Amendment No. 5
Page 18 of 56
2. Refer to TD-272, kindly provide us keyplan to be located Refer to Drawing No. (AR
the Integrated Grill panel on low wall (Facing the Barley 958) in Amendment No.4.
Road & Bidadari Part Drive Side). Part print of TD- 272:
200-21-04-4382
Amendment No. 5
Page 19 of 56
4. Refer to TD-100 Series, Kindly provide detail/keyplan for Refer to Drawing Nos. (AR
Aluminium Tresllis and Composite panels on each 641 – AR 646) in “Original
residential blocks. Part print of TD-188 & TD-223: Tender Drawing Set”
and “Amendment No. 4”.
200-21-04-4382
Amendment No. 5
Page 20 of 56
6. Refer to TD-701, kindly issue as detail dwg and also please Refer to architectural detail
reflect on plan as provided in legend: a) PDS-Precinct drawings (Section A7,
Drawing No. 17-42).
Directional Signboard b.)D- Precinct Directional Signboard
c) E-Signboard for block entrance f) illuminated directional
Sign plate. Part print of TD-701:
7. There is some discrepancies on the PL level Architectural Please highlight the area
Drawings and C&S Drawings. Kindly confirm the PL. [ queried on the
please refer to Drawing No.: HB-D1619-AR-051; HB-D1619- discrepancies.
CS-021 & HB-D1619-CS-022 ] To follow levels shown in
architectural drawings for
FFL in event that FFL and
SFL is the same.
200-21-04-4382
Amendment No. 5
Page 21 of 56
9. Please confirm what type of door we will use for bedroom To use UPVC doors to
area. bedroom instead of semi-
a. Provisional Quantity of 1,745 Nos. UPVC doors to solid timber doors.
bedroom including approved ironmongeries,
accessories and painting as specified, provision of all
labour, materials, mobilization and demobilization of
equipment and tools and all related works.
200-21-04-4382
Amendment No. 5
Page 22 of 56
A-051:
11. Please provide elevation shows the accent tiles Accent Tiles are not required
to Kitchen and Bathroom.
Requirement for Accent Tiles
amended in Amendment
No.4.
200-21-04-4382
Amendment No. 5
Page 23 of 56
13. As for metal roof, please provide the details roof drawing Refer to AR-364 that will be
showing the insulations. sent out in Amendment No.
5.
200-21-04-4382
Amendment No. 5
Page 24 of 56
15. Please provide detail of DU aircon Ledge as not provided Refer to architectural detail
on issued drawing. drawings (Section AWS02 –
Drawing Nos.7-9).
16. Refer to Std Supp Spect S73, please verify if accent tiles Accent Tiles are not
are required to Kitchen and Bathroom for residential blocks. required to Kitchen and
If yes, please provide us detail elevation. Below part Part Bathroom. Requirement
print of BS-S73: for Accent Tiles removed
in Amendment No.4.
200-21-04-4382
Amendment No. 5
Page 25 of 56
18. Refer to Form of Tender, please issue us detail of Built-in Refer to architectural detail
Kitchen cabinet and wardrobe for residential blocks. Below drawings (Section A7 –
part Part print of FOT ANNEXX B-22 of 30: Drawing Nos. 70-75).
200-21-04-4382
Amendment No. 5
Page 26 of 56
20. Refer to TD-341, Please verify the Door tag & detail service SPF Room Door Type to
room and ducts from Deck 1A/1B to 3rd sty the ff part print refer to architectural detail
of TD-314: drawings (Section A6,
Drawing No.45). Associated
Door Tag is (DT/1G), refer to
Drawing No. AR 274.
22. Kindly advise is it irrgation system needed in Hillock Irrigation system is not
Park. required for the Hillock Park
23. Kindly advise the water sources locations. Water source is not required
for the Hillock Park
24. Please kindly clarify that there is any light for Park area, For lighting plan of the Park,
If have, please kindly provide completed dwgs with please refer to EE028 and
light and cutsheet for Park. LA1820 & LA1821 (issued in
Amendment No. 5). For
details of the lighting, please
refer to LA1850 & SS79.33 –
Bollard Lighting
26. I went through the tender documents, however, I could There is no rainwater
not locate the information on the rain water harvesting harvesting system in the
system in the tender documents. Could you please M&E design.
provide me information like capacity, location of the rain
water harvesting system?
27. Please provide us completed dwgs with light and cutsheet For lighting plan of the Park,
for the Park area. please refer to LA1820 &
1821 in Amendment No. 5.
For details of the lighting,
please refer to LA1850 &
SS79.33 – Bollard Lighting
28. Please kindly issue us the Fire Alarm Schematic drawings Fire Alarm Schematic
which is not included in drawings can be found at
drawings (0 to A4). Dwg ME561 to ME564
200-21-04-4382
Amendment No. 5
Page 28 of 56
32. In FOT breakdown, Option-A (Conventional Carpark) and Please refer to Supplementary
Option-B (Future Ready Carpark), pls advise what is the Specifications Clause 73.51.
difference of these two options. For EPS system, please There is no difference for
provide to us schematic diagram, plan drawings and electrical installation for Option
specification. A & Option B. Please refer to
EE026, EE223, EE317 for
EPS system and single line
diagram.
33. Refer to as per attached Dwg No. HB-D1619-ME-131, 4rm & 5rm at 4th storey are
electrical schematic diagram for Blk-212C mentioned omitted. EE131 to be updated
4RM & 5RM rooms at 4th storey. But, these rooms are
not mentioned in plan (refer to as per attached Dwg
No.HB-D1619-ME-121). Please advise.
34. In regards with 8 numbers of shops at block 212, Please refer to EE266 and
please kindly know the shops's serial number to EE268 for the shop location
calculate the cable pricing as the incoming cable size is with different MCCB and
not same for these shops. incoming cable size
200-21-04-4382
Amendment No. 5
Page 29 of 56
45. Blk 212B & 212C - 3rd sty & 4th sty Part 2 Circled door is required at 3rd
Refer to Dwg No: AR-122, AR-124 & AR-128, does door storey for future
exist and what is the door code? Please clarify. maintenance. To use Door
Tag (DT/1C) for sanitary
stacks. Fire rating for door to
be 2 hours with self-closing
device.
46. Blk 212B - 4th sty Part 1 Circled Door is not required
Refer to Dwg No: AR-125, door code no stated. Please at 4th storey.
clarify.
200-21-04-4382
Amendment No. 5
Page 38 of 56
57. Blk 213B & 213C - 3rd sty To use Door Tag (DT/1H).
Refer to Dwg No: AR-171 7 AR-172, door code no Fire rating for door to be 2
stated. Please clarify. hours with self-closing
device.
To use Door Tag (DT/1C) for
door next to NS shelter. Fire
rating for door to be 2 hours
with self-closing device.
200-21-04-4382
Amendment No. 5
Page 43 of 56
64. Blk 215B - 5th sty Part 1 To use Door Tag (FDT/1H).
Refer to Dwg No: AR-228, no door code provided. Fire rating for door to be 2
Please clarify. hours with self-closing
device.
200-21-04-4382
Amendment No. 5
Page 48 of 56
66. Utility Centre @ Blk 212C Door Schedule for Door Type
Refer to Dwg No: AR-391, door code D1 and D1A is not (D/1) / (D/1A) to refer to
provided in door schedule. Please clarify. architectural detail drawings
(Section A6, Drawing Nos. 38
& 40).
200-21-04-4382
Amendment No. 5
Page 49 of 56