200-21-04-4382

Amendment No. 5
Page 18 of 56

Tender Clarification No. 3 / Page 1 of 39

PART A : BUILDING WORKS AT BIDADARI CONTRACT 10 TO CONTRACT 12 AND


PARK (TOTAL : 1,355 DWELLING UNITS)
PART B : CONTINGENCY WORKS

Tender Clarification No. 3

S/N Query Response


1. Refer to TD-100 Series (Bldg blocks) eg. TD-110-112 Refer to Drawing No. (AR
Elevation, Kindly provide us detail and keyplans where to 801) in Amendment No.4.
located all the alum screens: Part print TD-111 Alum. Louvre rainscreens to
be located in front of RC
beam and terminates at
horizontal RC Canopy. For
horizontal RC Canopy that
stops above 1st storey
whereby there’s void decks
(non M&E room frontages),
additional alum. louvre
rainscreens to also be
catered for up to 3000mm
high from 1st storey FFL.

2. Refer to TD-272, kindly provide us keyplan to be located Refer to Drawing No. (AR
the Integrated Grill panel on low wall (Facing the Barley 958) in Amendment No.4.
Road & Bidadari Part Drive Side). Part print of TD- 272:
200-21-04-4382
Amendment No. 5
Page 19 of 56

Tender Clarification No. 3 / Page 2 of 39

S/N Query Response


3. Refer to TD-100 Series, and TD-272, kindly confirm To deploy GS Railing
between boundary of Common corridor and Soft sty are GS 1,250mm Height between
railing 1250mm ht or full height wall. Part print of TD-158& boundary of common corridor
272: and soft storey (clouded in
blue) inside attachment.

4. Refer to TD-100 Series, Kindly provide detail/keyplan for Refer to Drawing Nos. (AR
Aluminium Tresllis and Composite panels on each 641 – AR 646) in “Original
residential blocks. Part print of TD-188 & TD-223: Tender Drawing Set”
and “Amendment No. 4”.
200-21-04-4382
Amendment No. 5
Page 20 of 56

Tender Clarification No. 3 / Page 3 of 39

S/N Query Response


5. Kindly issue a Residential Block Signage’s drawings Refer to Drawing No. (AR
701) in Amendment No.1.

6. Refer to TD-701, kindly issue as detail dwg and also please Refer to architectural detail
reflect on plan as provided in legend: a) PDS-Precinct drawings (Section A7,
Drawing No. 17-42).
Directional Signboard b.)D- Precinct Directional Signboard
c) E-Signboard for block entrance f) illuminated directional
Sign plate. Part print of TD-701:

7. There is some discrepancies on the PL level Architectural Please highlight the area
Drawings and C&S Drawings. Kindly confirm the PL. [ queried on the
please refer to Drawing No.: HB-D1619-AR-051; HB-D1619- discrepancies.
CS-021 & HB-D1619-CS-022 ] To follow levels shown in
architectural drawings for
FFL in event that FFL and
SFL is the same.
200-21-04-4382
Amendment No. 5
Page 21 of 56

Tender Clarification No. 3 / Page 4 of 39

S/N Query Response


8. Please provide the missing drawings below Door Schedule Drawing No.
AR 275 is not valid. Refer to
Door Schedule Drawing No.
274.
For plan & section of
detention tank, refer to
Drawing No. AR 393 in
Amendment No.4.
Refer to Drawing No. 481 for
Alum. Door Schedule in
Amendment No.4.

9. Please confirm what type of door we will use for bedroom To use UPVC doors to
area. bedroom instead of semi-
a. Provisional Quantity of 1,745 Nos. UPVC doors to solid timber doors.
bedroom including approved ironmongeries,
accessories and painting as specified, provision of all
labour, materials, mobilization and demobilization of
equipment and tools and all related works.
200-21-04-4382
Amendment No. 5
Page 22 of 56

Tender Clarification No. 3 / Page 5 of 39

S/N Query Response


10. Please confirm if "(For Unit 587 & 607)" means we will use Yes, to use CW3/NS9 for
Window Type CW3/NS9 from 3rd to 16th floor of unit 587 & Unit Stacks 587 & 607 due to
607. See attached below use of thermochromic glass
windows for these west-
AR-243: cafing units. To refer to
Drawing No. AR 956 from
Amendment No. 4 for
locations of thermochromic
glass windows.

A-051:

11. Please provide elevation shows the accent tiles Accent Tiles are not required
to Kitchen and Bathroom.
Requirement for Accent Tiles
amended in Amendment
No.4.
200-21-04-4382
Amendment No. 5
Page 23 of 56

Tender Clarification No. 3 / Page 6 of 39

S/N Query Response


12. Please kindly confirm the material for linkway by using Please use Alum.
Aluminium Composite panel or Aluminium Honeycomb Honeycomb Panels (10mm
panel? what is the thickness? thk) instead of composite
panels.
Associated drawings AR 638,
AR 639, AR 641 will be sent
out in Amendment No.5.

13. As for metal roof, please provide the details roof drawing Refer to AR-364 that will be
showing the insulations. sent out in Amendment No.
5.
200-21-04-4382
Amendment No. 5
Page 24 of 56

Tender Clarification No. 3 / Page 7 of 39

S/N Query Response


14. Refer to TD-100 Series (Bldg blocks, Kindly verify what is To provide waterproofing
water proofing required to Roof over M&E and Utility room treatment to Roof Slab of
(CSR,TER,SPF, PUMP ROOM, etc. Below part Part print of M&E and Utility Rooms
TD-102: (CSR, TER, SPF, Pump
Rooms, etc).

15. Please provide detail of DU aircon Ledge as not provided Refer to architectural detail
on issued drawing. drawings (Section AWS02 –
Drawing Nos.7-9).

16. Refer to Std Supp Spect S73, please verify if accent tiles Accent Tiles are not
are required to Kitchen and Bathroom for residential blocks. required to Kitchen and
If yes, please provide us detail elevation. Below part Part Bathroom. Requirement
print of BS-S73: for Accent Tiles removed
in Amendment No.4.
200-21-04-4382
Amendment No. 5
Page 25 of 56

Tender Clarification No. 3 / Page 8 of 39

S/N Query Response


17. Refer to Form of Tender, please issue us detail of Grab bars Refer to Drawing No. AR 970
for residential blocks. Below part Part print of FOT ANNEXX and Sup Specs 73.52 (Grab
B-23 of 30: Bar Provisions to 2-RM
FLEXIs).

18. Refer to Form of Tender, please issue us detail of Built-in Refer to architectural detail
Kitchen cabinet and wardrobe for residential blocks. Below drawings (Section A7 –
part Part print of FOT ANNEXX B-22 of 30: Drawing Nos. 70-75).
200-21-04-4382
Amendment No. 5
Page 26 of 56

Tender Clarification No. 3 / Page 9 of 39

S/N Query Response


19. Refer to Booster pmp level of all resid blkcs and TD-100 Details for Metal Cat walk at
Series. Please provide detail of Catwalk maintenance to Solar Panel Area to be
solar panel area. Please provide also structural detail proposed by Builder
support and safety railing whether required. Below part print (compliant to statutory
of TD-108: requirements – BCA, etc)
and approved by SO Rep.
Safety Railings is required as
part of BCA’s requirements.
Refer to Section HE
(H.3.4.4A) and other relevant
info within code for safety
railing provisions for Metal
Cat Walk at Solar Panel
Area.

20. Refer to TD-341, Please verify the Door tag & detail service SPF Room Door Type to
room and ducts from Deck 1A/1B to 3rd sty the ff part print refer to architectural detail
of TD-314: drawings (Section A6,
Drawing No.45). Associated
Door Tag is (DT/1G), refer to
Drawing No. AR 274.

Door for Tel, El to use


(FDT/1E), refer to Drawing
No. AR 274.
Door for L&M to use
(FDT/3D), refer to Drawing
No. AR 274.
Door for W to use (FDT/1H(,
refer to Drawing No. AR 274.
200-21-04-4382
Amendment No. 5
Page 27 of 56

Tender Clarification No. 3 / Page 10 of 39

S/N Query Response


21. Again, may we request to issue us the signages for Refer to architectural detail
residential blocks, MSCP and Carpark at AAH. drawings Section A7
(Drawing Nos. 17-45 /
Drawing Nos. 51-69).
Refer to Drawing No. (AR
701) in Amendment No.1 on
Residential Blocks -
Signages.
Refer to Drawing No. (AR
702- AR 704) in Amendment
No.4. on Car Park Blocks -
Signages.
Refer to Drawing Nos. (AR
981 – AR 995) in
Amendment No. 4. On Car
Parks Blocks - Additional
Signages.

22. Kindly advise is it irrgation system needed in Hillock Irrigation system is not
Park. required for the Hillock Park
23. Kindly advise the water sources locations. Water source is not required
for the Hillock Park

24. Please kindly clarify that there is any light for Park area, For lighting plan of the Park,
If have, please kindly provide completed dwgs with please refer to EE028 and
light and cutsheet for Park. LA1820 & LA1821 (issued in
Amendment No. 5). For
details of the lighting, please
refer to LA1850 & SS79.33 –
Bollard Lighting

25. Please kindly find Hosereel Pressure Vessel Capacity. 60L

26. I went through the tender documents, however, I could There is no rainwater
not locate the information on the rain water harvesting harvesting system in the
system in the tender documents. Could you please M&E design.
provide me information like capacity, location of the rain
water harvesting system?

27. Please provide us completed dwgs with light and cutsheet For lighting plan of the Park,
for the Park area. please refer to LA1820 &
1821 in Amendment No. 5.
For details of the lighting,
please refer to LA1850 &
SS79.33 – Bollard Lighting

28. Please kindly issue us the Fire Alarm Schematic drawings Fire Alarm Schematic
which is not included in drawings can be found at
drawings (0 to A4). Dwg ME561 to ME564
200-21-04-4382
Amendment No. 5
Page 28 of 56

Tender Clarification No. 3 / Page 11 of 39

S/N Query Response


29. Please provide the lighting & power layout plan and single Please refer to EE029 to
line diagram for Precinct Pavilion (Blk- 213A & EE031 for lighting & power
215).(Refer to attached Dwg No.HDB-D1619-ME-005) layout plan and single line
diagram for precinct pavilion
30. For street lighting, we can found Legend at Dwg No.HDB- Please refer to EE026 and
D1619-ME-003.But, we can't find any drawing for street EE027 for lamppost location
lighting. Please provide the external lighting layout plan. and DB’L’ outdoor lightings
single line diagram
31. Refer to Dwg No. HB-M&E-STD-V1-EE(TEL-06), the EE(TEL-06) is for reference
schematic diagram of Alert Alarm system mentioned that only. Not applicable for this
floors are up to 31 storey. Actually, all blocks have up to project.
16 storey. Please clarify for this. Please provide also
specification for this system.

32. In FOT breakdown, Option-A (Conventional Carpark) and Please refer to Supplementary
Option-B (Future Ready Carpark), pls advise what is the Specifications Clause 73.51.
difference of these two options. For EPS system, please There is no difference for
provide to us schematic diagram, plan drawings and electrical installation for Option
specification. A & Option B. Please refer to
EE026, EE223, EE317 for
EPS system and single line
diagram.
33. Refer to as per attached Dwg No. HB-D1619-ME-131, 4rm & 5rm at 4th storey are
electrical schematic diagram for Blk-212C mentioned omitted. EE131 to be updated
4RM & 5RM rooms at 4th storey. But, these rooms are
not mentioned in plan (refer to as per attached Dwg
No.HB-D1619-ME-121). Please advise.
34. In regards with 8 numbers of shops at block 212, Please refer to EE266 and
please kindly know the shops's serial number to EE268 for the shop location
calculate the cable pricing as the incoming cable size is with different MCCB and
not same for these shops. incoming cable size
200-21-04-4382
Amendment No. 5
Page 29 of 56

Tender Clarification No. 3 / Page 12 of 39

S/N Query Response


35. Refer to Dwg No: Door code DM 5 for unit Bedroom door is To use UPVC doors to
timber or PVC door? Door schedule AR-274 Rev 1 (A1) bedroom instead of semi-
stated as Semi-solid Timber door, however FOT solid timber doors.
Amendment No.3 stated as UPVC door. Please clarify.
200-21-04-4382
Amendment No. 5
Page 30 of 56

Tender Clarification No. 3 / Page 13 of 39

S/N Query Response


36. Refer to Dwg No: AR-481 Rev 1 (A3), door code FDT 1H is one To use 2 hour fire-rated
hour or 1/2 hour fire rated door? Please clarify. doors for all service closets
at residential buildings and
car parks. Revised schedule
will be issued in Amendment
No.6.
200-21-04-4382
Amendment No. 5
Page 31 of 56

Tender Clarification No. 3 / Page 14 of 39

S/N Query Response


37. Refer to Dwg No: AR-482 Rev 1 (A3), door code FDT To use 2 hour fire-rated
2F1 is two hour or 1/2 hour fire rated door? Please doors for all service closets
clarify. at residential buildings and
car parks. Revised schedule
will be issued in Amendment
No.6.
200-21-04-4382
Amendment No. 5
Page 32 of 56

Tender Clarification No. 3 / Page 15 of 39

S/N Query Response


38. Blk 212A - 2nd sty Circled door is not required
Refer to Dwg No: AR-102 Rev 1 (A1), does circled door on 2nd storey.
exist at 2nd sty and what is the door code? Please
clarify.
200-21-04-4382
Amendment No. 5
Page 33 of 56

Tender Clarification No. 3 / Page 16 of 39

S/N Query Response


39 Blk 212A - 3rd sty Circled door is not required at
Refer to Dwg No: AR-103, does circled door exist at 3rd 3rd storey.
sty and what is the door code? Please clarify.

40. Blk 212A - 3rd sty Circled door is required at 4th


Refer to Dwg No: AR-104, does circled door exist at 4th storey for future
sty and what is the door code? Please clarify. maintenance. To use Door
Tag (DT/1C) for sanitary
stacks.
Circled door for FHR is not
required.
200-21-04-4382
Amendment No. 5
Page 34 of 56

Tender Clarification No. 3 / Page 17 of 39

S/N Query Response


41. Blk 212A - Main Roof To provide circled door at
Refer to Dwg No: AR-107_R1 (A1), does circled door main roof storey. Please use
exist at Main Roof sty and what is the door code? Please door tag (FDT/1G).
clarify.
200-21-04-4382
Amendment No. 5
Page 35 of 56

Tender Clarification No. 3 / Page 18 of 39

S/N Query Response


42. Blk 212B - 1st sty Part B Circled door is required. To
Refer to Dwg No: AR-114, does circled door exist and use Door Tag (DT/1C). Fire
what is the door code? Please clarify. rating for door to be 2 hours
with self-closing device.
200-21-04-4382
Amendment No. 5
Page 36 of 56

Tender Clarification No. 3 / Page 19 of 39

S/N Query Response


43. Blk 212B & 212C - 2nd sty Part 2 To use (FDT/2J) for doors to
Refer to Dwg No: AR-118_Rev A, door code stated as protected staircase. Fire
FDT 2H for Stair 1B however Tender Clarification No.1 rating for door to be ½ hour.
S/N 47 stated as FDT 2J for Stair 1B at Blk 212C 2nd Aforementioned doors to
storey Part 2. Door schedule AR-274_Rev A also stated come with vision panels for
FDT 2H for Staircase at 2nd storey. Please clarify. safety.
200-21-04-4382
Amendment No. 5
Page 37 of 56

Tender Clarification No. 3 / Page 20 of 39

S/N Query Response


44. Blk 212C - 3rd sty Part 2 To use Door Tag (FDT/1E)
Refer to Dwg No: AR-124, what is the exactly door code for Elect. Duct Riser Ducts.
for E and G&W riser? Please clarify. Fire rating for door to be 2
hours with self-closing
device.
To use Door Tag (FDT/1G)
for G&W Riser Ducts. Fire
rating for door to be 2 hours
with self-closing device.

45. Blk 212B & 212C - 3rd sty & 4th sty Part 2 Circled door is required at 3rd
Refer to Dwg No: AR-122, AR-124 & AR-128, does door storey for future
exist and what is the door code? Please clarify. maintenance. To use Door
Tag (DT/1C) for sanitary
stacks. Fire rating for door to
be 2 hours with self-closing
device.

46. Blk 212B - 4th sty Part 1 Circled Door is not required
Refer to Dwg No: AR-125, door code no stated. Please at 4th storey.
clarify.
200-21-04-4382
Amendment No. 5
Page 38 of 56

Tender Clarification No. 3 / Page 21 of 39

S/N Query Response


47. Blk 212D - 1st sty To use Door Tag (DT/2E).
Refer to Dwg No: AR-145, door code no stated. Please
clarify.

48. Blk 212D - 6-10th sty To use Door Tag (FDT/1K).


Refer to Dwg No: AR-149, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 39 of 56

Tender Clarification No. 3 / Page 22 of 39

S/N Query Response


49. Blk 213A - 1st sty To use Door Tag (FDT/1E).
Refer to Dwg No: AR-156, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.

50. Blk 213A - 1st sty To use Door Tag (DT/1C).


Refer to Dwg No: AR-156, please confirm actual door Fire rating for door to be 2
code. Please clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 40 of 56

Tender Clarification No. 3 / Page 23 of 39

S/N Query Response


51. Blk 213A - 3rd sty To use Door Tag (DT/1C).
Refer to Dwg No: AR-158, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.

52. Blk 213B - 1st sty To use Door Tag (DT/1H).


Refer to Dwg No: AR-167, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.

53. Blk 213B - 1st sty To use Door Tag (DT/1H).


Refer to Dwg No: AR-167, please confirm the actual door Fire rating for door to be 2
code. Or DT 1H? Please clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 41 of 56

Tender Clarification No. 3 / Page 24 of 39

S/N Query Response


54. Blk 213B - 1st sty To use Door Tag (DT/1C).
Refer to Dwg No: AR-167, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.

55. Blk 213C - 1st sty To use Door Tag (DT/1H).


Refer to Dwg No: AR-168, door code no stated. Please Fire rating for door to be 2
clarify. hours with self-closing
device.
To use Door Tag (DT/1C) for
door next to NS shelter. Fire
rating for door to be 2 hours
with self-closing device.
200-21-04-4382
Amendment No. 5
Page 42 of 56

Tender Clarification No. 3 / Page 25 of 39

S/N Query Response


56. Blk 213B - 2nd sty To use Door Tag (FDT/1E).
Refer to Dwg No: AR-169 Rev A, door code no stated. Fire rating for door to be 2
Please clarify. hours with self-closing
device.

57. Blk 213B & 213C - 3rd sty To use Door Tag (DT/1H).
Refer to Dwg No: AR-171 7 AR-172, door code no Fire rating for door to be 2
stated. Please clarify. hours with self-closing
device.
To use Door Tag (DT/1C) for
door next to NS shelter. Fire
rating for door to be 2 hours
with self-closing device.
200-21-04-4382
Amendment No. 5
Page 43 of 56

Tender Clarification No. 3 / Page 26 of 39

S/N Query Response


58. Blk 213B & 213C - 4th sty To use (FDT/2J) for doors to
Refer to Dwg No: AR-173, door code no stated. Please protected staircase. Fire
clarify. rating for door to be ½ hour.
Aforementioned doors to
come with vision panels for
safety.

59. Blk 214A - 2nd sty To ignore (FDT/1H)


Refer to Dwg No: AR-186 Rev A, this FDT 1H for what highlighted. Door is not
door? Please clarify. required at the area shown.
200-21-04-4382
Amendment No. 5
Page 44 of 56

Tender Clarification No. 3 / Page 27 of 39

S/N Query Response


60. Blk 214A, 214B, 214C & 215A - 5- sty To use (FDT/1G) based on
Refer to Dwg No: AR-191 and AR-192, different door 850 wide door. Fire rating for
code provided for same door type and same door door to be 2 hours with self-
location but different storey. Please clarify. closing device.
200-21-04-4382
Amendment No. 5
Page 45 of 56

Tender Clarification No. 3 / Page 28 of 39

S/N Query Response


61. Blk 215B - 1st sty Part 1 To use Door Tag (DT/1C).
Refer to Dwg No: AR-203, no door code provided. Fire rating for door to be 2
Please clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 46 of 56

Tender Clarification No. 3 / Page 29 of 39

S/N Query Response


62. Blk 215B - 3rd sty Part 1 To use Door Tag (DT/1C).
Refer to Dwg No: AR-206, no door code provided. Fire rating for door to be 2
Please clarify. hours with self-closing
device.
Doors are only required at
the stack ducts 1 storey
under habitable units for
future maintenance. Where
the immediate storey above
is a soft storey (non-
residential units), door to the
stack duct is not required.
200-21-04-4382
Amendment No. 5
Page 47 of 56

Tender Clarification No. 3 / Page 30 of 39

S/N Query Response


63. Blk 215B - 11-16th sty Part 1 To use Door Tag (FDT/1B).
Refer to Dwg No: AR-210, no door code provided. Fire rating for door to be 2
Please clarify. hours with self-closing
device.

64. Blk 215B - 5th sty Part 1 To use Door Tag (FDT/1H).
Refer to Dwg No: AR-228, no door code provided. Fire rating for door to be 2
Please clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 48 of 56

Tender Clarification No. 3 / Page 31 of 39

S/N Query Response


65. Blk 215C - 6-10th sty Part 2 To use (FDT/2J) for doors to
Refer to Dwg No: AR-231, no door code provided. protected staircase. Fire
Please clarify. rating for door to be ½ hour.
Aforementioned doors to
come with vision panels for
safety.

66. Utility Centre @ Blk 212C Door Schedule for Door Type
Refer to Dwg No: AR-391, door code D1 and D1A is not (D/1) / (D/1A) to refer to
provided in door schedule. Please clarify. architectural detail drawings
(Section A6, Drawing Nos. 38
& 40).
200-21-04-4382
Amendment No. 5
Page 49 of 56

Tender Clarification No. 3 / Page 32 of 39

S/N Query Response


67. Utility Centre @ Blk 215C Door Schedule for Door Type
Refer to Dwg No: AR-391, door code D1 and D1A is not (D/1) / (D/1A) to refer to
provided in door schedule. Please clarify. architectural detail drawings
(Section A6, Drawing Nos. 38
& 40).
200-21-04-4382
Amendment No. 5
Page 50 of 56

Tender Clarification No. 3 / Page 33 of 39

S/N Query Response


68. EPS Room @ Blk 215C To use Door Tag (AD/10) for
Refer to Dwg No: AR-392, no door code provided for the EPS room. Refer to drawing
circled item. Door schedule AR-482 Rev 1 stated as AD No. AR 482 for associated
10 for EPS Room, is it apply to this three EPS room? door schedule.
Please clarify.
200-21-04-4382
Amendment No. 5
Page 51 of 56

Tender Clarification No. 3 / Page 34 of 39

S/N Query Response


69. 212 MSCP Deck 2 - Part 2 Door is not required at the
Refer to Dwg No: AR-306, no door code provided for the highlighted area. Refer to
circled item. Please clarify. Drawing No. AR 306 for
updated drawings of the area
shown.

70. 212 MSCP Deck 1 - Part 1 Door exist. Please use


Refer to Dwg No: AR-301 REV 1, door code FDT 1D (FDT/1D) for Staircase D.
stated for E duct however staircase details AR-316 REV Fire rating for door to be ½
2 no stated such door. Please clarify does the door exist. hours with self-closing
device.
Provision of Elect Riser
Ducts varies for different type
of staircases.
200-21-04-4382
Amendment No. 5
Page 52 of 56

Tender Clarification No. 3 / Page 35 of 39

S/N Query Response


71. 212 MSCP Deck 1 - Part 3 Door exist. Please use
Refer to Dwg No: AR-301 REV 1, door stated for E duct (FDT/1D) for Staircase D.
and without door code, however staircase details AR-316 Fire rating for door to be ½
REV 2 no stated hours with self-closing
device.
Provision of Elect Riser
Ducts varies for different type
of staircases.
200-21-04-4382
Amendment No. 5
Page 53 of 56

Tender Clarification No. 3 / Page 36 of 39

S/N Query Response


72. 212 MSCP E-Deck - Part 2 Door not required at Car Park
Refer to Dwg No: AR-310, no door stated for Staircase roof. Doors to exit staircases
M, however staircase details AR-319 REV 1 stated there at Deck 1 and Deck 2 is
is one door CFD 10. Please clarify does the door exist. required, in which case the
fire rating for these doors to
be 2 hours with self-closing
device and vision panel.
200-21-04-4382
Amendment No. 5
Page 54 of 56

Tender Clarification No. 3 / Page 37 of 39

S/N Query Response


73. 213 MSCP - Deck 1 Door Schedule for toilet is
Refer to Dwg No: AR-341 Rev 1, no door code stated for Door Type (D/1).
the circled item. Please clarify. Door Schedule for Store is
Door Type (D/1A).
To use Door Tag (AD/15) for
Consumer Switch Room.
Refer to Drawing No. AR 482
in Amendment No.3.

SPF Room Door Type to


refer to architectural detail
drawings (Section A6,
Drawing No.45). Associated
Door Tag is (DT/1G), refer to
Drawing No. AR 274. Fire
rating for door to be 2 hours
with self-closing device.
Drawings will be updated in
Amendment No.6.

Refer to Drawing Nos. (AR


341 - AR 343) in Amendment
No. 4.
200-21-04-4382
Amendment No. 5
Page 55 of 56

Tender Clarification No. 3 / Page 38 of 39

S/N Query Response


74. 213 MSCP - Deck 2 Refer to Drawing Nos. (AR
Refer to Dwg No: AR-342 Rev 1, no door code stated for 341 - AR 343) in Amendment
the circled item. Please clarify. No. 4. Refer to Drawings
Nos. (AR 481-AR 482) for
associated door schedule in
Amendment No.4.

To use door tag (FDT/1H) for


FHR door. Fire rating for door
to be 2 hours with self-
closing device.
200-21-04-4382
Amendment No. 5
Page 56 of 56

Tender Clarification No. 3 / Page 39 of 39

S/N Query Response


75. Door Schedule Highlighted Door Tag is
Refer to Dwg No: AR-274 Rev A, is it DT 1C instead of (DT/1C).
DF 1C? Please clarify.

76. Blk 212A - 16th sty Highlighted door to be


Refer to Dwg No: AR-106, Tender Clarification No.1 S/N (FT/2A). Fire rated door not
53 stated as FDT 2J, please kindly confirm is FDT 2J or required for top-most storey
DT 2A? Please clarify. within staircase.