Documente Academic
Documente Profesional
Documente Cultură
09175375413
INTRODUCTION
MEF 513D1 – Air Conditioning and Ventilation Systems 2
Hot and Humid
CHAPTER 1
INTRODUCTION
enjoyment of healthy eating. For students who use the canteen regularly, the
food purchased makes a significant contribution to their total food intake and
The two main ways in which school canteens have an impact on school
life are in supporting teaching through proper nutrition and health practices;
including the provision of special dietary requirements for some students and
staff, and in being sectors of schools which can easily become trouble zones if
energy levels and prevents diseases, such as obesity and anaemia, which are
related to poor diet.
However, overheated places can and will affect the occupant’s comfort
and productivity. Air conditioners keep the students, faculties, employees and
MEF 513D1 – Air Conditioning and Ventilation Systems 3
Hot and Humid
1. Air Change. A quantity of fresh air equal to the volume of the room or
building being ventilated.
through which heat, light, air and moisture are transferred between the
internal spaces and the outside environment.
deposition of water from moist, warm air onto a relatively cold surface of
between two surfaces such as within a cavity wall.
7. Cooling Load. The rate at which heat must be extracted from a space to
(humidity ration decreases); serves to increase the cooling power of the air
and can contribute to occupant comfort.
9. Dehumidifier. (1) An air cooler or washer used for lowering the moisture
content of the air passing through it; (2) An absorption or adsorption
maintaining the same ratio of sensible to total heat load in the process.
11. Enthalpy. The enthalpy of a mixture of dry air and water vapor is the sum
difference.
14. Heat, Latent. Refers to the heat added or removed during a change of
state of a substance wherein the temperature remains constant.
MEF 513D1 – Air Conditioning and Ventilation Systems 5
Hot and Humid
substance.
17. Heat Transfer. The movement of heat energy from one body to another
convection or conduction.
18. Humidification. The process of increasing the moisture content of the air
19. Humidity. It is defined as the amount of moisture or water vapor in the air.
20. Humidity, Specific. The amount of water vapor actually present in the air
21. Humidity, Relative. The ratio of the actual partial pressure exerted by the
water vapor in any volume of air to the saturation pressure corresponding
24. Psychrometry. The branch of physics that deals with the measurement of
atmospheric conditions and the study of the properties of mixtures of air
25. Temperature, Dew Point. The temperature where the water vapor content
of moist or humid air becomes saturated and any further cooling will
cause condensation.
28. Vapor. A gas, particularly one near to equilibrium with the liquid phase of
the substance and which does not follow the gas laws. Usually used
instead of gas for a refrigerant, and in general, for any gas below the
critical temperature.
been conditioned.
to the building location. A system must be designed to cope with the maximum
value of each of these requirements. The degree to which an HVAC system fails
To maintain air quality within acceptable limits of carbon dioxide, oxygen and
odor content;
To remove airborne contaminants produced by processes and occupants;
DESIGN
CONDITIONS
MEF 513D1 – Air Conditioning and Ventilation Systems 9
Hot and Humid
CHAPTER 2
DESIGN CONDITIONS
For this design, the authors referred to the range set by the American
Society of Heating, Refrigerating and Air-conditioning Engineers. These
reports available. The designers chose the month of April 2016 as the basis for
The selection of the outdoor dry bulb temperature was based from the
The following chart was the basis for the selection of the dry bulb
temperature which was based from a monthly weather report on Quezon City,
35
30
25
20
15
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
ARCHITECTURAL
LAYOUT
MEF 513D1 – Air Conditioning and Ventilation Systems 12
Hot and Humid
CHAPTER 3
ARCHITECTURAL LAYOUTS
MEF 513D1 – Air Conditioning and Ventilation Systems 13
Hot and Humid
EXTERNAL LOAD
GAIN
MEF 513D1 – Air Conditioning and Ventilation Systems 14
Hot and Humid
CHAPTER 4
EXTERNAL LOAD GAIN
loads and the internal loads. External load gains are cooling loads which were
based from the outside factors that influences the space being conditioned.
These are the heat conducted through walls, ceiling, floors, doors and glass
partitions.
W/m2K
A – Cross sectional area, m2
From the Table 18.2 Surface Heat Transfer Coefficients (p. 577)
-
Any Position 12.5 kmph Any 23.3 - -
-
Insulating
Mineral or Glass Wool 0.67 24 - 64 0.038 -
Materials
Rockwool 64 0.067 -
Fibreglass Board 0.7 64 - 144 0.038 -
Cork board 1.884 104 - 128 0.038 -
Cork granulated 1.88 45 - 120 0.045 -
Expanded polysterene (thermocole) - 30 0.037 -
PUF (Polyurethane foam) - 0.0173 -
Diatomaceous earth - 320 0.061 -
MEF 513D1 – Air Conditioning and Ventilation Systems 17
Hot and Humid
Thermal Thermal
Thickness Conductance
Material Conductivity Resistance
(m) (W / m2 K)
(W / m K) (m2 K / W)
External
- - 35 0.028571
Surface
Glass 0.00635 0.78 - 0.008141
Internal
- - 8.5 0.117647
Surface
Total Thermal Resistance, RT 0.154359
Ugw = 6.478404 W⁄ 2
m ∙K
Northeast Side
Agw = (0.40 m)(0.10 m)
Agw = 0.04 m2
Southwest Side
Agw = (0.40 m)(0.10 m)
Agw = 0.04 m2
Ugd = 6.478404 W⁄ 2
m ∙K
Southeast Side
Agd = (0.80 m)(2.10 m)(2)
Agd = 3.36 m2
Thermal Thermal
Thickness Conductance
Material Conductivity Resistance
(m) (W / m2 K)
(W / m K) (m2 K / W)
External
- - 35 0.028571
Surface
Glass 0.00635 0.78 - 0.008141
Internal
- - 8.5 0.117647
Surface
Total Thermal Resistance, RT 0.154359
Thermal Thermal
Thickness Conductance
Material Conductivity Resistance
(m) (W / m2 K)
(W / m K) (m2 K / W)
External
- - 35 0.028571
Surface
Wood, hard 0.05 0.158 - 0.316456
Internal
- - 8.5 0.117647
Surface
Total Thermal Resistance, RT 0.462674
Northeast Side
Qtdne =2(0.056976)=0.113952 kW
Southeast Side
Qtdse =2(0.056976)=0.113952 kW
Southwest Side
Qtdsw =3(0.056976)=0.170928 kW
Northwest Side
Qtdnw =2(0.056976)=0.113952 kW
Qtwd =0.51278 kW
Uwall = 2.943470 W⁄ 2
m ∙K
Northeast Side
Awne =[(3×81)-(16×0.04)-(2×0.8×2.1)]
Awne =239.0 m2
Qwne =UA(∆T)=2.943470×239×(37-24)
Qwne =9145.36 W=9.14536 kW
MEF 513D1 – Air Conditioning and Ventilation Systems 23
Hot and Humid
Southeast Side
Awse =42+27+5.64
Awse =74.64 m2
Qwse =UA(∆T)=2.943470×74.64×(37-24)
Qwse =2856.11 W=2.85611 kW
Southwest Side
Awsw =79.32+21+11.28+64.14+21+77.44
Awsw =274.18 m2
Qwsw =UA(∆T)=2.943470×274.18×(37-24)
Qwsw =10491.53 W=10.49153 kW
Northwest Side
Awnw =42+13.5+5.64+11.82
Awnw =72.96 m2
Qceiling =UA∆T=3.81183×1048.5×(30-24)
Qceiling =23980.22 W
Qceiling =23.98022 kW
MEF 513D1 – Air Conditioning and Ventilation Systems 25
Hot and Humid
Qfloor =UA∆T
Qfloor =1.574344×1048.50×(30-24)
Qfloor =9904.198 W
Qfloor =9.90420 kW
MEF 513D1 – Air Conditioning and Ventilation Systems 26
Hot and Humid
Qtgw = 0.07074 kW
Qtgd = 0.84893 kW
Qtwd = 0.51278 kW
Qwall = 25.28482 kW
Qceiling = 23.98022 kW
Qfloor = 9.90420 kW
QEXT = 60.60169 kW
MEF 513D1 – Air Conditioning and Ventilation Systems 27
Hot and Humid
INTERNAL LOAD
GAIN
MEF 513D1 – Air Conditioning and Ventilation Systems 28
Hot and Humid
CHAPTER 5
INTERNAL LOAD GAIN
cooling load came from lightings, occupants, equipment and other internal
loads.
5.2 FORMULAS
The formulas of external load gain are as follows:
Where:
Where:
The conditioned space uses GE work spaces 32 watt T8 for its interior
lighting, which provides 88 lumens per watt. GE work space fluorescent bulbs
provide neutral white light to help facilitate a positive place for work to get
done. These bulbs are ideal for home and commercial offices, retail and light
commercial applications.
MEF 513D1 – Air Conditioning and Ventilation Systems 31
Hot and Humid
Rating: 32 Watts
Qlights =2.680 kW
5.4 OCCUPANTS
By utilizing Table 19.1 for the rating of its occupants (indoor
temperature of 24°C), the designers are able to determine the proper rating
for its occupants. Diners fall under the category of eating in a restaurant,
counter staffs and food servers fall under standing category, food stalls crews
fall under light work in factory category, and the cleaners fall under the
category of dancing (even though they were not but their nature of its
Canteen also caters Senior Highschool Students and Faculty members. Thus, it
is expected that the heat gain from the occupants is much bigger than the
previous designs.
Heat Liberated
Type of Quantit Sensible Latent
Occupants S L y Heat Heat
5.5 EQUIPMENT
1 Cratcho 112
Food 1 920
Warmer
Chiller 1 - 64
Utensil 1 - 240
Sanitizer
1 Cratcho 280
Food 2 - 920
Warmer
- 690
Utensil 1 - 240
Sanitizer
Two-Way 1 - 28.8
Drinking
Fountain
Main Food 3 Food warmer 1 - 920
(Faculty lounge)
Chiller 1 - 368
Utensil 1 - 240
Sanitizer
Total 17550.44 W
MEF 513D1 – Air Conditioning and Ventilation Systems 35
Hot and Humid
VENTILATION
AND
INFILTRATION
CHAPTER 6
MEF 513D1 – Air Conditioning and Ventilation Systems 36
Hot and Humid
outdoor air and indoor recirculation air is not ventilation air either. It is
referred to as supply air.
outdoor air into an enclosed space. Infiltration occurs through cracks in the
building envelope and due to pressure differences between the inside and
outside conditions. The outdoor air entering through open doors and
windows is considered infiltration although the purpose of opening the door
6.2 FORMULAS
The calculation of ventilation and air change rate are achieved using the
where:
Outdoor Conditions
tout =37°C
RHout =70%
Indoor Conditions
tin =24°C
RHin =50%
Minimum
Recommended
Application Smoking Status cmm/m floor
cmm/person cmm/person
area
From Table,
The occupant count was based from the occupancy load calculations of the
diners. The count was 372 people. The designers utilize 0.21 cmm per person
based from the table above.
cmm=372×0.21
3
cmm=78.12 m ⁄min
OASH=0.0204×78.12×(37-24)
OASH=20.72 kW
OALH=50(cmm)(ωout -ωin )
OALH=50×78.12×(0.02821-0.0093)
OALH=73.86 kW
Given doors: 9 unused wooden doors (with doorlite) and 6 glass doors
OALH=50(cmm)(ωout -ωin )
OALH=50×34.776×(0.02821-0.0093)
OALH=32.880 kW
FOOD LOAD
MEF 513D1 – Air Conditioning and Ventilation Systems 44
Hot and Humid
CHAPTER 7
FOOD LOAD
7.1 INTRODUCTION
7.2 FORMULAS
7._ COMPUTATIONS
Dish Load
1. Chicken (fried);
QS = mCp∆t
m = 10 kg
Hours = 2hrs
10 kg 1 hr kg
m=( ) ( 3600 s ) = 0.001388888
2 hr s
kg kj
QS = (0.001388888 s ) (3.1 kg°C)(190 – 20)°C
MEF 513D1 – Air Conditioning and Ventilation Systems 45
Hot and Humid
QS = 0.731943976 kW
QL = mhfg (w1 – w2 )
kj kg
QL = (135.42 kg)(0.001388888 s )
QL = 0.188083213 kW
2. Fish (fried);
QS = mCp∆t
m = 3 kg
Hours = 2 hrs.
3 kg 1 hr kg
m = ( 2 hr ) ( 3600 s ) = 0.000416666 s
kg kj
QS = (0.000416666 s ) (3.6 kg°C)(190 – 20)°C
QS =0.255 kW
QL = mhfg (w1 – w2 )
kj kg
QL = (112.85 kg)(0.000416666 )
s
QL = 0.0470207581 kW
MEF 513D1 – Air Conditioning and Ventilation Systems 46
Hot and Humid
3. Beef
QS = mCp∆t
m = 10 kg
Hours = 2hrs
10 kg 1 hr kg
m=( ) ( 3600 s ) = 0.001388888
2 hr s
kg kj
QS = (0.001388888 ) (3.36kg°C)(100 – 20)°C
s
QS =0.3733333333 kW
QL = mhfg (w1 – w2 )
kj
= 64% - 60% = 4 %(2257) = 90.28kg
kj kg
QL = (90.28 kg)(0.001388888 s )
QL = 0.1253888086 kW
4. Pork;
QS = mCp∆t
m = 10 kg
Hours = 2hrs
10 kg 1 hr kg
m=( ) ( 3600 s ) = 0.001388888
2 hr s
kg kj
QS = (0.001388888 s ) (1.51 kg°C)(190 – 20)°C
QS =0.3565275496 kW
QL = mhfg (w1 – w2 )
kj
= 50% - 44% = 6 %(2257) = 135.42 kg
kj kg
QL = (135.42 kg)(0.001388888 s )
QL = 0.188083213 kW
A. Fruit Load
1. Banana
QBanana = mBanana (Respiration Heat)
m = 20 kg
W
= 20 kg (0.3kg)
QL = 6 W = 0.006 kW
B. Cooked Rice
Given:
75 cups of water = 15 kg
Total weight = 30 kg
kj
Cp(mix)=2.2142 kg C as according to research.net
QS = mCp∆t
30 kg 1 hr kj
QS = ( ) ( 3600 s )(2.2142 kg C) (100 − 20)
1 hr
QS = 1.476133333 kW
QL = mhg (w1 – w2 )
MEF 513D1 – Air Conditioning and Ventilation Systems 48
Hot and Humid
m = 5 kg of water
kj
hg=2676.1kg @ sat. Temp 1000C
15 kg 1 hr kj
QL = ( ) ( 3600 s )(0.43) (2676.1 kg)
1 hr
QL = 4.794679167 kW
PSYCHROMETRIC
PROCESSES
CHAPTER 8
PSYCHROMETRIC PROCESSES
8.1 INTRODUCTION
After the cooling and heating loads are calculated, these loads must be
picked up and applied to a specific system to be able to select the proper
HVAC equipment. One of the most useful tools available for this step is the
MEF 513D1 – Air Conditioning and Ventilation Systems 51
Hot and Humid
Equipment 17.55 0
Lightning 2.680 0
A 5% allowance of heat load is needed for safety for both RSH and RLH,
therefore:
RSH=139.63 kW
Components
Ventilation 20.72 73.86
OASH = 20.72 kW
RSH 139.63
RLH 71.5
OASH 20.72
OALH 73.86
GTH 305.71 kW
1 TR
GTH=305.71 kW×
3.516 kW
GTH=86.9482 TR
EQUIPMENT
SCHEDULE AND
SPECIFICATION
CHAPTER 9
EQUIPMENT SCHEDULE AND SPECIFICATION
Unit Weight:95.0Kg
Maximum Pipe Length 25.0m
Maximum Vertical
Seperation:15.0m
Compressor Type:Scroll
Refrigerant Piping
Connection:Flare
Refrigerant:R22
(Piping) Liquid:9.52mm (diameter)
Gas:19.05mm (diameter)
Connection Type:Flare
Condensate Drain:25mm
(outside diameter)
Cooling Capacity:63,300kJ/Hr
Model No.:42XQ061
Unit Dimensions
(WxHxD):(1650x625x232)mm
Unit Weight:39.0Kg
Carrier Floor Mounted FIXED SPEED
Unit Weight:90.0Kg
MEF 513D1 – Air Conditioning and Ventilation Systems 58
Hot and Humid
Maximum Vertical
Seperation:15.0m
Compressor Type:Scroll
Refrigerant Piping
Connection:Brazed
Refrigerant:R22
(Piping) Liquid:9.52mm (diameter)
Gas:19.05mm (diameter)
Connection Type:Flare
Condensate Drain:25mm
(outside diameter)
Cooling Capacity:63,300kJ/Hr
Model No.:42ASBFE600
Unit Dimensions
(WxHxD):(580x1750x430)
Unit Weight:62.0Kg
The AC units that are placed near the walls will start operating at 7:45
came in and out of the canteen to take early snack and take their lunch time
begun, all of the AC units will be started and changed in a high-cooled fan
with the same temperature for them to be more comfortable when peak
hours occur especially when it is 12 noon of the day where the diners keep on
becomes fully-operational that contributes a lot in the total heat load inside
the canteen.
Then after the peak hours and the hottest hour of the days which is
around 3:00 pm, the AC units that are in the middle will be the one left
operating until the closing hours of the canteen to prevent the over-usage of
Reading Installation Manuals or Tips before installing a unit in certain area can
save you time and money. And it covers the basic, but it also provides specific
guidelines for special situations that you may encounter in installing. It shows
drawings, charts and diagrams that help you get the most out of your
equipment.
The proper thermal expansion valve adjustment for superheat can increase
the efficiency of the evaporator, give you better system balance and more
evaporator. A properly sized and adjusted expansion valve will adjust to the
varying evaporator load and frosting conditions, allowing the evaporator to
refrigerant, preventing the system from cooling enough. The expansion valve
should be selected for the condensing unit capacity and not the evaporator
capacity.
From the evaporator, air must freely circulate in and around the product and
return back to the evaporator. The installation manual outlines minimum
space requirements away from walls and between units. It also provides tips
like, “Always avoid placement of unit cooler directly above doors and doors
opening.” Also, take into consideration accessibility to the unit for future
service and maintenance. It is not enough to get the unit in place, you must
have access to end panels, drain pan, etc. to be able to work on it later. In our
design, we place evaporative unit with .3 meters away from the wall.
oil return to the compressor. From Tech Topics volume three, number one:
“For oil return, the suction pipe is the most critical. The suction pipe should
slope toward the compressor and should be sized for minimum pressure drop
and proper refrigerant velocities.” Select pipe sizes carefully. If the pipe size
selected is too large, the refrigerant velocity becomes insufficient to carry oil
vertically up to the compressor when the compressor is above the evaporator.
The oil must pass freely through the entire system and reach a state of
equilibrium to maintain stable oil levels in the compressor.
Equally important in system piping design is the use of traps in the suction
line.
Step 5: Wirings
Prior to an installation, you need to evaluate your system and determine the
type and gauge of wire required for that particular job. For each length of
wire, you should consider all loads that will be powered on that circuit
MEF 513D1 – Air Conditioning and Ventilation Systems 62
Hot and Humid
including relays, contactors, and solenoids. The wire and transformer should
recommendations.
outside air to get to your unit. That includes space away from walls, fences,
and other units. Also, make sure one unit’s exhaust is not feeding into another
unit’s intake. Each unit should be located so air may circulate freely and not
be re-circulated. For proper airflow and access, all sides of the unit should be
a minimum of the width of the unit “W” away from any wall or obstruction. It
is preferred that this distance be increased whenever possible. Also make sure
you are providing yourself enough clearance to come back and service the
unit. Make sure all panels can open freely and that you have space to
manoeuvre tools and equipment. And don’t forget to look up, overhead
problems like loss of capacity and higher head pressures, which cause poor
operation and potential failure of equipment.
Before you install the expansion valve on the distributor of the evaporator, the
proper distributor nozzle must be installed. Most evaporators come with at
least two distributor nozzles, one for R-22 and another for most other
refrigerants. The nozzles that are shipped with the evaporator are sized to
meet most standard applications. The nozzles supplied the majority of
MEF 513D1 – Air Conditioning and Ventilation Systems 63
Hot and Humid
after the final leak test, refrigerant lines exposed to high or low temperature
environment conditions should be insulated to reduce subcooling in the
liquid line or heat gain in the suction line. Proper insulation maintains
consistent refrigerant temperatures, allowing the expansion valve and nozzle
temperature of the suction line you are running and by the R factor of the
insulation.
MEF 513D1 – Air Conditioning and Ventilation Systems 64
Hot and Humid
RECOMMENDATIONS
MEF 513D1 – Air Conditioning and Ventilation Systems 65
Hot and Humid
CHAPTER 10
RECOMMENDATIONS
canteen to minimize the Solar Heat Load. The ACU will be placed beside of
the food table or the food warmer to prevent the scattering of the odor of the
food.
should observed proper etiquette inside the canteen and avoid unnecessary
activities aside from eating that produce higher occupancy load.
The walls should be insulated so that the heat coming from the solar
radiation would be minimal. The glass windows should be reduced especially
MEF 513D1 – Air Conditioning and Ventilation Systems 66
Hot and Humid
in the south west area so that it will minimize the heat transfer coming from
direct sunlight especially during peak of the hottest hours of the day.
MAINTENANCE TIPS
You wouldn’t drive your car 100,000 miles without changing the oil.
The same logic holds true for your home comfort system. Regular HVAC
to avoid a system failure in severe hot or cold weather when you need it
most, and it can also keep your energy bill from getting out of control.
Many dealers provide priority service for their customers who have an
annual maintenance or service agreement. Bi-annual preventative
maintenance will ensure that your system runs as efficiently as possible. Your
local dealer will perform the following tasks, depending on the unit:
as necessary
Inspect coil and cabinet—clean as needed
Inspect fan motor and fan blades for wear and damage—on older
models lubricate as needed
capacitors, sump heat and other accessories. All control box and
On older models, lubricate motor and inspect and replace fan belt if
needed
Check combustion blower housing for lint and debris and clean as
necessary
Inspect evaporator coil, drain pan and condensate drain lines. Clean
as needed
refrigerant charge
Measure outdoor dry bulb temperature
Monitor gas furnace for correct line and manifold gas pressure—
make adjustments as needed
Draw blinds or drapes to block the sunlight during the hottest part of
the day.
than necessary.
Don't place lamps, TV sets or other heat-producing devices beneath a
Maintaining your air filter is easy, and routine maintenance will keep
you breathing easier.
Most filters are easy to slide or swap out, and it’s one of the few things
you can do to maintain your filter.
your filter will ensure the best filtration, increase the life of your machine, and
give you peace of mind that you’re breathing easier
To clean your Clean Effects™, simply remove your filter and then rinse
or vacuum it. If you rinse the collection cells, allow them to dry thoroughly
before replacing them.
SAFETY REMINDERS
Fan – re-circulating the filtered room air at low fan speed without the
Low cool – switches the compressor on the fan motor at high speed
for quick lowering of temperature depending on the weather
condition.
MEF 513D1 – Air Conditioning and Ventilation Systems 71
Hot and Humid
when set to a desired temperature. Turn the knob clockwise for cooler
temperature and counter clockwise for warmer.
down and/ or vertically louver from left to right. This should not be
done all throughout the day and should be ON only for 30 minutes to
spread evenly the cool temperature within the areas and also to
from your A/C unit during the coming cooling season, we are offering the
following recommendations
MEF 513D1 – Air Conditioning and Ventilation Systems 72
Hot and Humid
CRANKCASE - One of the most critical controls in the A/C unit is the
of once each year. If the condenser is located in a high dust and dirt
area, it should be scheduled for more frequent cleaning. A clean
condenser will prevent high head pressure which can shorten the life of
the unit. This is a easy step to avoid external equipment failure.
to start-up,
1. The contacts may be deteriorated as the result of cycling of
the compressor.
2. All terminal connections should be checked and tightened,
results of the analysis will let you know if the oil will hold up for the
coming season. If there is any question about the oil quality, the oil
should be replaced.
indicator. This device will detect the presence of moisture within the
system. If moisture is present, filter dryers should be installed or
the condition. New refrigerants (post R-22), will attract moisture and
can cause internal icing failures.
maintenance oversights.
HSB HELP - A/C logs are available through your local HSB inspector.
This information will help you schedule maintenance for your unit.
MEF 513D1 – Air Conditioning and Ventilation Systems 74
Hot and Humid