Charger

48V DC SYSTEM :-

SYSTEM VOLTAGE : 48V

BATTERY CAPACITY : 200 AH (Considered form battery details)

CONTINUOS LOAD CURRENT : 14.75 Amps (Considered form battery details)

BATTERY CHARGING CURRENT : 200 Ah X 0.2 = 40.0A

CHARGER RATING : Continuous current + Battery charging current


: 14.75 A + 40.0 = 54.75A

CHARGER RATING WITH FACTORS : 54.75 A x 1.1 = 60.21 AMPS (Rounded to 60A)

CHARGER OFFERED : 48 TP 60 Single Float cum Boost Charger