Documente Academic
Documente Profesional
Documente Cultură
Introduction 3/2
3
Overview 3/4
Accessories 3/8
Dimensions 3/12
The PSE has been designed to meet the most common requirements from the
water segment and is specialized on pump operation. It combines the requested
protections with a very compact design and built-in bypass. Remote operation
with external keypad or over fieldbus is available as an option.
3
• Two-phase controlled • Coated PCBA protecting from dust,
• Operational voltage: 208...600 V AC moist and corrosive atmosphere
• Wide rated control supply voltage: • Illuminated display that uses symbols to
100...250 V AC, 50/60 Hz become language neutral
• Rated operational current: 18...370 A • External keypad rated IP66 (Type 1, 4X,12)
• Voltage ramp and torque control for both as an option
start and stop • Fieldbus communication with FieldBusPlug
• Current limit adapter and the FieldBusPlug
• Kick-start • Analog output for display of motor current
• Built-in bypass for energy saving and • Electronic overload protection
easy installation • Underload protection
• Locked rotor protection
Saving time and money with built-in bypass and compact design
Improve installation
On the PSE, the bypass is built in and verified by ABB, saving you time during
Efficiency installation and space in your panel. The keypad is language neutral and illuminated
for easy set-up and operation in field. The compact design makes installation fast
and easy.
Productivity special torque stop ramp that is designed together with a pump manufacturer to
eliminate water hammering in an optimal way.
Screw mounting
PSE is fast easy to install by using screw mounting.
LED indicators
Illuminated and language-neutral
Green ready LED display with icons
Flashing - Suppy available The display on PSE uses icons for
Steady - Main available fast and easy set-up of parameters.
Green run LED Each icon indicates a different
Flashing - Ramping up/down parameter to set and makes
Steady - TOR navigation and setting of parameters
easy. Set-up is done by using the
Yellow protection LED
four buttons on the keypad.
Red fault LED
Normal start
PSE18 PSE25 PSE30 PSE37 PSE45 PSE60 PSE72 PSE85 PSE105
In-line connected
(400 V) kW 7.5 11 15 18.5 22 30 37 45 55
IEC, max. A 18 25 30 37 45 60 72 85 106
(440-480 V) hp 10 15 20 25 30 40 50 60 75
UL, max. FLA 18 25 28 34 42 60 68 80 104
400 V, 40 ºC
MCCB (35 kA)
Using MCCB only, type 1 T2N160 T3N250
coordination will be achieved 1) MCCB (50 kA)
T2S160 T3S250
To achieve type 2 coordination, Fuse protection (85 kA), Semiconductor fuses, Bussmann
semi-conductor fuses must be
used 1) 170M1563 170M1564 170M1566 170M1567 170M1568 170M1569 170M1571 170M1572 170M3819
1)
This is an example of coordination. For more examples see: applications.it.abb.com/SOC
Normal start
PSE142 PSE170 PSE210 PSE250 PSE300 PSE370
In-line connected
(400 V) kW 75 90 110 132 160 200
IEC, max. A 143 171 210 250 300 370
(440-480 V) hp 100 125 150 200 250 300
UL, max. FLA 130 169 192 248 302 361
400 V, 40 ºC
MCCB (35 kA)
Using MCCB only, type 1 T3N250 T4N320 T5N400 T5N630
coordination will be achieved 1) MCCB (50 kA)
T3S250 T4S320 T5S400 T5S630
1)
This is an example of coordination. For more examples see: applications.it.abb.com/SOC
Description
Selection table for normal start. Typical applications:
– Bow thruster
– Centrifugal pump
1SFC132001V0001
– Compressor
– Conveyorbelt (short)
– Elevator
3 PSE18 ... PSE105
– Escalator
If more than 10 starts/h, select one size larger than the standard selection.
For a more precise selection, use the online softstarter selection tool available by scanning the shown QR
code or using the selection tool available on:
new.abb.com/low-voltage/products/softstarters
Description
Selection table for heavy-duty start. Typical applications:
– Centrifugal fan
– Conveyor belt (long)
1SFC132001V0001
– Crusher
– Mill
– Mixer
– Stirrer 3
PSE18 ... PSE105
If more than 10 starts/h, select one size larger than the standard selection.
For a more precise selection, use the online softstarter selection tool available by scanning the shown QR
code or using the selection tool available on:
new.abb.com/low-voltage/products/softstarters
For softstarter type Wire range Tightening Type Order code Pkg Weight
1SFT98099_095C2
3
For softstarter type Wire range Tightening Type Order code Pkg Weight
1SFT98099-01C1
mm2 Nm kg (lb)
Cable connectors for Al and Cu cables
PSE142 … PSE170 95...185 31 – 1SDA054988R1 3 0.078 (0.172)
PSE210 … PSE370 185...240 43 – 1SDA055020R1 3 0.133 (0.293)
1SFT98000_011C3
kg (lb)
1SFT98099_125
Terminal shrouds
PSE142 ... PSE170, short for use with cable clamps 2 LT185-AC 1SFN124701R1000 2 0.050 (0.110)
PSE142 ... PSE170, long for use with compression lugs 2 LT185-AL 1SFN124703R1000 2 0.220 (0.485)
LT ... -AC LT ... -AL PSE210 ... PSE370, short for use with cable clamps 2 LT300-AC 1SFN125101R1000 2 0.070 (0.154)
PSE210 ... PSE370, long for use with compression lugs 2 LT300-AL 1SFN125103R1000 2 0.280 (0.617)
1SFC132328F0002
qty (1 pce)
kg (lb)
FieldBusPlug connection accessory
PSE18 ... PSE370 PS-FBPA 1SFA896312R1002 1 0.060 (0.132)
PS-FBPA
Time (s)
10 000
3
1000
100
Class 30
10 Class 20
Class 10
Class 10 A
1SFC132134F0201
1
0
0 1 2 3 4 5 6 7 8
Tripping curves for electronic overload protection (cold) for PSE and PSTX. Current (x Ie)
5 5
E1858D
ø 8.5
ø 10.2
5 mm (0,20 in)
13 mm
(0,51 in) 17,5 mm (0,67 in)
(1,57 in)
40 mm
6,5 mm (0,24 in)
(1,46 in)
37 mm
1SFC132260F0001
1SFC132259F0001
1SFC132266F0001
3 mm (0,12 in)
35 mm 35 mm
3 mm (0,12 in)
43,75 mm 43,75 mm
80 mm (3,15 in)
(1,69 in) (1,69 in)
26 mm
88 mm (3,46 in) (1,02 in)
27,4 mm
(1,06 in)
L1 L1
L2 L2
L3 L3
N N
L N L N
MCCB
Start Stop Start Stop 3
8 9 11 8 9 11
Start Start
Stop KM1 Stop
NC NO NC NO
2T1 4T2 6T3 3 4 5 6 7 2T1 4T2 6T3 3 4 5 6 7
1SFC132274F0001, rev.2
1SFC132237F0001, rev.3
U V W U V W
M M
3 3