The present manual is intended for getting to know lift unit ver. 7.2 of Lift Monitoring and
Diagnostics System, its characteristics and rules for safe operation (use, transportation,
storage and technical maintenance).
Installation, operation, technical maintenance, repair works, modification, re-mounting of LMDS
must be performed by service contractor that has sufficient technical means and qualified
personnel having undergone training at LMDS manufacturer’s site.
The present manual is to be used with lift units ver. 7.2 LNGS.465213.270-10,
LNGS.465213.270-11, LNGS.465213.270-14 … LNGS.465213.270-78.
During operation of lift units of LMDS it is required to follow recommendations of the
present manual as well of other documents provided by the manufacturer of LMDS.
In this manual, the following abbreviations and indications are used:
EEPROM: nonvolatile memory microchip;
RSA: relay station adaptor;
CDs: car doors;
LDs: liftshaft doors;
SC: short circuit;
LU: lift unit version 7.2;
ER: engine room;
PC: personal computer;
LCR: lift control room;
TM: technical maintenance;
SD: safety device;
LSCU: lift speed control unit.
1. DESCRIPTION AND FUNCTIONING OF LIFT UNIT
1.1. DESIGNATION
1.1.1. Lift units LNGS.465213.270-10, LNGS.465213.270-11, LNGS.465213.270-14 …
LNGS.465213.270-78 are part of Lift Monitoring & Diagnostic System.
1.1.2. Types of lift units versions are shown in Table 1.
Table 1. LU Types/Options
Name Short name Description
Lift unit ver. 7.2 - Р LU 7.2 - Р LNGS.465213.270-10
Lift unit ver. 7.2 «OTIS» LU 7.2 «OTIS» LNGS.465213.270-11
Lift unit ver. 7.2 «SHULK-17» LU 7.2 «SHULK-17» LNGS.465213.270-12
Lift unit ver. 7.2 «SHULK-32» LU 7.2 «SHULK-32» LNGS.465213.270-14
Lift unit ver. 7.2 «UKL/UL» LU 7.2 «UKL/UL» LNGS.465213.270-15
Lift unit ver. 7.2 «NKU-MPPL» LU 7.2 «NKU-MPPL» LNGS.465213.270-16
Lift unit ver. 7.2 «UUL» LU 7.2 «UUL» LNGS.465213.270-17
Lift unit ver. 7.2 «SODIMAS» LU 7.2 «SODIMAS» LNGS.465213.270-18
Lift unit ver. 7.2 «SUL» LU 7.2 «SUL» LNGS.465213.270-19
Lift unit ver. 7.2 «LG» LU 7.2 «LG» LNGS.465213.270-20
Lift unit ver. 7.2 «ESK» LU 7.2 «ESK» LNGS.465213.270-21
Lift unit ver. 7.2 «AXEL» LU 7.2 «AXEL» LNGS.465213.270-22
4
LNGS.465213.270-10 RE
Lift unit ver. 7.2 «ELEX» LU 7.2 «ELEX» LNGS.465213.270-23
Lift unit ver. 7.2 «THYSSEN» LU 7.2 «THYSSEN» LNGS.465213.270-24
Lift unit ver. 7.2 «SPUL» LU 7.2 «SPUL» LNGS.465213.270-25
Lift unit ver. 7.2 «OLYMPUS» LU 7.2 «OLYMPUS» LNGS.465213.270-26
Lift unit ver. 7.2 «KLEEMANN» LU 7.2 «KLEEMANN» LNGS.465213.270-27
Lift unit ver. 7.2 «DOPPLER» LU 7.2 «DOPPLER» LNGS.465213.270-28
Lift unit ver. 7.2 «BLT» LU 7.2 «BLT» LNGS.465213.270-29
Lift unit ver. 7.2 «EXPRESS» LU 7.2 «EXPRESS» LNGS.465213.270-30
LU 7.2 «THYSSEN
Lift unit ver. 7.2 «THYSSEN TAC50» LNGS.465213.270-31
TAC50»
Lift unit ver. 7.2 «SCHINDLER» LU 7.2 «SCHINDLER» LNGS.465213.270-32
Lift unit ver. 7.2 «BG-15» LU 7.2 «BG-15» LNGS.465213.270-33
Lift unit ver. 7.2 «ORONA» LU 7.2 «ORONA» LNGS.465213.270-34
LU 7.2 «NKU-MPPL
Lift unit ver. 7.2 «NKU-MPPL BPSH-2» LNGS.465213.270-35
BPSH2»
Lift unit ver. 7.2 «ARKEL» LU 7.2 «ARKEL» LNGS.465213.270-36
Lift unit ver. 7.2 «SODIMAS QI» LU 7.2 «SODIMAS QI» LNGS.465213.270-37
Lift unit ver. 7.2 «ORONA ARCA1» LU 7.2 «ORONA ARCA1» LNGS.465213.270-39
Lift unit ver. 7.2 «DMG» LU 7.2 «DMG» LNGS.465213.270-40
Lift unit ver. 7.2 «MIK-EL» LU 7.2 «MIK-EL» LNGS.465213.270-41
Lift unit ver. 7.2 «KONE» LU 7.2 «KONE» LNGS.465213.270-42
Lift unit ver. 7.2 «VEGA» LU 7.2 «VEGA» LNGS.465213.270-43
Lift unit ver. 7.2 «HYUNDAI» LU 7.2 «HYUNDAI» LNGS.465213.270-44
Lift unit ver. 7.2 «NICE» LU 7.2 «NICE» LNGS.465213.270-45
Lift unit ver. 7.2 «S9» LU 7.2 «S9» LNGS.465213.270-46
Lift unit ver. 7.2 «AC-01» LU 7.2 «AC-01» LNGS.465213.270-47
Lift unit ver. 7.2 «iAStar» LU 7.2 «iAStar» LNGS.465213.270-48
Lift unit ver. 7.2 «FST2» LU 7.2 «FST2» LNGS.465213.270-49
Lift unit ver. 7.2 «CANNY» LU 7.2 «CANNY» LNGS.465213.270-50
Lift unit ver. 7.2 «SILVER» LU 7.2 «SILVER» LNGS.465213.270-51
Lift unit ver. 7.2 «DOPPLER ACT» LU 7.2 «DOPPLER ACT» LNGS.465213.270-52
Lift unit ver. 7.2 «INV» LU 7.2 «INV» LNGS.465213.270-53
Lift unit ver. 7.2 «E9» LU 7.2 «E9» LNGS.465213.270-54
Lift unit ver. 7.2 «ECLIPSE» LU 7.2 «ECLIPSE» LNGS.465213.270-55
Lift unit ver. 7.2 «VASSLER» LU 7.2 «VASSLER» LNGS.465213.270-56
Lift unit ver. 7.2 «TMS600» LU 7.2 «TMS600» LNGS.465213.270-57
Lift unit ver. 7.2 «BETACONTROL» LU 7.2 «BETACONTROL» LNGS.465213.270-58
Lift unit ver. 7.2 «CARLOS SILVA» LU 7.2 «CARLOS SILVA» LNGS.465213.270-59
Lift unit ver. 7.2 «ShK6000» LU 7.2 «ShK6000» LNGS.465213.270-60
5
LNGS.465213.270-10 RE
Lift unit ver. 7.2 «TKL» LU 7.2 «TKL» LNGS.465213.270-61
Lift unit ver. 7.2 «SOYUZ» LU 7.2 «SOYUZ» LNGS.465213.270-62
Lift unit ver. 7.2 «LLC» LU 7.2 «LLC» LNGS.465213.270-63
Lift unit ver. 7.2 «SHL-R» LU 7.2 «SHL-R» LNGS.465213.270-64
Lift unit ver. 7.2 «FT9x0» LU 7.2 «FT9x0» LNGS.465213.270-65
Lift unit ver. 7.2 «VEK» LU 7.2 «VEK» LNGS.465213.270-66
Lift unit ver. 7.2 «KOLLMORGEN» LU 7.2 «KOLLMORGEN» LNGS.465213.270-67
Lift unit ver. 7.2 «THYSSEN CMC» LU 7.2 «THYSSEN CMC» LNGS.465213.270-68
Lift unit ver. 7.2 «SECURLIFT» LU 7.2 «SECURLIFT» LNGS.465213.270-69
Lift unit ver. 7.2 «THYSSEN MCI» LU 7.2 «THYSSEN MCI» LNGS.465213.270-70
Lift unit ver. 7.2 «WIPO» LU 7.2 «WIPO» LNGS.465213.270-71
Lift unit ver. 7.2 «KLST» LU 7.2 «KLST» LNGS.465213.270-72
Lift unit ver. 7.2 «ELCO MICRO» LU 7.2 «ELCO MICRO» LNGS.465213.270-73
Lift unit ver. 7.2 «KOYO» LU 7.2 «KOYO» LNGS.465213.270-74
Lift unit ver. 7.2 «BL6» LU 7.2 «BL6» LNGS.465213.270-75
Lift unit ver. 7.2 «WEBER» LU 7.2 «WEBER» LNGS.465213.270-76
Lift unit ver. 7.2 «GTE» LU 7.2 «GTE» LNGS.465213.270-77
Lift unit ver. 7.2 «DAESUNG» LU 7.2 «DAESUNG» LNGS.465213.270-78
1.1.3. LU 7.2 is to be used with serially produced lifts:
- «P»: together with relay station adaptors for lifts with automatic doors drive having no
serial port for dispatching;
- «OTIS»: with OTIS lifts with LCB-I (MCS-310, 320), LCB-II (MCS-220), LB-II (MCS-300),
RCB-II (MCS-311, 321, 411, 413, 421), TCB\HCB (OTIS2000, GeN2), TCBC (GeN2 Can),
GECB-II (MCS-222) control systems, escalators and travelators NCE, NCT, NPE (ECB, ECBII);
- «SHULK-17»: with SHULK lifts having PKL-17 lift control board;
- «SHULK-32»: with SHULK, SHULM, SHULR lifts having PKL-32 control board;
- «UKL/UL»: with lifts having UKL (MPU control board), UL (сPU-2, PU-3 control boards)
and UEL (CPU central controller board) control boards;
- «NKU-MPPL»: with NKU-MPPL lifts with BPSH-1 controller (equipped with KDS-1, KDS-2
boards);
- «UUL»: with RSUL (distributed control system) and UUL control unit;
- «SODIMAS»: with SODIMAS lifts having NG12 control board;
- «SUL»: with SUL1 lifts manufactured by OAO “MEL” (JSC);
- «LG»: with LG lifts having DI-1, DI-2 and DSS control stations;
- «ESK»: with escalators (except OTIS);
- «AXEL»: with AXEL lifts having ELE2000 control station (MRV1 controller);
- «ELEX»: with ELEX lifts (LEXQ3 controller);
- «THYSSEN»: with THYSSEN lifts (TCI, TCM, E-COR controllers);
- «SPUL»: with SPUL lifts (manufactured by ZAO “ETLIЗАО”);
- «OLYMPUS»: with OLYMPUS lifts;
- «KLEEMANN»: with KLEEMANN lifts (LiSA controller);
- «DOPPLER»: with DOPPLER lifts having E-Type control station (manufactured by SEC);
- «BLT»: with BLT lifts (MPK708 controller);
- «EXPRESS»: with EXPRESS lifts having STEP control station (F5021 and SM-01-DP/C
controllers);
- «THYSSEN TAC50»: with THYSSEN lifts (TAC-50 16Bit, 32Bit control board);
6
LNGS.465213.270-10 RE
- «SCHINDLER»: with SCHINDLER lifts (BIONIC 5, MICONIC BX, MICONIC MX control
stations);
- «BG-15»: with lifts having BG-15 control boards;
- «ORONA»: with ORONA lifts having ARCA II control board;
- «NKU-MPPL BPSH-2»: with NKU-MPPL lifts having BPSH-2, LIRA control boards;
- «ARKEL»: with lifts having ARL-300, ARL-500, ARCODE controllers;
- «SODIMAS QI»: with lifts SODIMAS having QI control board;
- «ORONA ARCA1»: with ORONA lifts having ARCA 1 control board;
- «DMG»: with «DMG» lifts;
- «MIK-EL»: with MIK-EL lifts having MIKRONIK S-HI controllers;
- «KONE»: with KONE lifts having LCECPUnc, LCECPU40 and LCECPU561 control boards;
- «VEGA»: with VEGA, Liftex lifts having VEG2000 control board;
- «HYUNDAI»: with HYUNDAI lifts having STVF7 controller;
- «NICE»: with lifts having NICE3000 controller;
- «S9»: with lifts having S9 controller;
- «AC-01»: with lifts having AC-01 controller;
- «iAStar»: with lifts having iAStar, AS380 controllers;
- «FST2»: with lifts having FST2 controller;
- «CANNY»: with lifts having FR2000-STB-V9 and BL2000 controllers;
- «SILVER»: with lifts having NETIS controller;
- «DOPPLER ACT»: with lifts having ACT, ACH (AYBEY) controllers;
- «INV»: with platforms for handicapped passengers;
- «E9»: with UNGERT lifts having E9 controller;
- «ECLIPSE»: with lifts having SICON-4000 controller;
- «VASSLER»: with lifts having VASSLER controller;
- «TMS600»: with KONE lifts having TMS600 controller;
- «BETACONTROL»: with lifts having KKWEBMON controller;
- «CARLOS SILVA»: with lifts having HIDRA controller;
- «ShK6000»: with lifts having ShK6000 control system;
- «TKL»: with lifts having TKL controller;
- «SOYUZ»: with lifts having SOYUZ control station;
- «LLC»: with KLEEMANN lifts having LLC 100 controller;
- «SHL-R»: with lifts having SHL-R (manufactured by ZAO SP «Pod’yom») controller;
- «FT9x0»: with THYSSEN escalators having FT 9х0 controller;
- «VEK»: with VEK lifts having SUL2010 (manufactured by OOP TsNTU «VEK») controllers;
- «KOLLMORGEN»: with lifts having MPK400 controller;
- «THYSSEN CMC»: with THYSSEN lifts having СМС3, СМС4, СМС4+ controllers;
- «SECURLIFT»: with lifts having SECURLIFT controller;
- «THYSSEN MCI»: with THYSSEN lifts having МСI controller;
- «WIPO»: with lifts having WP-CAN 3000 controller;
- «KLST»: with VESTNER lifts having KLST controller;
- «ELCO MICRO»: with lifts having ELCO MICRO controller;
- «KOYO»: with KOYO lifts having KOYO controller;
- «BL6»: with SANEY lifts having BL6 controller;
- «WEBER»: with WEBER lifts having WECON controller;
- «DAESUNG»: with HANDOK, YUNJIN and other lifts having DAESUNG KJ-D100
controller.
1.1.4. Working parameters of lift unit:
- Ambient air temperature: +1 to +35°C;
- Relative humidity (upper limit) 80% at +25°C;
- Atmospheric pressure (upper limit) 106,7kPa (800 mm Hg);
- Power supply voltage 220V ±10%, frequency 50±1 Hz.
7
LNGS.465213.270-10 RE
1.2. TECHNICAL CHARACTERISTICS
1.2.1. Technical data
1.2.1.1. LU power supply: external stabilized DC power supply +9…24V. Power
consumption: not more than 4 W.
1.2.1.2. LU duty cycle: round-the-clock, continuous.
1.2.1.3. LU dimensions: not more than 150х110х31 mm.
1.2.1.4. LU weight: not more than 1.2 kg.
1.2.1.5. Control actuator module nominal voltage output: 220V.
1.2.1.6. Control actuator module nominal current output, not more than 1A.
1.2.1.7. Type of ABL input: potential.
1.2.1.8. Nominal voltage at «ABL» input: 24V.
1.2.1.9. Types of inputs/outputs, their designation, technical characteristics and possible
application are shown in 2.
Table 2
Designation, technical characteristics and possible application USER1…4 and OUT1
Input Output Name Technical characteristics Possible application
Input - «dry contact»,
Input/Output
USER1 USER1 Output - voltage +5V, User defined
USER1
maximum current 200 mA.
Input - «dry contact»,
Input/Output
USER2 USER2 Output - voltage +5V, User defined
USER2
maximum current 200 mA.
Input - «dry contact»,
Input/Output
USER3 USER3 Output - voltage +5V, User defined
USER3
maximum current 200 mA.
Input - «dry contact»,
Input/Output User defined, input of LSCU sensor
USER4 USER4 Output - voltage +5V,
USER4 pulses
maximum current 200 mA.
Dispatcher command control, voice
Output - voltage +5V, alert control, emergency light
- OUT1 Output OUT1
maximum current 200 mA. control, power supply to LSCU
sensor.
Types of inputs/outputs of lift unit ver. 7.2, their designation, technical characteristics and
possible application are shown in Addendum B.
Variables for LNGS.465213.270-10 connection
1.2.1.10. Connection to relay lifts having no serial ports for dispatching: via relay station
adaptor LNGS.465213.061-03.
Variables for LNGS.465213.270-21 connection
1.2.1.11. Connection to escalators having no serial port for dispatching: via relay station
adaptor.
Variables for LNGS.465213.270-53 connection
1.2.1.12. Connection to lifting platforms for disabled and handicapped passengers (platforms
to be connected to dispatch control units and have no serial port for dispatching): via dry
contacts.
Variables for LNGS.465213.270-11, LNGS.465213.270-14 … LNGS.465213.270-20,
LNGS.465213.270-22 … LNGS.465213.270-78 connection
1.2.1.13. Type of connection to microprocessor SUL: serial link.
1.2.1.14. Data exchange interface LU 7.2 using serial link:
8
LNGS.465213.270-10 RE
- «OTIS»: RS422;
- «SHULK-32», «UUL», «SUL», «ELEX», «SPUL», «OLYMPUS», «NKU-MPPL BPSH-2»,
«HYUNDAI», «ECLIPSE», «ShK6000», «TKL», «VEK», «GTE»: RS485;
- «UKL/UL», «NKU-MPPL», «CARLOS SILVA», «SHL-R»: current output;
- «LG», «AXEL», «THYSSEN», «KLEEMANN», «DOPPLER», «EXPRESS», «THYSSEN
TAC50», «SCHINDLER», «BG-15», «SODIMAS QI», «ORONA ARCA1», «KONE», «VEGA»,
«NICE», «S9», , «iAStar», «FST2», «CANNY», «VASSLER», «BETACONTROL»,
«KOLLMORGEN», «THYSSEN CMC», «THYSSEN MCI», «BL6», «WEBER»: RS232;
- «SODIMAS», «DMG», «E9», «ELCO MICRO», «AC-01», «SOYUZ»: RS232-TTL;
- «BLT», «ORONA», «ARKEL», «MIK-EL», «SILVER», «DOPPLER ACT», «LLC», «FT9x0»,
«SECURLIFT», «WIPO», «KLST», «KOYO», «DAESUNG»: CAN bus.
1.2.2. Lift unit functions
1.2.2.1. Lift unit as part of dispatcher set equipment enables control over functioning of
lift and provides:
- two-way voice communication between dispatching room and lift car, car roof, engine
room, lift pit and floors; it also provides audio signaling when calling dispatcher;
- warning of liftshaft doors opening with no lift car on floor;
- warning of engine and service rooms doors opening and of control carets doors opening
(when located outside of engine room, in case of machine room-less lifts);
- warning of lift safety circuit activation;
- identification of incoming warnings (which lift and what signal);
- exchange of operating regime status with lift control station;
- fault-finding in lift operation;
- detection of unauthorized intrusion into engine (service) room;
- lift shutdown by command from dispatcher board (optional);
- connection of communication devices located in lift car, on car roof, in engine room, lift
pit and on floors to audio tract of Lift Monitoring & Diagnostic Complex;
- automatic testing of communication with lift car (optional);
- audio announcement of floor number;
- audio accompaniment (when using microSD card);
- remote renewal of voice announcements;
- microprogram updating through remote reprogramming of microcontroller.
1.2.3. Regimes/statuses generated by LU 7.2
1.2.3.1. Based on information received from lift control system, lift unit will configure the
following standard statuses:
- no voltage in control circuit (by presence of connection with SUL);
1
- STOP button jammed in lift car (CANCEL button pressed) ;
2
- SC of safety circuit ;
- safety circuit disconnection;
1
- lift car door open ;
- multiple reverse of doors;
- doors drive failure;
- dispatcher call;
- unauthorized movement of lift car;
- main drive failure by LSCU;
3
- liftshaft intrusion ;
- emergency/safety lock;
- intrusion into engine room;
- engine room open;
- technical maintenance;
- car has not arrived to floor;
9
LNGS.465213.270-10 RE
1
- CM sensor failure ;
2
- SD sensor failure ;
2
- SD failure ;
- no communication with SUL;
- LU failure;
- Actuator or optosymistor failure (optional);
- Status of USER1;
- Status of USER2;
- Status of USER3;
- Status of USER4;
- LU backup power supply;
2
- AC voltage in safety circuit .
Notes: 1. Not generated for LU LNGS.465213.270-10. 2. Status generated for LU LNGS.465213.270-10 only.
3. When lift has available normally open contacts for LDS switches or information available via serial link with
lift control station. 4. List of standard statuses can be amended for lifts of foreign make.
1.2.3.2. Lift units LNGS.465213.270-11, LNGS.465213.270-14 … LNGS.465213.270-20,
LNGS.465213.270-22 … LNGS.465213.270-74 allows formation of additional notifications on
operation of SUL received from lift via serial link.
1.3. SET OF DELIVERY
1.3.1. Lift unit complete set of delivery depending on design version is given in Addendum
B.
1.4. CONFIGURATION OF LIFT UNIT
1.4.1. On top cover of LU 7.2 the following output is located (see Figure 1):
- "Mini USB" for connection with PC and configuring of LU parameters.
ATTENTION!
When LU is connected to PV via USB-cable, CAN bus operation is
terminated
10
LNGS.465213.270-10 RE
LED 1
Loundspeaker
LED 2
LED 3
Type of LU
Mini-USB
Mike 1 2 3
"Mode" LED
"CALL" button
"Pit" button
"Car" button
"Reset" button
1 2 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11
EXT12V
+EPWR
-EPWR
USER1
USER2
USER3
USER4
CAN-G
CAN-H
CAN-P
CAN-L
OUT1
MPR
GND
GND
GND
ABL
Light
Name Status Designation
color
Flashing
Interface board not installed or memory chip
"1" 5 times per green
fault
sec.
11
LNGS.465213.270-10 RE
Flashing
Interface board installed but no active
1 time per green
microprogram in memory chip
sec.
on/lit green Interface board installed; microprogram is used
Failure of quartz resonator; lift unit operating on
on/lit red
backup timing source
Flashing
1 time per red Ethernet cable not connected
sec.
Flashing
DHCP or PPPoE connection is being
5 times per red
established
sec.
Receipt of data via Ethernet, CAN bus or Wi-
on/lit green
"2" Fi
on/lit red Data transfer via Ethernet, CAN bus or Wi-Fi
‘Call’ status registered (calling dispatcher on
on/lit green
interphone)
Flashing
Ethernet cable connected, no network
5 times per green
settings. LU configuring required.
sec.
"3"
not on/lit - Interphone switched off.
Interphone communication with engine room
on/lit red
switched on. Direction: lift to dispatcher.
Interphone communication with engine room
flashing red
switched on. Direction: dispatcher to lift.
Series of
red Indication of cause for lift power off.
flashes
Service key inserted or service device
"Failure" flashing red
connected.
No exchange via serial link with lift control
on/lit red
station or relay station adaptor.
Command ‘On’ sent to electromagnetic
on/lit
actuator.
"Lift On " red
Command ‘Off’ sent to electromagnetic
not on/lit
actuator.
No exchange with intercom unit via CAN
not on/lit
bus (or Wi-Fi)
Local communication link established with
flashing
"Car" blue car.
Exchange with intercom unit established
on/lit via CAN bus (or Wi-Fi) and local communication
link terminated.
"Lift pit" not on/lit blue No exchange with intercom unit via CAN
12
LNGS.465213.270-10 RE
bus (or Wi-Fi)
Local communication link established with lift
flashing
pit.
Exchange with intercom unit established
on/lit via CAN bus (or Wi-Fi) and local communication
link terminated.
on/lit ‘Call’ from engine room registered
"Call" green Interphone communication switched on
flashing
between engine room and dispatcher.
not on/lit Wi-Fi switched off.
"Wi-Fi" flashing -
Wi-Fi connection parameters not configured.
continuously
Overdischarge of battery with ~220V power
«Reset» on/lit
supply present
For design version «- P» (LNGS.465213.270-10)
Liftshaft doors closed, 110V AC voltage
on/lit green present at relay station adaptor checkpoint
present.
"Operation"
not on/lit One or more wings of liftshaft doors open.
110V AC voltage present at relay station
flashing green
adaptor checkpoint present.
For all other design versions (beside «- P»)
on/lit green LU power supply from 220V AC mains.
"Operation"
flashing green Power supply from backup battery.
Description
No. of jack Marking Designation
of jacks
DC IN 1 DC IN
Lift unit power supply +9…24V
(J2) 2 GND
XP2 1-9 - Depending in lift unit design version
U2 1-8 - Per Ethernet standard
1 -EPWR Common for actuator control module
XP3
2 +EPWR Actuator control module signal
13
LNGS.465213.270-10 RE
1 CAN-P Power output +9…24V
2 CAN-L CAN Low
XP5
3 CAN-H CAN High
4 CAN-G Common
1 EXT12V Battery connection
2 MPR Engine room security sensor connection
3 GND Common
4 ABL ‘Safety lock’ input
5 GND Common
XP4 6 USER1 «USER1» Input/Output
7 USER2 «USER2» Input/Output
8 USER3 «USER3» Input/Output
9 USER4 «USER4» or LSCU sensor Input/Output
10 OUT1 OUT1 or LSCU sensor output
11 GND Common
1.4.3. To secure nonvolatility, lift unit has internal battery.
ATTENTION!
To connect battery to LU internal circuit connecting strip is to be used
between terminals 1 and 3 of XP4 (XS4) jack.
14
LNGS.465213.270-10 RE
XS1
Status
Manufacturer: Lift-Complex DS, JSC
ROD
RZD
RKD
KN Serial No. Issue date
KV
XP1
KN
KV
DZ
Figure. 2. Exterior of relay station adaptor
1.5.3. Printed board of relay station adaptor contains the following jacks: - ХР1: to connect
RSA to lift control station;
- ХS1: to connect RSA to lift unit.
1.5.4. Diagnosed faults
1.5.4.1. In case of lift faults, fault codes are converted by lift unit into corresponding statuses
of the Lift Monitoring & Diagnostics System.
ATTENTION!
In relay station adaptors with blue ‘Status’ LED automatic switching
to currency threshold of 24/110V is performed simultaneously at all
checkpoints (ROD, RZD, RKD, KN and KV).
15
LNGS.465213.270-10 RE
"MODE" LED
"Wi-Fi" LED
Mode setting:
"PIT"
1 2 3 4 1 2 3 4 5 6 7 8
"CAR"
GLED
YLED
CAN-G
CALL
CAN-H
CAN-P
CAN-L
FIRE
GND
SPC
BAT
MIC
Light
Name Status Designation
color
‘Pit’ mode. Power supply from internal
flashing red
battery.
‘Car’ mode. Power supply from internal
"MODE" flashing green
battery
on/lit red ‘Pit’ mode. Power supply via CAN bus.
on/lit green “Car’ mode. Power supply via CAN bus.
"Wi-Fi" on/lit red Data transfer via Wi-Fi
16
LNGS.465213.270-10 RE
on/lit green Connection with LU established via Wi-Fi
not on/lit - No connection with LU via Wi-Fi
on/lit red Data transfer via CAN
"CAN" on/lit green Connection with LU established via CAN
not on/lit - No connection with LU via CAN
Interphone connection established towards
on/lit white
dispatcher.
Interphone connection established towards
flashing white
lift unit.
"Call"
flashing
(series of 2 white Dispatcher Call registered.
flashes)
Not on/lit - No interphone, no dispatcher call registered.
Description No. of
Marking Designation
of jack output
Input for switching over to mode of fire
1 FIRE
brigades transportation
2 GLED Output to control green LED pictogram
3 YLED Output to control yellow LED pictogram
17
LNGS.465213.270-10 RE
Pressing of ‘Call’ button will make request for establishing interphone communication with
dispatcher, and voice confirmation ‘Call accepted. Wait for answer’ will follow.
SW2 2
2 1 SP1 1 XP2
4 1
LED
CAN-L
"CALL" button
LKDS
Light
Name Status Designation
color
on/lit green Connection with LU established via CAN
on/lit red ‘Call” button pressed
"LED " green/ Request for establishing interphone
flashing
red communication with dispatcher registered
flashing green Interphone communication established.
18
LNGS.465213.270-10 RE
1 2 3
Figure 5. Connection of lift unit 7.2 to external Internet/Ethernet and Wi-Fi networks
1.8.2. Configuration of internal network of lift unit ver. 7.2
To operate with external devices Lift unit ver. 7.2 organizes its internal network which can
use internal wired CAN bus and/or internal wireless Wi-Fi network (see Figure 6).
19
LNGS.465213.270-10 RE
1 2 3
1 2 3
1 2 3 4
1 2 3 4
yellow
yellow
green
green
black
black
red
red
In case of successful connection ‘Wi-Fi’ LED on intercom unit will light green.
ATTENTION!
After change of lift unit Wi-Fi password each intercom unit must be connected to
properly configured lift unit 7.2 via CAN bus to
‘educate’ and to ‘match’ once again.
A3 A3 "8"
communication device. C9
21
LNGS.465213.270-10 RE
To match load on CAN bus, resistor of 120 Ohm (‘terminator’) must be connected to terminal
devices of the bus. ‘Terminal’ is connected via jumpers only on terminal ends of CAN bus of lift
unit. Location of jumpers on printed circuit board of on-the-floor intercom unit is shown in
Figure below.
4 2 4 4 2 4
R2 7
R2 7
1 3 1 1 3 1
AN
CANH
CANL
CANL
N JP2 JP2
GD
N
GD
CH
‘Terminator’ ‘Terminator’
off on
22
LNGS.465213.270-10 RE
After reprogramming is complete, functioning tests are to be run in accordance with Section
3 of the present manual.
Manufacturer recommends periodical renewal/updating of lift unit microprograms.
1.8.12. Control of OUT1 output
Output OUT1 of lift unit can operate in four modes:
- control mode by dispatcher command;
- control mode of voice alert system (signal generated automatically);
- control mode of lift car emergency lights;
- power supply of LSCU sensor.
OUT1 output mode is shown in EEPROM of lift unit.
1.8.13. Processing of USER1…4 inputs/outputs
USER1..4 inputs of LU ver. 7.2 can be matched against one of local statuses of lift unit. By
default, USER1..4 inputs are matched against «Status USER1..4» correspondingly. Matching of
USER1...4 inputs is executed even for those statuses which are prohibited to be generated. If
several USER inputs are matched against one and the same LU status, the resulting value
would be logical ‘OR’ for USER inputs.
Value «0» prohibits matching of USER input against status, values «1..48» allow matching of
USER input against corresponding status «1..48», values «101..148» allow inverse matching of
USER input against corresponding status «1..48». Values «210..214» define the mode of
operation of USER1..4 outputs (see Table in ADDENDUM A).
1.8.14. Designation of YLED and GLED outputs of interphone communication device ver.
7.2
YLED and GLED outputs of interphone communication device ver. 7.2 are used for control
over LED indicators of yellow and green pictograms inside lift car per items 5.4.4.3 of GOST P
51361-2008 (EN 81-70:2003). Yellow pictogram lit means the emergency call has been
registered, green pictogram lit means communication channel is open (see Figure 8).
Yellow pictogram will lit when personnel call button is pressed. Green pictogram will lit when
dispatcher-to-lift car communication has been established.
YLED and GLED outputs generate voltage of 5V with current limitation of 25 mA.
23
LNGS.465213.270-10 RE
1.8.16. ‘Backup power supply of LU’ and ‘AC voltage in safety circuit’ statuses
‘Backup power supply of LU’ status is generated when lift unit switches over to backup
(battery) power supply in case of failure of mains power supply of 220V.
‘AC voltage in safety circuit’ status is generated when AC voltage is detected in checkpoint
110V (v101) of relay station adaptor. This status is generated in LU 7.2 – Р only.
1.8.17. Control over presence of passengers in lift car
In relay version of lift unit there is an algorithm introduced to detect passengers inside lift
car. With lift units using serial link, the present status is used to display presence of man in lift
car. This function is enabled by entering value «1» in address 92 of lift unit EEPROM.
1.8.18. Control over good condition of relay lift calls circuit
Lift unit design version «–P» (relay) has the function to control integrity of calls circuit. To
enable this function, ABL checkpoint of lift unit must be connected to lift circuit and function of
control must be permitted by entering value «99» to address 12 of lift unit EEPROM.
1.8.19. Audio announcements in lift car
Lift unit has the function of audio announcements in lift car. Audio announcements may be
implemented in the way of sound signal, phrase ‘Call accepted. Wait for answer’ and
announcement of floor number. Control over this function is enabled by entering values «0…7»
to address 14 of lift unit EEPROM. Value «0» turns audio announcements off, value «1» will
switch on sound signal, value «2» will switch on voice announcements, value «3» will enable
sound signal and voice announcements, value «4» will switch on floor announcement, value
«5» switches on floor announcement and sound signal; value «6» will enable floor
announcement and voice announcement, value «7» will turn on floor announcement, phrase
announcement and sound signal.
1.8.20. Sound accompaniment in lift car
Sound accompaniment in lift car function is possible with microSD memory card installed in
microSD slot of interphone communication in lift car. Supported file format: WAV.
1.8.21. Use of LSCU sensor
To use LSCU sensor it must be connected as shown in Figure 9. To allow operation of LSCU
sensor, value ‘1’ must be entered to address 94 of lift unit EEPROM. Upon receipt of permission
input/output of USER4 is registered as input for receiving data from CMSA output of LSCU
sensor, and Output OUT1 provides power supply to LSCU sensor. When value ‘1’ is entered to
address 94 EEPROM of lift unit, previously assigned usage of USER4 input/output and OUT1
output at addresses 3 and 9 of EEPROM is ignored.
24
LNGS.465213.270-10 RE
1 2 3 4
1 2 1 2 3 4 5 6 7 8 9 10 11
brown
black
gray
JP1
[CMSG]
CMSG
[CMSA]
CMSA
[VCCB]
VCCB
LSCU sensor
25
LNGS.465213.270-10 RE
1 2 3 4
1 2 1 2 3 4 5 6 7 8 9 10 11
~220V 50Hz
N L
brown
blue
А1 А2
1 3 5
КМИ-34012
2 4 6
ATTENTION!
Prior to switching on lift power supply, make sure you know the
reason why lift was turned off and remedy such cause, and make sure
there are no people in liftshaft
26
LNGS.465213.270-10 RE
2.1.3. Interphone communication with dispatcher
2.1.3.1. Communication with engine (operating) room
To make request for communication it is necessary to press and hold ‘CALL’ button on lift
unit for not less than 1.5 seconds and wait for voice confirmation of ‘Call registered. Wait for
answer’. Green LED lit means that request was registered. Pressing ‘CANCEL’ button will cancel
request fro communication from engine room. After establishment of interphone communication
by dispatcher green ‘CALL’ LED will start flashing.
2.1.3.2. Communication with lift car/top of lift car
To make request for communication it is necessary to press and hold ‘CALL’ button on lift car
panel for not less than 1.5 seconds and wait for voice confirmation of ‘Call registered. Wait for
answer’. No redirection for such communication is required.
To make request for communication from top of lift it is necessary to press and hold ‘CALL’
button on lift top panel for not less than 1.5 seconds and wait for voice confirmation of ‘Call
registered. Wait for answer’. Redirection of call is made with the help of ‘Call’ button.
2.1.4. Internal communication
2.1.4.1. Communication with pit/lower floor landing
To make request for communication it is necessary to press and hold ‘CALL’ button on
communication device of pit/lower floor landing for less that 1.5 seconds or press ‘Pit’ button on
lift unit. After initiation of communication ‘Call’ button on pit communication device will be lit
continuously, and ‘Pit’ LED will be flashing on lift unit. Redirection of call is executed with ‘Call’
button of communication device or ‘Pit’ button on lift unit. Redirection of communication is not
required when calling from lower floor landing. Communication time is limited to 3 minutes.
2.1.4.2. Communication with lift car/top of lift car
To make request for communication it is necessary to press and hold ‘CALL’ button on
communication device of pit/lower floor landing for less that 1.5 seconds or press ‘Car’ button
on lift unit. After initiation of communication ‘Call’ button on pit communication device will be lit
continuously, and ‘Car’ LED will be flashing on lift unit. Redirection of call is executed with ‘Call’
button of communication device or ‘Pit’ button on lift unit. Redirection of communication is not
required when calling from lift car. Communication time is limited to 3 minutes.
2.1.4.3. To terminate internal communication ‘Reset’ button must be pressed on lift unit.
2.1.5. Indication of causes for lift immobilization
Indication of faults leading to switching off of lift power supply is executed via ‘FAILURE’ LED
located on front panel of lift unit. The fault is defined by number of flashes of ‘FAILURE’ LED.
Interval between series of flashes is four seconds. Correspondence between failure number and
number of flashes is given in Addendum B.
When power supply is terminated by lift unit, conditions/statuses of checkpoints are
registered and can be examined in dispatcher’s program or with the help of service device (see
service device manuals).
2.1.6. Technical maintenance mode
Upon insertion of service key lift unit will be switched in technical maintenance mode.
This mode is required when implementing technical maintenance of lifts. In this mode lift
power supply is not switched off even when such status arises.
After completion of technical maintenance service key must be removed from its slot.
2.1.7. Safety measures
Electric shock protection class rating corresponds to class III per GOST 12.2.007.0 – 75.
27
LNGS.465213.270-10 RE
To operate LU are authorized persons who have undergone safety training and studied the
present operating manual.
During exploitation and technical maintenance one should take into account high voltages
inside LU, hazardous to life, so no exploitation of LU without its cover is allowed.
Switching on and off of outer circuits may be performed only with power input terminal
disconnected.
2.1.8. Servicing of battery
Battery installed in LU has limited service life (2-3 years). Upon termination of this period of
upon corresponding message the battery must be replaced.
2.1.9. Resetting to factory default settings
To return to factory default settings use a thin tool (like a paperclip) to press and hold ‘Reset’
button (see Figure 1), wait until LED start flashing and then release the button. Factory default
settings are as follows: connection type – DHCP, network key reset to www.lkds.ru, external
Wi-Fi network disconnected. Configuring lift unit is possible via USB or internal Wi-Fi network.
2.1.10. Battery connection
Lift unit and communication devices have internal batteries. To connect battery of 18650
type and with capacity of 2000 mA/h to lift unit circuit it is necessary to set jumper between
terminals 1 and 3 of XP4 (XS4) jack, as shown in Figure 11. To connect battery of 14500 type
and with capacity of 750 mA/h to lift unit circuit it is necessary to set jumper between terminals
4 and 5 of XP1 (XS1) jack, as shown in Figure 12.
1 2 3 4
1 2 1 2 3 4 5 6 7 8 9 10 11
Install jumper to
connect battery
28
LNGS.465213.270-10 RE
XP3 XP1
4 5
Install jumper to
connect battery
29
LNGS.465213.270-10 RE
dispatcher station and lift car. available.
Switch on communication with lift car from PC.
Checking of audio and visual notification on When liftshaft doors are open PC
liftshaft doors opening with no lift car on the should register audio and visual
6. floor. notification. LU should power off
3
Open liftshaft door with no lift car on the floor. lift .
Checking of audio and visual notification on When doors are open PC should
7. opening doors of engine (operating) room. register audio and visual
Open doors of engine (operating) room. notification.
1
Control of LSCU operation:
- Move lift to be controlled from ER;
- Switch on input device of lift; After start of lift movement PC
- Disconnect ‘LSCU pulses’ conductor (CMSA) should register ‘Main drive failure
8. from LSCU; (LSCU-initiated)’ status.
- Switch on input device of lift; LU should power off lift.
- SWITHC ON LIFT;
- Move lift car.
Control over unauthorized movement of lift
1
car : After start of lift movement PC
- Move lift to be controlled from ER; should register ‘Unauthorized
9. - Set lift car to medium stop; movement of car’ status.
- Wait 4 seconds to exclude car inertia; LU should power off lift.
- press release brakes lever.
30
LNGS.465213.270-10 RE
4. TECHNICAL MAINTENANCE
4.1. General directions
4.1.1. Technical maintenance is performed on scheduled preventive basis which envisages
quarterly technical maintenance.
4.1.2. Technical maintenance of equipment installed in liftshaft is performed by electro-
technician.
4.1.3. Technical maintenance of equipment installed in engine room is performed by
dispatching equipment and automatic telecontrol electro-technicians.
4.2. Safety measures
4.2.1. In the course of maintenance work requirements of technical guidance and safety
manuals are to be complied with.
4.3. Quarterly technical maintenance
4.3.1. Quarterly technical maintenance must include:
- appearance test;
- cleaning lift unit and LSCU of dust and dirt;
- checking of state of connecting wires, harnesses and contact terminals;
- checking of threaded joints.
4.4.2. In case of any faults found in the course of the above actions, dispatcher must
immediately power off lift and apply for repair work.
5. RUNNING REPAIR
5.1. During warranty period repair work will be performed at manufacturer’s
production facilities.
5.2. Warranty period of lift unit is 18 months from the day of commissioning but not more
that 24 months after the day of shipment to the consumer on condition that he complies with
the rules of transportation, storage, installation and operation as stipulated in the operating
manual and instructions on operation, commissioning, fine-tuning and run-in.
5.3. Repair of LU is to be performed by manufacturer or qualified personnel trained and
attested at manufacturer’s plant.
5.4. Repair of lift unit must be performed in technical workshop by qualified personnel. In the
course of repair operations it is necessary to protect integrated microcircuit from static
electricity.
6. STORAGE
6.1. LU of Lift Monitoring & Diagnostics System can be stored up to 6 months from the date
of manufacturing.
6.2. LU in original packing must be stored in enclosed spaces with natural ventilation, without
artificial air conditioning, with air temperature and humidity fluctuations being sufficiently
less than in the open air, located in macro-climatic regions of moderate or cold climate as
per storage regulations group 2 of GOST 15150-69.
6.3. Storage facilities must not have dust, vapor of acids or alkali, aggressive gases and
other harmful or corrosive substances.
7. TRANSPORTATION
7.1. Packed LU must be transported by closed transportation means (railway carriages,
containers, closed trucks, etc.) of any way with the exception of naval transportation, in
accordance with acting rules for transportation by this particular type of transportation.
7.2. When transported by air, LU in original packing must be stored in heated pressurized
compartments.
31
LNGS.465213.270-10 RE
7.3. Placement and fixing of boxes must ensure their stable positioning, eliminating any
possibility of their displacement and rough knocking onto each other and transportation vehicles
walls. Allowed stacking – not more than 5 crates up.
7.4. In the course of transportation it is necessary to comply with notices on transportation
crates.
7.5. Transportation and intermediate storage time should not exceed three months.
7.6. As concerns climatic impacts during transportation, Group 2 GOST 15150-69 regulations
must be followed.
7.7. After transportation under negative temperatures or in excessive humidity LU’s must be
matured under normal climatic conditions for at least 24 hours before installation and
commissioning.
32
LNGS.465213.270-10 RE
ADDENDUM A
Table 1. Algorithm of status generation, LU 7.2 - Р
33
LNGS.465213.270-10 RE
ADDENDUM A
Table 2. Lift unit parameters
36
LNGS.465213.270-10 RE
ADDENDUM A
addresses 3 and 9 of EEPROM are ignored.
96 ‘LDS’ indicator mode of operation 0 – SD only; 1 – standard
97 Main drive speed 0 – 0,35-0,8 m/sec; 1 -0,71-1,6 m/sec
98 Lift speed control type 0 – magnetic; 1 - optical
Table 4. Cross-reference of interval codes and real time.
100 msec tick One-second tick 10-second tick
Interval code Time in ticks
Time in seconds Time in seconds Time in seconds
0 0 0 0 0
1 3 0.3 3 30
2 4 0.4 4 40
3 5 0.5 5 50
4 6 0.6 6 60
5 10 1 10 100
6 15 1.5 15 150
7 20 2 20 200
8 30 3 30 300
9 40 4 40 400
10 60 6 60 600
11 80 8 80 800
12 100 10 100 1000
13 120 12 120 1200
14 160 16 160 1600
15 250 25 250 2500
37
LNGS.465213.270-10 RE
ADDENDUM A
61 Engine room intrusion sensor 161 MPR
62 ‘Call’ button in lift car or in engine room 162 CALL
63 LSCU sensor pulses present 163 CMSA
64 ‘Voice alert’ connected 164 RIN
65 ‘Lift On’ button 165 PWR
66 ‘Call’ button in engine room 166 CMP
67 USER1 input 167 USER1
68 USER2 input 168 USER2
69 USER3 input 169 USER3
70 USER4 input 170 USER4
71 RESERVED 171 -
72 RESERVED 172 -
73 220V AC power present 173 220V
74 OUT1 output status 174 OUT1
75 RESERVED 175 -
76 Upward movement attribute 176 UP
77 Downward movement attribute 177 DOWN
78 15 kg load in car 178 15KG
79 90% car load 179 90%
80 110% car load 180 110%
81 RESERVED 181 -
82 Precise stop sensor 182 DTO
83 One liftshaft door open by SD 183 UB1
84 Two liftshaft doors open by SD 184 UB2
Notes:
1. If several inputs are chosen for one and the same checkpoint, resulting value for checkpoint status will be logical ‘OR’ of all inputs.
2. Redefining of checkpoint is performed after main definition and unconditionally replaces status of man definition.
38
SBN.465213.270-10 RE
ADDENDUM B
Table 1. Complete set of LU ver. 7.2 depending on design version
Version of LU 7.2
-10 -11 -12 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23 -24 -25
Name Description Quantity
Lift unit LNGS.465213.270 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay station adaptor LNGS.465213.061-03 1 - - - - - - - - - 1 - - - -
Lift speed control unit LNGS.465213.065 1 - - - - - - - - - - - - - -
2
Resistor С2-33-1 3,3 kOhm ±5% 18 - - - - - - - - - - - - - -
Resistor С2-33-2 110 kOhm 2 - - - - - - - - - 2 - - - -
Cable LNGS.465213.060.610-02 1 - - - - - - - - - - - - - -
Cable LNGS.465213.060.610(-01) - 11 - 1 - 1 - 11 1 - 1 1 - - -
Cable LNGS.465213.060.620 - - 1 - - - - - - - - - - - -
Cable LNGS.465213.060.630 - - - - 1 - - - - - - - - - -
Cable UUL LNGS.465213.060.630-01 - - - - - - 1 - - - - - - - -
Cable LG-DSS LNGS.465213.060.640 - - - - - - - - - 1 - - - - -
Cable ELEX LNGS.465213.060.920-02 - - - - - - - - - - - - 1 - -
Cable F-F NHS LNGS.465213.060.610-08 - - - - - - - - - - - - - 1 -
Cable SPUL LNGS.465213.060.660 - - - - - - - - - - - - - - 1
LG-DI adaptor LNGS.465213.060.271-02 - - - - - - - - - 1 - - - - -
Power adaptor ~220В /+12В 2А - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-02P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-04P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-11P 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
2 2
Terminal block 2EDGK-5.08-08P 1 - - - - - - - - - 1 - - - -
Security alarm IO 102-2 (МС31) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Holder LNGS.465213.270.002 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Communication device7.2 LNGS.465213.270.500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Actuator control module 7.2 LNGS.465213.270.020 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Patchcord Crossover Ethernet cat. 5E - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Lift unit label LNGS.465213.270-ХХ ET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operating manual LNGS.465213.270-10 RE 1 pcs per batch
Installation manual LNGS.465213.270-10 IM 1 pcs per batch
Notes: 1. Cable LNGS.465213.060.610-01 (10m) supplied for machine room-less lifts 2. Not supplied with installation set. Codes: “-“ not supplied, “+/-“ – supplied on
demand, “ХХ“ - LU design version.
39
SBN.465213.270-10 RE
ADDENDUM B
Complete set of LU ver. 7.2 depending on design version (continued from Table 1)
Version of LU 7.2
-26 -27 -28 -29 -30 -31 -32 -33 -34 -35 -36 -37 -38 -39 -40
Name Description Quantity
Lift unit LNGS.465213.270 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay station adaptor LNGS.465213.061-03 - - - - - - - - - - - - - - -
Lift speed control unit LNGS.465213.065 - - - - - - - - - - - - - - -
Resistor С2-33-1 3,3 kOhm ±5% - - - - - - - - - - - - - - -
Resistor С2-33-2 110 kOhm - - - - - - - - - - - - - - -
OptoadaptoAdaptorr 12-110V LNGS.465213.060.320 - - - - - - - 2 - - - - - - -
Cable LNGS.465213.060.610(-01) 1 - - - - 1 - - - 1 - 1 - 1
Cable F-F NFS LNGS.465213.060.610-11 - 1 - - - - - - - - - - - - -
Cable DOPPLER LNGS.465213.060.670 - - 1 - - - - - - - - - - - -
Cable DOPPLER+ LNGS.465213.060.670-01 - - +/- - - - - - - - - - - - -
Cable BLT LNGS.465213.060.690 - - - 1 - - - - - - - - - - -
Cable F-F NHS LNGS.465213.060.610-08 - - - - 1 - - - - - - - - - -
Cable SCHINDLER LNGS.465213.060.610-09 - - - - - - 1 - - - - - - - -
Cable BG-15 LNGS.465213.060.640-01 - - - - - - - 1 - - - - - - -
Cable ORONA LNGS.465213.060.910 - - - - - - - - 1 - - - - - -
Cable ARKEL LNGS.465213.060.920 - - - - - - - - - - 1 - - - -
Cable F-F DFS LNGS.465213.060.610-04 - - - - - - - - - - - - - 1 -
Wire bundle LNGS.465213.060.090 - - - - - - - - - - - - 1 - -
KLEEMANN BG-15 adaptor LNGS.465213.060.280-01 - - - - - - - 1 - - - - - - -
Power adaptor ~220В /+12В 2А - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-02P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-04P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Terminal block 15EDGK-3.5-11P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 2EDGK-5.08-08P - - - - - - - - - - - - - - -
Security alarm IO 102-2 (МС31) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Holder LNGS.465213.270.002 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Communication device7.2 LNGS.465213.270.500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Actuator control module LU 7.2 LNGS.465213.270.020 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Patchcord Crossover Ethernet cat. 5E - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Lift unit label LNGS.465213.270-ХХ ЭТ 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operating manual LNGS.465213.270-10 RE 1 pcs per batch
Installation manual LNGS.465213.270-10 ИМ 1 pcs per batch
Notes: 1. Cable LNGS.465213.060.610-01 (10m) supplied for machine room-less lifts. 2. Not supplied with installation set. Codes:“-“ - not supplied, “+/-“ – supplied
on demand, “ХХ“ - LU design version.
40
SBN.465213.270-10 RE
ADDENDUM B
Complete set of LU ver. 7.2 depending on design version (continued from Table 1)
Version of LU 7.2
-41 -42 -43 -44 -45 -46 -47 -48 -49 -50 -51 -52 -53 -54 -55
Name Description Quantity
Lift unit LNGS.465213.270 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay station adaptor LNGS.465213.061-03 - - - - - - - - - - - - - - -
Lift speed control unit LNGS.465213.065 - - - - - - - - - - - - - - -
OptoadaptoAdaptorr 12-110V LNGS.465213.060.320 - 2 - - - - - - - - - - 3 - -
Cable MIK-EL LNGS.465213.060.930 1 - - - - - - - - - - - - - -
Cable F-F NHL LNGS.465213.060.610-05 - 1 - - - - - - - - - - - - -
Cable F-F NHS LNGS.465213.060.610-08 - - 1 - - - - 1 - 1 - - - - -
Cable STVF LNGS.465213.060.610-07 - - - 1 - - - - - - - - - - -
Cable F-M LNGS.465213.060.610-06 - - - - 1 - - - - - - - - - -
Cable DOPPLER LNGS.465213.060.670 - - - - - 1 - - - - - - - - -
Cable LNGS.465213.060.610(-01) - - - - - - 1 - 1 - - - - -
Cable F-F NFS LNGS.465213.060.610-11 - - - - - - - - 1 - - - - - -
Cable SILVER LNGS.465213.060.940 - - - - - - - - - - 1 - - - -
Cable ARKEL LNGS.465213.060.920 - - - - - - - - - - - 1 - - -
Cable VASSLER LNGS.465213.160.710-03 - - - - - - - - - - - - - - -
Wire bundle LNGS.465213.060.090 - - - - - - - - - - - - 1 - -
P313 AUTINOR AC-01 adaptor LNGS.465213.160.410 - - - - - - 1 - - - - - -
SWORD RS232 interface board LNGS.465213.160.400 - - - - - 1 - - - - - - - - -
Cable E9 LNGS.465213.060.610-10 - - - - - - - - - - - - - 1 -
Cable ECLIPSE LNGS.465213.060.690-01 - - - - - - - - - - - - - - 1
Power adaptor ~220В /+12В 2А - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-02P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-04P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Terminal block 15EDGK-3.5-11P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 2EDGK-5.08-08P - - - - - - - - - - - - - - -
Security alarm IO 102-2 (МС31) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Holder LNGS.465213.270.002 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Communication device7.2 LNGS.465213.270.500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Actuator control module LU 7.2 LNGS.465213.270.020 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Patchcord Crossover Ethernet cat. 5E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Lift unit label LNGS.465213.270-ХХ ET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operating manual LNGS.465213.270-10 RE 1 pcs per batch
Installation manual LNGS.465213.270-10 IM 1 pcs per batch
Notes: 1. Cable LNGS.465213.060.610-01 (10m) supplied for machine room-less lifts 2. Not supplied with installation set. Codes: “-“ - not supplied, “+/-“ – supplied on
demand, “ХХ“ - LU design version.
41
SBN.465213.270-10 RE
ADDENDUM B
Complete set of LU ver. 7.2 depending on design version (continued from Table 1)
Version of LU 7.2
-56 -57 -58 -59 -60 -61 -62 -63 -64 -65 -66 -67 -68 -69 -70
Name Description Quantity
Lift unit LNGS.465213.270 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay station adaptor LNGS.465213.061-03 - - - - - - - - - - - - - - -
Lift speed control unit LNGS.465213.065 - - - - - - - - - - - - - - -
Resistor С2-33-1 3,3 kOhm ±5% - - - - - - - - - - - - - - -
Resistor С2-33-2 110 kOhm - - - - - - - - - - - - - - -
Cable VASSLER LNGS.465213.160.710-03 1 - - - - - - - - - - - - - -
Cable TMS600 LNGS.465213.160.710 - 1 - - - - - - - - - - - - -
Cable BETACONTROL LNGS.465213.160.710-01 - - 1 - - - - - - - - - - - -
Cable TP LNGS.465213.160.710-02 - - - 1 - - - - - - - - - - -
Cable ShK6000 LNGS.465213.160.720-02 - - - - 1 - - - - - - - - - -
Cable TKL LNGS.465213.160.720 - - - - - 1 - - - - - - - - -
Cable SOYUZ LNGS.465213.160.720-01 - - - - - - 1 - - - - - - - -
Cable LLC LNGS.465213.160.720-05 - - - - - - - 1 - - - - - - -
Cable SHL-R LNGS.465213.160.710-05 - - - - - - - - 1 - - - - - -
Cable F-F DFS LNGS.465213.060.610-04 - - - - - - - - - 1 - - - - -
Cable VEK LNGS.465213.160.720-03 - - - - - - - - - - 1 - - - -
Cable KOLLMORGEN LNGS.465213.160.720-04 - - - - - - - - - - - 1 - - -
Cable THY-CMC/MCI LNGS.465213.160.710-06 - - - - - - - - - - - - 1 - 1
Cable SECURLIFT LNGS.465213.160.730 - - - - - - - - - - - - - 1 -
СМС4+ adaptor LNGS.465213.160.270-01 - - - - - - - - - - - - 1 - -
Power adaptor ~220В /+12В 2А - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-02P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 15EDGK-3.5-04P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Terminal block 15EDGK-3.5-11P 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Terminal block 2EDGK-5.08-08P - - - - - - - - - - - - - - -
Security alarm IO 102-2 (МС31) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Holder LNGS.465213.270.002 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Communication device7.2 LNGS.465213.270.500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Actuator control module LU 7.2 LNGS.465213.270.020 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Patchcord Crossover Ethernet cat. 5E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Lift unit label LNGS.465213.270-ХХ ET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operating manual LNGS.465213.270-10 RE 1 pcs per batch
Installation manual LNGS.465213.270-10 IM 1 pcs per batch
Notes: 1. Cable LNGS.465213.060.610-01 (10m) supplied for machine room-less lifts 2. Not supplied with installation set. Codes: “-“ - not supplied, “+/-“ – supplied on
demand, “ХХ“ - LU design version.
42
SBN.465213.270-10 RE
ADDENDUM B
Complete set of LU ver. 7.2 depending on design version (continued from Table 1)
Version of LU 7.2
-71 -72 -73 -74 -75 -76 -77 -78 - - - - - - -
Name Description Quantity
Lift unit LNGS.465213.270 1 1 1 1 1 1 1 1 - - - - - - -
Relay station adaptor LNGS.465213.061-03 - - - - - - - - - - - - - - -
Lift speed control unit LNGS.465213.065 - - - - - - - - - - - - - - -
Resistor С2-33-1 3,3 kOhm ±5% - - - - - - - - - - - - - - -
Resistor С2-33-2 110 kOhm - - - - - - - - - - - - - - -
Cable WIPO LNGS.465213.160.710-07 1 - - - - - - - - - - - - - -
Cable KLST LNGS.465213.160.720-06 - 1 - - - - - - - - - - - - -
Cable ELCO MICRO LNGS.465213.160.710-08 - - 1 - - - - - - - - - - - -
Cable ARKEL LNGS.465213.060.920 - - - 1 - - - - - - - - - - -
Cable BL6 LNGS.465213.160.730-01 - - - - 1 - - - - - - - - - -
Cable WEBER LNGS.465213.160.710-10 - - - - - 1 - - - - - - - - -
Cable GTE LNGS.465213.160.710-11 - - - - - - 1 - - - - - - - -
Cable DAESUNG LNGS.465213.160.730-02 - - - - - - - 1 - - - - - - -
Cable LNGS.465213.060.610(-01) - - - - - - - - - - - - - - -
Power adaptor ~220В /+12В 2А - 1 1 1 1 1 1 1 1 - - - - - - -
Terminal block 15EDGK-3.5-02P 1 1 1 1 1 1 1 1 - - - - - - -
Terminal block 15EDGK-3.5-04P 1 1 1 1 1 1 1 1 - - - - - - -
Terminal block 15EDGK-3.5-11P 12 12 12 12 12 12 12 12 - - - - - - -
Terminal block 2EDGK-5.08-08P - - - - - - - - - - - - - - -
Security alarm IO 102-2 (МС31) 1 1 1 1 1 1 1 1 - - - - - - -
Holder LNGS.465213.270.002 1 1 1 1 1 1 1 1 - - - - - - -
Communication device7.2 LNGS.465213.270.500 1 1 1 1 1 1 1 1 - - - - - - -
Actuator control module LU 7.2 LNGS.465213.270.020 1 1 1 1 1 1 1 1 - - - - - - -
Patchcord Crossover Ethernet cat. 5E 1 1 1 1 1 1 1 1 - - - - - - -
Lift unit label LNGS.465213.270-ХХ ET 1 1 1 1 1 1 1 1 - - - - - - -
Operating manual LNGS.465213.270-10 RE 1 pcs per batch
Installation manual LNGS.465213.270-10 IM 1 pcs per batch
Notes: 1. Cable LNGS.465213.060.610-01 (10m) supplied for machine room-less lifts 2. Not supplied with installation set. Codes: “-“ - not supplied, “+/-“ – supplied on
demand, “ХХ“ - LU design version.
43
SBN.465213.270-10 RE
ADDENDUM C
Types of inputs/outputs of LU ver. 7.2 and options of their usage
Vcc (+5V) Vcc (+5V) Vcc (+5V) Vcc (+5V) Vcc (+5V) Vcc (+5V)
USER 1 100K
USER 2 100K
USER 3 100K
Maximum output current 200mA Maximum output current 200mA Maximum output current 200mA
DC IN
Vcc (+5V) Vcc (+5V)
V2 (+5V)
10K
USER 4 100K
P6SMB6,8A
CAN PWR
OUT 1
Maximum output current defined by
-
Maximum output current 200mA Maximum output current 200mA power source but must not exceed 4A
44